22
4.2 - Physical data 30XBE
30XBE 250 to 800
30XBE
250
300
350
400
450
500
600
700
750
800
Sound levels
Standard unit
Sound power
(1)
dB(A)
99
99
99
99
101
99
101
99
103
103
Sound pressure at 10 m
(2)
dB(A)
67
67
67
67
69
67
68
66
70
70
Unit + option 15
(3)
Sound power
(1)
dB(A)
93
93
94
95
95
95
97
96
97
98
Sound pressure at 10 m
(2)
dB(A)
61
61
62
63
63
63
64
63
64
65
Unit + option 15LS
(3)
Sound power
(1)
dB(A)
87
87
87
90
91
91
93
92
94
94
Sound pressure at 10 m
(2)
dB(A)
55
55
55
58
59
59
60
59
61
61
Unit + option 15LS+
(3)
Sound power
(1)
dB(A)
-
-
-
-
89
89
91
90
91
92
Sound pressure at 10 m
(2)
dB(A)
-
-
-
-
57
57
58
57
58
59
Dimensions
Standard unit
Length
mm
3604 3604 3604 4798 4798 4798 7186 7186 7186 7186
Width
mm
2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height
mm
2322 2322 2322 2322 2322 2322 2322 2322 2322 2322
Operating weight
(4)
Standard unit
kg
3040 3071 3091 3674 3737 3798 4797 4943 5201 5514
Unit + option 15
(3)
kg
3308 3339 3359 3973 4036 4097 5128 5274 5532 5845
Unit + option 118a
(3)
kg
3124 3155 3175 3778 3841 4182 4929 5075 5348 5661
Unit + option 50
(3)
kg
3385 3417 3437 4106 4248 4590 5550 5696 6056 6368
Compressors
06T semi-hermetic screw compressor, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
1
No. of control stages
Refrigerant for standard unit
(4)
R134a
Circuit A
kg
39
37
37
52
53
55
60
61
69
69
teqCO
2
55,8
52,9
52,9
74,4
75,8
77,9
85,8
87,2
98,0
98,7
Circuit B
kg
40
38
39
40
40
37
61
64
61
67
teqCO
2
57,2
54,3
55,8
57,2
57,2
52,9
87,2
91,5
86,5
95,8
Oil
Circuit A
l
20,8
20,8
20,8
23,5
23,5
23,5
23,5
23,5
27,6
27,6
Circuit B
l
20,8
20,8
20,8
20,8
20,8
20,8
23,5
23,5
23,5
23,5
(1) In dB ref=10
-12
W, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20μPa, ‘A’ weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Options : 15 = Low noise, 15LS = Very Low noise, 118a = DX freecooling option, 50= Heat recovery.
(4) Values are guidelines only. Refer to the unit name plate.
Eurovent certified values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS