background image

42 WHC/AQUASMART

GB - 12

Room Controller (CRC)  - Infrared remote control

Configuration using the Room Controller or
the infrared remote control

Upon request, the unit can be equipped with an infrared remote
controller or with a wired “Room Controller” (CRC).
System configuration can be done either via the “System Manager”
or via the controls “Room Controller” or infrared remote control if
mounted.
With the Room Controller or infrared remote control the following
parameters can be selected:

• Unit type (Hi-Wall).

• Window Contact (normally open / normally closed).

• Boost / Heating function (only for heaters)

(not available).

• 2 pipe / 4 pipe operation

(4 pipe not available).

• °C (Celsius), °F (Fahrenheit) temperature selection (for CRC only).

• Air sensor on CRC (ON)

• Air sensor on Fan Coil (OFF) (for CRC only).

Note:
To select these parameters, refer to the “Room Controller” or
infrared remote controller manual.

Window Contact

If the window contact is open for longer than one minute
the unit is enabled for “Frost protect” operation. The unit returns to
normal operation when the window contact is closed.

The window contact can be configured as follows:

NO Configuration (normally open) using the CRC or the infrared
remote control or System Manager.

Contact closed - indicates window open (frost protect operation).

Contact open - indicates window closed (normal operation).

Remote control functions

A

Display readout

B

ON/OFF button

C

Fan speed selection button

D

Position of air outlet louvre

E

Increase temperature
button

F

Decrease temperature
button

G

Reset button

A

E

D

B

C

F

G

CRC functions

Display

Temperature increase button

Temperature decrease button

 

Fan speed selection button

Operating mode selection button

 

NC Configuration (normally closed) using the CRC or the infrared
remote control or System Manager.

Contact closed - indicates window closed (normal operation).

Contact open - indicates window open (Frost protect operation).

System self-diagnosis

The control has diagnostics which automatically check system
integrity.
If a fault is found, the system is blocked and all functions are
disabled.
In this case, the LED on the HY-NEC board flashes (0.5 sec. ON,
0.5 sec. OFF), until the alarm condition is eliminated.
The monitoring system can be used to interpret the type of fault
according to the following table.

Error

Fault

code

type

2

Air sensor

3

Water sensor

4

Incorrect EEPROM address

5

Condensate discharge pump fault

6

Incorrect heater configuration

7

Defective EEPROM

8

Incorrect water configuration

9

Booster configuration for heaters incorrect

10

Air configuration not available on 4-pipe versions

1 2 3 4 5 MTB

WS

Summary of Contents for AQUASMART 42WHC

Page 1: ...AQUASMART 42WHC 001 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 9001 INSTALLATION MANUAL...

Page 2: ...Communicating AQUASMART control system 8 Unit warning lights and controls 8 Changeover sensor installation 9 Unit connection to water valve panel 10 Wiring diagram 11 Room Controller Infrared remote c...

Page 3: ...team pressing premises Be conscious of the room temperature and general comfort particularly when this units is used near children senior or handicapped people This unit contains rotating equipment fa...

Page 4: ...d according to the unit discharge head in order to allow sufficient and continuous water evacuation Only partial insulation of the piping Installation not correctly levelled which will cause condensat...

Page 5: ...nd delay type fuses consult the electrical connections section in this manual Note All the values in the table include the valve power input Mod 016 020 028 A mm 800 800 800 B mm 290 290 337 C mm 190...

Page 6: ...Nominal single phase voltage 230V 50Hz min 198V max 264V Ref Description Q ty Use Unit 1 Installation manual 1 Unit installation Hanging panel valve kit 1 Screw anchors and screws 4 4 Fixing the hangi...

Page 7: ...ermo electric valve piloted by the room thermostat control terminal board valve connection unit support chain this permits the unit to be swung downwards through 90 facilitating installation flexible...

Page 8: ...WHC AQUASMART E N G L I S H AQUASMART system A B A Building Management System B System Manager C Electrical box D Hi Wall unit E Room Controller Infrared remote controller CCN bus 128 Terminals 32 Zon...

Page 9: ...WS Window contact switch N Green indicator unit ON unit OFF when not lit P Yellow indicator not used Q Red indicator indicates a failure on the unit R Operation switch used by authorized service pers...

Page 10: ...nected in the unit electric box During installation the changeover sensor has to be located on the water inlet pipe using the sensor holder clip and nylon clamps after removing the existing insulation...

Page 11: ...EC board Changeover sensor electrically connected in the electric box HY NEC board The changeover sensor has to be positioned on the inlet water pipe during installation see page 9 Electric valve and...

Page 12: ...roller connector ATTENTION Changing or tampering with the wiring and or control settings for this unit will immediately void the warranty NOTE The connection sequence does not represent the physical l...

Page 13: ...System Manager Contact closed indicates window open frost protect operation Contact open indicates window closed normal operation Remote control functions A Display readout B ON OFF button C Fan speed...

Page 14: ...the same place Do not excessively compress the insulation on the connection pipes with clamps and tape Condensate drain pipe and other piping Position the condensate drain pipe towards its hole in th...

Page 15: ...on between the flexible pipe and the coil pipe This operation permits partial coil draining in any case the quantity of drained water is sufficient to guarantee removal of the unit without any further...

Page 16: ...Clean the filters and reposition them in the unit Run the unit in fan only mode for a few hours to dry the inside Switch the electric mains supply OFF Clean the unit Optimum comfort and lowest consum...

Page 17: ...xhausted replace the batteries The remote control has not been pointed correctly at the unit receiver turn the remote control on and repeat the operation pointing the remote control in the correct dir...

Page 18: ...nzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice Order No 14476 74 October 2001 Supersedes Order No 14476 74 Apri...

Reviews: