![Carrier AQUASnap 30RB Controls And Troubleshooting Download Page 103](http://html.mh-extra.com/html/carrier/aquasnap-30rb/aquasnap-30rb_controls-and-troubleshooting_2560210103.webp)
103
4.3.12 - DESCRIPTION OF THE ALARMS MENU
This menu is used to display and reset up to 5 active
alarms. It also permits alarm reset. If no alarm is active
this menu is not accessible.
4.3.13 - DESCRIPTION OF THE ALARMS HISTORY MENU
4.3.14 - DESCRIPTION OF THE RUNTIME MENU
4.3.14.1 - DESCRIPTION OF THE RUNTIMES 1 MENU
BROADCAST CONFIGURATION SUB-MENU (broAdCASt)
ITEM #
FORMAT
COMMENTS
0
broAdCASt MEnu
When selected this item authorises a return to the main menu.
1
YES/no
Determines whether or not the unit is a
broadcast acknowledger
when the unit is connected on a CCN network. There must be only
one broadcast acknowledger
in a CCN.
Warning
: if the unit operates in standalone mode (not CCN connected) this choice must be set to Ye s if the holiday function is used
(see section 4.3.11.6) or if you want to configure the daylight saving time function.
2
0/1/2
This item permits
activation or deactivation of the broadcast mode
.
0 = the controller is not the broadcaster, and it is not useful to configure another selection in this table.
1 = broadcasts time, date, holidays and the outside temperature.
2 = for chillers only. Summertime and holidays are not taken into consideration without broadcasting the information on the bus
.
3
nnn
OAT Broadcaster bus number
: it is the bus number of the system that has the outside air temperature sensor connected to it.
4
nnn
OAT Broadcaster element number
: it is the element number of the system element that has the outside air temperature sensor
connected to it.
ITEM #
0 [1]
1 [1]
2 [1]
3 [1]
4 [1]
5 [1]
FORMAT
X ALArM
rESEt ALArM
Alarm code text
Alarm code text
Alarm code text
Alarm code text
Alarm code text
COMMENTS
X alarms are active
Reset of alarms is requested
To reset all active alarms, continuously press
the Enter key. ‘rESETALArM’ is then displayed.
Press the select key again: all alarms are reset.
Current alarm code 1**
Current alarm code 2**
Current alarm code 3**
Current alarm code 4**
Current alarm code 5**
ALARMS MENU
1
This item is masked when nil
*
See section “Alarm codes”
**
Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
“time of alarm” “date of alarm” “full CCN alarm message”
- “time of alarm”: xxhmm
- “date”: dd-mm
- “full CCN alarm message”: up to 64 characters
1
This item is masked when nil
*
See section “Alarm codes”
**
Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
“time of alarm” “date of alarm” “full CCN alarm message”
- “time of alarm”: xxhmm
- “date”: dd-mm
- “full CCN alarm message”: up to 64 characters
ITEM #
0 [1]
1 [1]
2 [1]
3 [1]
4 [1]
5 [1]
6 [1]
7 [1]
8 [1]
9 [1]
10 [1]
....
19 [1]
FORMAT
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
Alarm code text*
....
Alarm code text*
COMMENTS
Alarm history code 1**
Alarm history code 2**
Alarm history code 3**
Alarm history code 4**
Alarm history code 5**
Alarm history code 6**
Alarm history code 7**
Alarm history code 8**
Alarm history code 9**
Alarm history code 10**
Alarm history code 10**
....
Alarm history code 20**
ALARMS HISTORY MENU
RUNTIMES 1
[runtiMES 1]
MAINTENANCE
[MAintEnAnCE]
RUNTIMES 2
[runtiMES 2]
RUNTIMES 3
[runtiMES 3]
RUNTIMES
ITEM #
0
1
2
3 [1]
4 [1]
5 [1]
6
7
8 [1]
9 [1]
10
11
12 [1]
13 [1]
14 [1]
15
16
17 [1]
18 [1]
FORMAT
RuntiME 1 menu
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
nnnn | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
- | M 10 | M100
UNITS
-
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
hrs/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
-/10 or 100
COMMENTS
When selected this item
authorises return to the
previous menu
Unit operating hours*
Compressor A1 operating
hours*
Compressor A2 operating
hours*
Compressor A3 operating
hours*
Compressor A4 operating
hours*
Compressor B1 operating
hours*
Compressor B2 operating
hours*
Compressor B3 operating
hours*
Compressor B4 operating
hours*
Machine starts*
Compressor A1 starts*
Compressor A2 starts*
Compressor A3 starts*
Compressor A4 starts*
Compressor B1 starts*
Compressor B2 starts*
Compressor B3 starts*
Compressor B4 starts*
RUNTIMES MENU [1]
1
This item is masked when not used
NOTES
*
Certain values are divided by 10 or by 100, so that number of hours or start-
ups of less then 10 are displayed as 0.
When the value is divided by 10 or by 100 it is displayed in turn with “M 10” or
“M100”.