APPENDIX J — FACTORY-SUPPLIED PUMPS
Sensorless pump speed control is standard on factory supplied
pumps. This control monitors power and speed of the pump to
determine where the pump is on the system curve. The system
curve is defined by site specific user settings entered at startup
of the unit. Pump motors are ECM design and are in a parallel
arrangement. All of the pump motors may operate at once de-
pending on the most efficient point for the pump system. See
Fig. K for login details, Fig. L for system information, Fig. M for
unit and language settings, Fig. N for hand, off, and auto modes,
Pump Display
The pump motors have a touchscreen display where system pa-
rameters must be adjusted for the site. This consists of setting
the design flowrate, total static pressure, and zero head pres-
sure. The total static pressure includes the building and chiller
pressure drop. Below is the layout of the touchscreen display.
Password
There are two levels of passwords: User and Configuration.
See Fig. K for login details.
User Password = 1234
Configuration Password
Pump Display – 7644
WiFi Connection – 7^4$
Fig. K — Login Details
Summary of Contents for AquaForce 30XV140
Page 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Page 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Page 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Page 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Page 240: ...240 Fig 99 30XV Communication Wiring...
Page 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Page 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Page 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Page 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Page 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Page 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Page 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Page 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Page 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Page 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Page 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Page 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Page 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...