21
7.2 -
Configuration menu
Icon
Displayed text*
Description
Associated table
Genunit Config
General configuration
GENCONF
Pump Configuration
Pump configuration
PUMPCONF
Heat/Cool Config
Heat/Cool configuration
HCCONFIG
HDC Configuration
Heating Device Control configuration
HDC_CONF
Reset Config
Reset configuration
RESETCFG
User Configuration
User configuration
USERCONF
Schedule
Schedule menu
SCHEDULE
Holiday
Holiday menu
HOLIDAY
Broadcast
Broadcast configuration
BROCASTS
Date/Time
Date/time configuration
DATETIME
Control Identification
Control identification
CTRL_ID
*Depends on the selected language (English by default).
CAUTION:
Since specific units may not include additional features, some tables may contain parameters that cannot be
configured for a given unit.
Genunit Config Menu – GENCONF
No. Point name
Status
Default
Unit
Displayed text*
Description
1
lead_cir
0 to 2
0
-
Cir Priority Sequence
Circuit priority
2
0=Auto 1=A Lead 2=B Lead
0 = Automatic circuit selection
1 = Circuit A priority
2 = Circuit B priority
3
seq_typ
no / yes
no
-
Staged Loading Sequence
Staged loading sequence
4
ramp_sel
no / yes
no
-
Ramp Loading Select
Ramp loading selection
5
off_on_d
1 to 15
1
min
Unit Off to On Delay
Unit Off to On delay
6
nh_limit
0 to 100
100
%
Night Capacity Limit
Night capacity limit
7
nh_start
00:00
00:00
-
Night Mode Start Hour
Night mode start hour
8
nh_end
00:00
00:00
-
Night Mode End Hour
Night mode end hour
*Depends on the selected language (English by default).
Pump Configuration Menu – PUMPCONF
No. Point name
Status
Default
Unit
Displayed text*
Description
1
COOLER PUMP
EVAPORATOR PUMP
2
clpmpseq
0 to 4
0
-
Cooler Pumps Sequence
Evaporator pumps sequence
3
0 = No Pump
0 = No Pump
4
1 = One Pump Only
1 = One Pump Only