17
Table 5 — Blower Data — 50HQP072
LEGEND
NOTES:
1. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C =
High Rpm/Standard Motor.
2. Unit factory shipped with standard static sheave and drive at 2.5 turns
open. Other speed require field selection.
3. For applications requiring higher static pressures, contact your local rep-
resentative. Performance data does not include drive losses and is based
on sea level conditions.
4. All airflow is rated at lowest voltage if unit is dual voltage rated, i.e., 380V
for 380/420V units.
5. Airflow in l/s with wet coil and clean filter.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0
25
50
75
100
125
150
175
200
225
250
275
300
325
350
375
614
BkW
—
—
0.09
0.12
0.14
0.17
0.19
0.21
0.24
0.25
0.27
0.29
0.31
0.32
0.34
0.35
Sheave/Mtr
—
—
B
A
A
A
A
A
C
C
C
C
C
C
C
C
RPM
—
—
505
563
615
655
695
730
765
790
815
840
870
890
910
925
Turns Open
—
—
3
5
3.5
3
2
1
5
4.5
4
3.5
2.5
2.5
2
1.5
661
BkW
—
0.12
0.14
0.17
0.19
0.22
0.24
0.26
0.29
0.30
0.33
0.34
0.36
0.38
0.40
—
Sheave/Mtr
—
B
A
A
A
A
C
C
C
C
C
C
C
C
C
—
RPM
—
526
578
635
675
715
755
785
815
840
870
890
910
930
950
—
Turns Open
—
2
4.5
3
2.5
1.5
5
4.5
4
3.5
3
2
2
1.5
1
—
708
BkW
0.12
0.14
0.17
0.19
0.22
0.25
0.27
0.29
0.32
0.34
0.36
0.38
0.41
0.43
—
—
Sheave/Mtr
B
B
A
A
A
A
C
C
C
C
C
C
C
C
—
—
RPM
500
547
604
650
695
735
775
805
835
865
890
915
940
960
—
—
Turns Open
3
1.5
4
3
2
1
4.5
4
3.5
3
2.5
2
1.5
1
—
—
755
BkW
0.14
0.17
0.19
0.22
0.25
0.27
0.29
0.32
0.34
0.37
0.39
0.41
0.44
—
—
—
Sheave/Mtr
B
B
A
A
A
A
C
C
C
C
C
C
C
—
—
—
RPM
510
568
620
665
710
750
785
820
855
885
910
935
960
—
—
—
Turns Open
2.5
1
3.5
2.5
1.5
1
4.5
3.5
3
2.5
2
1.5
1
—
—
—
802
BkW
0.16
0.19
0.22
0.24
0.27
0.29
0.32
0.34
0.36
0.39
0.42
0.44
—
—
—
—
Sheave/Mtr
B
A
A
A
A
C
C
C
C
C
C
C
—
—
—
—
RPM
531
583
635
680
720
765
800
835
870
900
925
950
—
—
—
—
Turns Open
2
4.5
3.5
2.5
1.5
5
4
3.5
2.5
2
1.5
1
—
—
—
—
850
BkW
0.15
0.18
0.21
0.24
0.26
0.29
0.31
0.34
0.36
0.39
0.42
0.45
—
—
—
—
Sheave/Mtr
B
B
A
A
A
A
C
C
C
C
C
C
—
—
—
—
RPM
500
547
599
645
690
735
775
815
850
885
910
940
—
—
—
—
Turns Open
3
1.5
4
3
2
1
5
4
3
2.5
2
1.5
—
—
—
—
897
BkW
0.18
0.21
0.23
0.27
0.30
0.33
0.36
0.40
0.43
0.46
0.49
0.52
—
—
—
—
Sheave/Mtr
B
B
A
A
A
A
C
C
C
C
C
C
—
—
—
—
RPM
510
557
604
655
695
740
780
820
855
890
920
950
—
—
—
—
Turns Open
2.5
1.5
4
3
2
1
4.5
3.5
3
2
1.5
1
—
—
—
—
944
BkW
0.21
0.23
0.26
0.29
0.33
0.37
0.41
0.44
0.48
0.50
0.54
0.56
—
—
—
—
Sheave/Mtr
B
B
A
A
A
C
C
C
C
C
C
C
—
—
—
—
RPM
521
568
615
660
705
750
785
825
865
895
930
960
—
—
—
—
Turns Open
2.5
1
3.5
2.5
1.5
5.5
4.5
3.5
2.5
2
1.5
1
—
—
—
—
991
BkW
0.25
0.28
0.32
0.34
0.37
0.40
0.44
0.48
0.52
0.55
0.58
—
—
—
—
—
Sheave/Mtr
B
A
A
A
A
C
C
C
C
C
C
—
—
—
—
—
RPM
536
583
630
670
715
755
795
835
875
905
940
—
—
—
—
—
Turns Open
2
4.5
3.5
2.5
1.5
5
4
3.5
2.5
2
1
—
—
—
—
—
1038
BkW
0.28
0.30
0.34
0.37
0.41
0.45
0.48
0.52
0.56
0.59
0.62
—
—
—
—
—
Sheave/Mtr
A
A
A
A
A
C
C
C
C
C
C
—
—
—
—
—
RPM
557
599
645
685
730
770
810
850
885
915
950
—
—
—
—
—
Turns Open
5
4
3
2
1
5
4
3
2.5
1.5
1
—
—
—
—
—
1086
BkW
0.32
0.35
0.38
0.42
0.45
0.48
0.52
0.56
0.60
0.63
0.67
—
—
—
—
—
Sheave/Mtr
A
A
A
A
A
C
C
C
C
C
C
—
—
—
—
—
RPM
573
620
660
705
745
785
820
860
895
925
960
—
—
—
—
—
Turns Open
4.5
3.5
3
1.5
1
4.5
3.5
3
2
1.5
1
—
—
—
—
—
1133
BkW
0.36
0.39
0.43
0.46
0.49
0.54
0.58
0.62
0.65
0.69
—
—
—
—
—
—
Sheave/Mtr
A
A
A
A
C
C
C
C
C
C
—
—
—
—
—
—
RPM
609
645
690
730
765
805
845
880
910
945
—
—
—
—
—
—
Turns Open
4
3
2.5
1.5
5
4
3
2.5
2
1
—
—
—
—
—
—
1180
BkW
0.39
0.42
0.46
0.49
0.54
0.58
0.62
0.66
0.70
0.73
—
—
—
—
—
—
Sheave/Mtr
A
A
A
A
C
C
C
C
C
C
—
—
—
—
—
—
RPM
620
660
700
740
780
815
850
885
920
950
—
—
—
—
—
—
Turns Open
3.5
3
2
1
4.5
4
3
2.5
1.5
1
—
—
—
—
—
—
—
—
Operation Not Recommended
BkW —
Brake Kilowatts
ESP —
External Static Pressure
RPM —
Revolutions Per Minute
A
—
Units with Standard Rpm/Standard Motor Option
B
—
Units with Low Rpm/Standard Motor Option
C
—
Units with High Rpm/Standard Motor Option
a50-8544
Summary of Contents for AQUAZONE 50HQP072
Page 33: ......