6 - aPPlICaTION DaTa
6.1 - Unit operating range
Cooling mode
Water heat exchanger (evaporator)
Minimum
Maximum
Entering water temperature at start-up
°C
6.8*
30
Leaving water temperature during operation °C
5
15
Entering water temperature at shut-down
°C
-
60
air heat exchanger (condenser)**
Air entering temperature
°C
0
46
Available static presssure
Pa
0
0
heating mode
Water heat exchanger (condenser)
Minimum
Maximum
Entering water temperature at start-up
°C
8
45
Leaving water temperature during operation °C
20
50
Entering water temperature at shut-down
°C
3
60
air heat exchanger (evaporator)
Air entering temperature**
°C
-10
35
Notes:
Do not exceed the maximum operating temperature.
*
For applications requiring a temperature below 6.8°C, please contact Carrier.
** For operation down to -20°C the unit must be equipped with option 28
(winter operation). In addition the unit must either be equipped with the frost
protec-tion option or the water loop must be protected by the installer by
adding a frost protection solution.
Maximum outside temperatures:
During storage and transport the minimum
and maximum temperatures must not exceed -20°C and +48°C. It is recom-
mended to observe these temperatures during transport by container.
Operating range 30RQ
Cooling mode
ATTENTION: Option 28 “Winter operation”
If the outside temperature is below -10°C and the unit has
been switched off for more than 4 hours, it is necessary to
wait 2 hours after the unit has been switched on again to
allow the frequency converter to warm up.
6.2 - Minimum chilled water flow (units without
hydronic module)
The minimum chilled water flow is shown in the table on the
next page. If the system flow is less than this, the water heat
exchanger flow can be recirculated, as shown in the diagram.
legend
1
Water heat exchanger
2
Recirculation
6.3 - Maximum chilled water flow (units without
hydronic module)
The maximum chilled water flow is shown in the table on the
next page. If the system flow exceeds the maximum value, it
can be bypassed as shown in the diagram.
For maximum chilled water flow rate
Leaving water heat exchanger water temperature, °C
Entering air temperatur
e, °C
Leaving air heat exchanger water temperature, °C
Entering air temperatur
e, °C
heating mode
Note:
Water heat exchanger and air heat exchanger
∆
T = 5 K
legend:
Standard unit operating at full load.
Operating range for units equipped with option 28 “Winter operation”:
Moreover the unit must either be equipped with the water heat exchanger
frost protection option or the water loop must be protected against frost by
the installer, using an anti-freeze solution.
legend
1
Water heat exchanger
2
Bypass
-20
15
1
2
1
2