41
Checking System Charge
Units are shipped with full operating charge. If recharging is
necessary:
1. Insert thermometer bulb in insulating rubber sleeve on liquid
line near filter drier. Use a digital thermometer for all
temperature measurements. DO NOT use a mercury or
dial-type thermometer.
2. Connect pressure gage to discharge line near compressor.
3. After unit conditions have stabilized, read head pressure on
discharge line gauge.
NOTE: Operate unit a minimum of 15 minutes before
checking
charge.
From
standard
field-supplied
Pressure-Temperature chart for R-410A, find equivalent
saturated condensing temperature.
4. Read liquid line temperature on thermometer; then subtract
from saturated condensing temperature. The difference
equals subcooling temperature.
Refrigerant Charging
NOTE: Do not vent or depressurize unit refrigerant to
atmosphere. Remove and recover refrigerant following accepted
practices.
TROUBLESHOOTING
When troubleshooting problems arise with a WSHP, refer to
Table 11 for fault codes. See Table 12 for troubleshooting solu
-
tions. The UPM on each unit includes an alarm indicator with
blink codes to indicate UPM fault.
Table 11 —
Fault Codes
WARNING
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system — this
can cause compressor flooding.
BLINK CODE
SINGLE COMPRESSOR
SIZES 025-071, 180, AND 210
DUAL COMPRESSOR
SIZES 122, 240-420
One Blink
High Pressure
High Pressure 1
Two Blinks
Low Pressure
Low Pressure 1
Three Blinks
Source Side Freeze
High Pressure 2
Four Blinks
Not Used on PSW
Low Pressure 2
Five Blinks
Brown Out
Freeze (Load or Source)
Six Blinks
Load Side Freeze
Not Used on These Sizes
Seven Blinks
Not Used on These Sizes
Brown Out
Summary of Contents for Aquazone 50PSW025
Page 15: ...15 Fig 9 Unit Size 122 1 Phase Complete C Deluxe D Control Package DWG No 50PSW120000 Rev 3 ...
Page 17: ...17 Fig 11 Unit Sizes 122 1 Phase W2W Open Control Package DWG No 50PSW120001 Rev 4 ...
Page 21: ...21 Fig 15 Unit Size 122 240 420 3 Phase W2W Open Control Package DWG No 50PSW320001 Rev 3 ...
Page 36: ...36 Fig 22 W2W Open Control Board ...
Page 37: ...37 Fig 23 Unit Protection Module UPM Sequence Of Operation ...