23

Step 1 — Inspect Shipment — 

Inspect the unit for

damage or missing parts. If damaged, or if shipment is incom-

plete, file a claim immediately with the shipping company.

Step 2 — Position the Unit — 

The unit may be

moved by means of rollers under the rails or a forklift truck.

If accessory mobility kit is to be used, install this accessory

after bringing the unit into the building and before moving the

unit to its final location per installation instructions provided

with the accessory. The factory-installed mobility kit option

consists of 6 swivel-type wheels that are field-mounted to the

legs of the unit. See Fig. 20.
NOTE: The wheels are equipped with a thumb-screw brake.

Fig. 20 — Mobility Kit

Step 3 — Place the Unit

NOTE: These units are not suitable for unprotected outdoor

use.

Carrier recommends that these units be located in the base-

ment or on the ground floor. However, if it is necessary to lo-

cate the unit on an upper floor, be sure the structure has been

designed to support the unit weight. If necessary, add structural

support to floor. Also, be sure the surface for installation is

level. Refer to Fig. 6-18 for space requirements and weight

distribution.

Only electrical power connections, controls, water connec-

tions for condenser, fluid connections for evaporator, and

strainer installation are required for 30MPW installation. In-

stallation of 30MPA units varies only in field piping required

for the remote condenser instead of a water connection.

When the unit is in its final position, remove the packaging

and remove the mobility kit wheels (if equipped). Remove the

3

/

8

-in. wheel nuts to remove the wheels from the unit legs. Lev-

el the unit (using a level), and bolt the unit to the floor or pad.

If unit is to be mounted on unit external vibration

isolators, follow the mounting instructions included with

the accessory vibration isolator.

If the unit has accessory leveling kit installed, follow the in-

structions provided with the accessory to make sure the unit is

level and in the correct position. The leveling kit is included

with all manifold units.

Step 4 — Check Compressor Mounting

30MP016-030, 040-045 UNITS — As  shipped,  30MP016-

030 units with two compressors are held down with six bolts

through rubber grommets. All 30MP040,045 units with three

compressors are held down with eight bolts per pair through

grommets. 

After unit is installed, verify that mounting bolt torque is 7

to 10 ft-lb (9 to 14 Nm). See Fig. 21.
30MP032 UNITS — For 30MP032 units, eight RED shipping

bolts must be removed from the compressor mounting rail.

These RED bolts are for shipping purposes only, see Fig. 22.
30MP050-071 UNITS — For 30MP050-071 units, two RED

shipping bolts from the compressor mounting rail must be re-

moved. These RED bolts are for shipping purposes only. See

Fig. 23.

Fig. 21 — Compressor Holddown Bolts

(Sizes 016-030, 040-045)

CAUTION

Unit is top heavy. Unit may tip if handled without care.

Damage to unit or injury may result.

BOLT

WASHER

NUT

LOCK WASHER

WASHER

COMPRESSOR
RACK HOLD 
DOWN BOLTS
TYPICAL 
BOTH SIDES

DO NOT REMOVE

A

SECTION A - A

A

A30-5624

COMPRESSOR
RACK HOLD 
DOWN BOLTS
TYPICAL 
BOTH SIDES

DO NOT REMOVE

SECTION A-A

UNIT SIZES 016-030

UNIT SIZES 040-045

Summary of Contents for AquaSnap 30MPA050

Page 1: ...controls The 30MPA units are condenserless units and the 30MPW units are fluid cooled See Fig 1 4 for dif ferent unit configurations See Fig 5 for model number no menclature and Fig 6 19 for unit dim...

Page 2: ...2 Fig 1 30MPA Unit Size 020 045 a30 6023 Fig 2 30MPA Unit Size 050 071 a30 6024 Fig 3 30MPW Unit Size 016 045 a30 6025 Fig 4 30MPW Unit Size 050 071 a30 6026...

Page 3: ...Interrupt High Condensing and Hot Gas Bypass 071 71 250 2 Fused Disconnect Switch selected models 0 Comfort Cooling Duty 32 60 F 0 0 16 5 C Std 1 Water Manifold Piping Includes Combination Valve 2 Wa...

Page 4: ...to the nearest beams Additional weight of factory installed sound enclosure op tion is 75 lb 34 kg Additional operating weight of 30MPA water manifold option is 218 lb 99 kg Additional operating weigh...

Page 5: ...37 48 952 0 mm 30MPA071 1506 683 kg 14 31 363 4 mm 27 30 693 4 mm 38 08 967 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions are shown i...

Page 6: ...59 9 mm 27 39 695 7 mm 37 48 952 0 mm 30MPA071 1506 683 kg 14 31 363 4 mm 27 30 693 4 mm 38 08 967 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3...

