81
At each drive where the LEN wiring enters, connects, and exits
to the next drive, the LEN shield must be connected together to
form a continuous ground, but not grounded in the drive itself.
At the last VFD of the daisy chain, the LEN shield must be
grounded at the drive. To do this, strip the LEN wire cable to
expose the shield under the jacket and pinch LEN wire cable
within the clamp as shown in Fig. 79.
Additionally, it is recommended that the BUS TER (Bus Ter-
mination) DIP Switch be turned ON at the last VFD in the dai-
sy chain. This switch is located behind the Local Control Panel
(LCP). See Fig. 80.
COMPRESSOR DRIVES
Each unit is equipped with two VFDs to control the compres-
sor operation, one for each circuit. The VFDs vary the operat-
ing speed of the compressors by changing the input power fre-
quency over a programmed range. The compressor VFDs
should not be operated below minimum programmed frequen-
cy, to ensure adequate oil return on the unit. See Fig. 81 for
compressor VFD locations.
For all chillers, the VFDs are inside the control panel. The right
and left doors allow access to the drives and displays.
CONDENSER FAN DRIVES
Chillers with M or H in the 10th position of the model number
or with the Low Ambient option will have condenser fans on
each circuit which are controlled by one or two VFDs. The
fans on each circuit all operate together at the same prepro-
grammed frequency. Table 50 shows the standard tier fan se-
quences. Tables 51-53 show which condenser fans are con-
trolled by each drive. See Tables 51-53 for typical fan VFD ar-
rangement. See Fig. 82 for typical fan VFD location.
Fig. 79 — LEN Shield Grounding
Fig. 80 — BUS TER Location
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...