OUTSIDE AIR TEMPERATURE RESET
The control system is capable of temperature reset based on
OAT. Typically as the outdoor temperature decreases so does
building cooling load. The chilled water temperature can be in-
creased to lower energy usage while still meeting load demand.
To use OAT Reset, four variables must be configured: Cooling
Reset Select, OAT No Reset Value (outdoor temperature at
which no reset is required), OAT Full Reset Value (outdoor
temperature at which full reset is required), and Cooling Reset
Deg Value (the amount of temperature reset desired).
To configure this option with the Carrier Controller display:
In the example in Fig. 39, the OAT reset provides 0°F (0°C)
chilled water set point reset at 85°F (29.4°C) OAT and 15°F
(8.3°C) reset at 55°F (12.8°C) OAT.
Fig. 39 — Example: OAT Reset
DISPLAY NAME
PATH
VALUE
Cooling Reset
Select
Main Menu
Configuration Menu
Reset Configuration
Default = 1
0=None,
1=OAT
2=Delta T,
3=4 to 20mA control
4=Space Temp
OAT No Reset
Value
Default = 14°F (7.8°C)
Range 14 to 125°F
(7.8 to 69.4°C)
OAT Full Reset
Value
Default = 14°F (7.8°C)
Range 14 to 125°F
(7.8 to 69.4°C)
Cooling Reset
Deg. Value
Default = 0°F (0°C)
Range –30 to 30°F
(–16.7 to 16.6°C)
0
2
4
6
8
10
12
14
16
Outdoor Temperature (de
g
F)
Re
s
et Amount (de
g
F)
Cooling Re
s
et
Deg. V
a
l
u
e
= 15 F (
8
.
3
C)
(cr_deg)
OAT No Re
s
et V
a
l
u
e
=
8
5 F (29.4 C)
(o
a
t_hrno)
OAT F
u
ll Re
s
et V
a
l
u
e
= 55 F (12.
8
C)
(o
a
t_hrf
u
)
20 40 60
8
0 100 120
0
a30-5887
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...