Page 7: ...h local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding charge Field removal of tube and reducing coupling is required Consult Installation Instructions for...

Page 8: ...34 42 874 2 mm 30MPA071 1724 782 kg 14 52 368 8 mm 29 96 760 9 mm 35 01 889 2 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions in are in mi...

Page 9: ...equired Consult Installation Instructions for dis charge and liquid pipe connection sizes UNIT OPERATING WEIGHT lb DIMENSIONS in NUMBER OF COMPRESSORS STANDARD UNIT A B C D E F G H J 30MPW016 671 305...

Page 10: ...and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding charge Field removal of tube and reducing...

Page 11: ...12 58 319 5 27 76 705 1 mm 35 27 895 5 mm 30MPW071 1719 780 kg 12 79 324 9 27 67 702 9 mm 35 02 889 5 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3...

Page 12: ...mm 3 30MPW045 1734 788 kg 12 69 332 mm 29 47 748 mm 32 19 818 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of gravity 3 Dimensions are shown in inches Dimensi...

Page 13: ...ntrol panel end opposite control panel end and above the unit All clearances must be in accordance with local codes 5 Denotes accessory or factory installed option 6 Unit shipped with nitrogen holding...

Page 14: ...13 26 336 8 mm 27 63 701 8 mm 31 36 796 5 mm 30MPW071 2155 977 5 kg 13 42 340 8 mm 27 55 699 8 mm 31 17 791 7 mm NOTES 1 Operating weight includes weight of water and refrigerant 2 Denotes center of...

Page 15: ...CLARITY STYLE B 11 38 in TYPICAL SEE DETAIL A 64 78 in TOP VIEW FRONT VIEW SIDE VIEW 57 00 in UNIT SIZES 016 045 65 05 in UNIT SIZES 050 071 68 81 in a30 6003 NOTE Style B water manifold is used on 30...

Page 16: ...70 63 in TOP VIEW FRONT VIEW SIDE VIEW SEE DETAIL A 6 VICTAULIC CONNECTIONS SPACER PIPE ACCESSORY DETAIL A CORNER POSTS REMOVED FOR CLARITY a30 6004 STYLE B 11 38 in TYPICAL NOTE Style B water manifol...

Page 17: ...3 Minimum Step Capacity 8 15 15 15 10 10 EVAPORATOR Weight lb empty 33 47 92 87 112 158 Net Fluid Volume gal 1 1 1 2 2 8 2 4 3 1 4 7 Maximum Refrigerant Pressure psig 505 505 565 650 565 565 Maximum F...

Page 18: ...PORATOR Weight lb empty 143 143 167 167 190 Net Fluid Volume gal 3 9 3 9 4 7 4 7 5 4 Maximum Refrigerant Pressure psig 650 650 650 650 650 Maximum Fluid Side Pressure psig 300 300 300 300 300 Evaporat...

Page 19: ...Net Fluid Volume L 4 1 4 7 10 5 8 9 11 8 17 9 Maximum Refrigerant Pressure kPa 3482 3482 3896 4479 3896 3896 Maximum Fluid Side Pressure kPa 2068 2068 2068 2068 2068 2068 Evaporator Connections in In...

Page 20: ...14 1 17 0 17 0 19 6 Maximum Refrigerant Pressure kPa 4481 4481 4481 4481 4481 Maximum Fluid Side Pressure kPa 2070 0 2070 0 2070 0 2070 0 2070 0 Water Connections in Inlet and Outlet Victaulic IPS 21...

Page 21: ...70 214 W045 413 256 393 235 W050 484 398 403 317 W055 490 402 407 319 W060 508 424 416 332 W065 519 432 424 337 W071 516 432 427 344 UNIT 30MP WITH MANIFOLD MOUNTING HOLE lb A B C D A020 258 326 134 2...

Page 22: ...9 249 319 259 W050 369 367 310 313 368 311 W055 372 370 312 315 371 313 W060 382 383 324 323 382 323 W065 388 389 328 327 389 327 W071 388 388 331 330 388 330 ESTIMATED WEIGHT DISTRIBUTION AT EACH MOU...

Page 23: ...final position remove the packaging and remove the mobility kit wheels if equipped Remove the 3 8 in wheel nuts to remove the wheels from the unit legs Lev el the unit using a level and bolt the unit...

Page 24: ...pressor mounting rail These RED bolts are for shipping purposes only COMPRESSOR HOLDDOWN BOLTS RED TO BE REMOVED BOTH SIDES COMPRESSOR HOLDDOWN BOLTS TO BE REMOVED BOTH SIDES NOTE For 30MP050 071 unit...

Page 25: ...tem Design Manual or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning Engineers handbook for details 5 See product data for minimum system fluid volume This system may...

