41
Table 9 —
Low Voltage VA Draw
UPM Dip Switch Settings
The DIP switches are used to configure most of the available fea
-
tures of the UPM as follows:
• Lockout mode: two (2) or four (4) strikes
• Reset mode: Y signal or R signal
• Alarm mode: Constant or Pulse
• Test mode: Normal or Test operation
Figure 36 shows the factory default settings for most heat
pump applications. However, the unit wiring diagram is the ul
-
timate guide for factory DIP switch default settings. See the
Unit Protection Module section in the Troubleshooting section
for further details.
Fig. 36 —
Typical DIP Switch Factory Defaults
Table 10 below shows the available options on the UPM board
DIP switch banks.
Table 10 —
UPM DIP Switch Options
Alarm Output
Alarm output is normally open (NO) dry contact. If pulse is select
-
ed the alarm output will be pulsed. The fault output will depend on
the DIP switch setting for ALARM. If it is set to CONST, a con
-
stant signal will be produced to indicate a fault has occurred and
the unit requires inspection to determine the type of fault. If it is
set to PULSE, a pulse signal is produced and a fault code is detect
-
ed by a remote device indicating the fault. The remote device must
have a malfunction detection capability when the UPM board is
set to PULSE.
WATERSIDE ECONOMIZER (ETO)
When the waterside economizer option is built with the Complete
C or Deluxe D controls, it will include an aquastat for economizer
control. The aquastat can be adjusted between 20°F and 60°F.
When the water loop temperature is below the aquastat set point,
the economizer is enabled. The recommended aquastat set point is
55°F. See Fig. 37.
BOILERLESS HEAT CONTROL (DELUXE D ONLY)
All units with Deluxe D control include an aquastat for boilerless
heat control. The aquastat can be adjusted between 20°F and 60°F.
When the water loop temperature is below the aquastat set point,
the heat pump heating is disabled and a field provided auxiliary
heat can be enabled. The recommended aquastat set point is 55°F.
See Fig. 37.
Fig. 37 —
Aquastat for Waterside Economizer and
Boilerless Control
STANDARD CONSTRUCTION
HOT GAS REHEAT OR ECONOMIZER
OPTIONAL COMPONENTS
Component
VA
Component
VA
Component
VA
Blower Relay
(PSC Motors Only)
6-7
Total from ‘Standard’
22-26
Monitor Relay (VA draw
per relay)
6-7
Reversing Valve
Solenoid
8-9
Additional Control
Relays
12-14
Internal 2 Way
Motorized Valve
7
Compressor Contactor
6-8
Hot Gas Reheat
Solenoid
8-9
UPM Board
2
—
—
Total VA Draw
22-26
Total VA draw
42-49
SWITCH
NUMBER
DIP SWITCH
ON
OFF
4
LOCKOUT
4
2
3
RESET
R
Y
2
ALARM
CONT
PULSE
1
TEST
YES
NO
CAUTION
Operation of unit in test mode can lead to accelerated wear and
premature failure of components. The "TEST" switch must be
set back to "NO" after troubleshooting/servicing.
IMPORTANT: If 24 VAC output is needed R must be wired to
ALR-COM terminal; 24 VAC will be available to the
ALR-OUT terminal when the unit is in the alarm condition.
Summary of Contents for AQUAZONE 50PSH
Page 17: ...17 Fig 15 PSC Motor Single Phase Single Stage WSHP Open Control ...
Page 20: ...20 Fig 18 Constant Torque Motor Single Phase Single Stage WSHP Open Control ...
Page 23: ...23 Fig 21 Constant Airflow Single Phase WSHP Open ...
Page 26: ...26 Fig 24 PSC Motor Three Phase Single Stage WSHP Open ...
Page 29: ...29 Fig 27 Constant Torque Motor Three Phase Single Stage WSHP Open ...
Page 32: ...32 Fig 30 Constant Airflow Motor Three Phase Single Stage WSHP Open ...