Typical wiring schematics (cont)
MANUAL CHANGEOVER WITH DELUXE D CONTROLLER
FP2
CAP
PB
DELUXE D
CONTROL
BR 2
(HI)
UMT
PBS
OS
GROUND
LOG
TRANSFORMER
CR
BR 1
(LO)
S
JW1
LP
TEST
PINS
JW2
FP2
JW3
FP1 LOW
LOW
N.O.
ACC1
FUNCTIONS
ACC2
FUNCTIONS
H: HI FAN/DEHUMID
NOT USED
OFFON
S2
DIP SWITCH PACKAGE
S1
DIP SWITCH PACKAGE
OFFON
PM: DISABLE/ENABLE
UNIT STAGE: 2/1
T’STAT: HEAT COOL/HEAT PUMP
RV ON B/RV ON O
DEHUMID/NORMAL
NOT USED
BOILERLESS: ENABLE/DISABLE
BOILERLESS: 40
°
F/50
°
F
SEE
NOTE 4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Y1
O/W2
G
R
C
AL1
W1
AL2
A
P3
R
C
ALARM
RELAY
SEE
NOTE 6
SEE
NOTE 7
NSB
ESD
OVR
H
P2
C
R
Y2
P1
R
R
COM
NC2
NO2
COM
NC1
NO1
RELAY
ACC1
RELAY
ACC2
1
2
3
4
5
6
7
8
COM2
COM1
R C S
C
JW4
AL2
DRY
RED
RED
2
3
2A
ORG
3A
RED GRY
YEL
ORG
YEL
UMT
2
3
PBS
1A
1B
YEL YEL YEL
ORG
DM
BRN
BRN
RED
TIME CLOCK
CLOSED-UNOCCUPIED
BRN
GRY
YEL
WHT
WV
WHT
RED
OS
NLL
GRY
GRY
PBS
RED
5
6
5A
6A
RED
7
7A
RED
GRY
P7
P6
CCG
24V
DC
EH1
EH2
BRN
CC
YEL
CR
1
COMPR
RELAY
0
FAN
E N A B L E
RELAY
STATUS
TEST
FAULT
G
DELUXE D
MICROPROCESSOR
CONTROL LOGIC
1
2
RV RELAY
3
4
5
7
9
10
HP
L O C
FP1
RV
C O
HP
LOC
FP1
BRN
ORG
YEL
VIO
SEE
NOTE 4
FP2
CO
Y
R
GRY
C O M
NO
NC
COM
NO
FAN
S P E E D
R E L A Y
GRY
RED
RED
12
8
6
NOT USED
RVS
BLU
BRN
VIO
GRY
YEL
BLU
1
BLK
RED
BLK
ORG
230V
24V
TRANS
CB*
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
GROUND
L2
L1
OPTIONAL
CORD
CONNECTION
RED
NEUTRAL ON 265V
SYSTEMS
L2 (ribbed)
GROUND
L1 (plain)
PB
1
2
H
C
F
CAP
RED
RED
6
8
2
4
BLK
BLK
R
S
C
CR
BLU
COMPRESSOR
BRN
YEL
2
1
BM
B (HIGH)
A (LOW)
BLK
115
208
230
265
WHT
RED
ORG
BRN
LEAD COLOR
VOLTAGE
TRANSFORMER PRIMARY
LEAD COLORS
GRY
SEE
NOTE 3
PUSH BUTTON SWITCH ATTRIBUTES
X = CLOSED
O = OPEN
TERMINALS
1
2
3
4
5
6
7
8
1A 1B 2A 3A 4A 5A 6A 7A 8A
STOP
X O O O O O O O O
FAN ONLY
X O O O O X O O O
LOW COOL
O X X O O O X O O
HIGH COOL
O X X O O O O X O
LOW HEAT
X O O X X O X O O
HIGH HEAT
X O O X X O O X X
BLOWER MOTOR WIRING
UNIT SIZE
POLE A
POLE B
07
5
3
09
5
4
12
4
3
15
4
3
19
4
3
AL
—
Alarm Relay Contacts
BM
—
Blower Motor
BR
—
Blower Relay
CAP
—
Capacitor
CB
—
Circuit Breaker
CO
—
Sensor, Condensate Overflow
CR
—
Compressor Relay
DM
—
Damper Motor
FP1
—
Sensor, Water Coil Freeze Protection
FP2
—
Sensor, Air Coil Freeze Protection
HP
—
High-Pressure Switch
JW1
—
Jumper Wire for Alarm
LOC
—
Loss of Charge Pressure Switch
NLL
—
Night Low Limit Switch
OS
—
Override Switch
PB
—
Power Terminal Block
PBS
—
Push Button Switch
PM
—
Performance Monitor
RVS
—
Reversing Valve Solenoid
TRANS
—
Transformer
UMT
—
Unit Mounted Thermostat
WV
—
Water Valve
----------
Field Line Voltage Wiring
Field Low-Voltage Wiring
LEGEND
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
>>
*Optional wiring.
NOTES:
1.
Compressor and blower motor thermally protected
internally.
2.
All wiring to the unit must comply with local codes.
3.
Transformer is wired to 115-V (WHT) lead for 115/1/60
units, 265-V (BRN) lead for 265/1/60 units or 208-V
(RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1 and insu-
late RED lead.
Transformer is energy limiting or may have circuit
breaker.
4.
FP1 thermistor provides freeze protection for WATER.
When using ANTI-FREEZE solutions, cut JW3 jumper.
5.
Typical unit-mounted thermostat wiring shown.
6.
24-V alarm signal shown. For dry alarm contact, cut AL2
DRY (JW4) jumper and dry contact will be available
between AL1 and AL2.
7.
Transformer secondary ground via Deluxe D board
standoffs and screws to control box. (Ground available
from top two standoffs as shown.)