Page 26: ...not intended for a specific installation Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards 3 All wiring must comply with applicable local...

Page 27: ...e adequate volume 6 Hot gas lines should rise above refrigerant level in condenser circuit With 30MPA 09DP matched condensers this is accomplished internally in the 09DP unit Double riser may be requi...

Page 28: ...piping techniques Refer to Carrier System Design Manual part 3 Carrier E20 II software Refrigerant Piping program or appropriate ASHRAE American Society of Heating Refrigerating and Air Conditioning E...

Page 29: ...crons or less isolate the vacuum pump from the system Observe the rate of rise of the vacuum in the sys tem If the vacuum rises by more than 50 microns in a 30 min ute time period continue the dehydra...

Page 30: ...s in the line Maintain system pressure by using a pressure tank or a combination of relief and reducing valves For units with water manifold option refer to manifold Victaulic spacer fitting kit acces...

Page 31: ...00 210 220 230 240 4 1 2 3 5 6 7 8 9 Water Pressure Drop GPM LEGEND NOTE Pressure drop curves assume water temperature of 68 F 20 C 1 30MP016 6 30MP045 2 30MP020 7 30MP050 055 3 30MP030 8 30MP060 065...

Page 32: ...30 140 150 160 170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 8 9 Water Pressure Drop kPa Liters Second 1 0 2 3 4 5 6 7 8 9 10 11 12 15 13 14 0 10 20 30 40 50 60 80 90 100 110 120 70 3 1 2 4 5 6 7 8 9...

Page 33: ...30MP045 2 30MP030 6 30MP050 55 3 30MP032 7 30MP060 065 071 4 30MP040 40 35 30 25 20 15 10 5 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 W...

Page 34: ...170 180 190 200 210 220 230 240 4 1 2 3 5 6 7 Water Pressure Drop GPM Water Pressure Drop kPa Liters Second 1 0 2 3 4 5 6 7 8 9 10 11 12 15 13 14 0 10 20 30 40 50 60 80 90 100 110 120 70 3 1 2 4 5 6...

Page 35: ...eaking this is the best place to install an air separator if possible 1 Install automatic air vents at all high points in the system If the 30MP unit is located at the high point of the system a vent...

Page 36: ...ATURE STRAINER 30MP CHILLER CONTROL BOX T SHIELDED GROUNDED WIRE 30MP CHILLER 30MP CHILLER CONTROL BOX CONTROL BOX DISTRIBUTION PUMP EXPANSION TANK S AIR SEPARATOR WITH VENTS DECOUPLER CHILLER 1 CHILL...

Page 37: ...ine water pH of 8 to 9 Avoid a pH greater than 10 since this will adversely affect pump seal components c A side stream filter is recommended see Fig 38 during the cleaning process Filter side flow ra...

Page 38: ...und in the 30MPA MPW control box which contains the low voltage field wiring terminal strip LVT All low voltage field wiring connections are made to this terminal block see Fig 39 Three 7 8 in 22 mm k...

Page 39: ...236 v AC 238 v Average Voltage 243 236 238 3 239 v Determine maximum deviation from average voltage AB 243 239 4 v BC 239 236 3 v AC 239 238 1 v Maximum deviation is 4 v Determine percent voltage imba...

Page 40: ...A EA LRA EA RLA EA LRA EA MCA ICF MOCP REC FUSE 016 208 230 3 60 187 253 24 8 240 0 17 2 164 N A N A 48 2 257 2 70 60 380 3 60 342 418 16 0 134 0 12 2 73 32 2 146 2 45 40 460 3 60 414 508 12 4 130 0 8...

Page 41: ...TS NAMEPLATE VOLTAGE COMPRESSOR A1 COMPRESSOR A2 UNIT RLA LRA RLA LRA MCA ICF MOCP REC FUSE MIN MAX 050 208 230 3 60 187 253 85 1 436 85 1 436 191 5 521 1 250 225 380 3 60 342 418 49 3 252 49 3 252 11...

Page 42: ...NAMEPLATE VOLTAGE COMPRESSOR A1 COMPRESSOR A2 UNIT RLA LRA RLA LRA MCA ICF MOCP REC FUSE MIN MAX 050 208 230 3 60 187 253 79 4 418 79 4 418 178 7 497 1 250 200 380 3 60 342 418 48 1 252 48 1 252 108 2...

Page 43: ...o 90 amps is 6 AWG to 3 0 e Incoming wire size range for non fused disconnect with MCA from 90 1 amps to 250 amps is 4 AWG to 350 kcmil f Incoming wire size range for fused disconnect is 6 AWG to 10 A...

Page 44: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300182 01 Printed in U S A Form 30MP 21SI Pg 44 1118 12 17 Replaces 30M...

Reviews: