66
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Option Configuration
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: CONF_OPT
PIC 5 PATH: Main Menu
Configuration Menu
Option Configuration
LINE
PIC 5 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1 Auto Restart Option
astart
DSABLE/ENABLE
DSABLE
RW
2 Common Sensor Option
commsens
DSABLE/ENABLE
DSABLE
RW
3 Water Pressure Option
wp_opt
DSABLE/ENABLE
DSABLE
RW
4 EC Valve Option
0 = No, 1= Cont
2 = On/Off, 3 = 4-20 mA
hgbp_opt
0 to 3
0
RW
5 EC Selection
0 = Disable, 1 = Surge
2 = Low Load, 3 = Comb
hgbp_sel
0 to 3
0
RW
6 ECV Open IGV1 Position
hpop_gv1
0.5 to 10
5.0
%
RW
7 ECV Close IGV1 Position
hgcl_gv1
1.5 to 20
10.0
%
RW
8 ECV Off DT for Low Load
hgb_toff
0.5 to 10.0
4.0
^F
RW
9 ECV On DT for Low Load
hgb_ton
0.5 to 10.0
2.0
^F
RW
10 ECV Low Load DB
hgbp_ldb
0.5 to 2.0
1.0
^F
RW
11 Head Pres Valve Option
hdpv_opt
DSABLE/ENABLE
DSABLE
RW
12 Head Pres Delta P 0%
hdp_0
20.0 to 85.0
25.0
psig
RW
13 Head Pres Delta P 100%
hdp_100
20.0 to 85.0
50.0
psig
RW
14 Head Pressure Min Output
hdpv_min
0.0 to 100.0
0.0
%
RW
15 Ice Build Option
ice_opt
DSABLE/ENABLE
DSABLE
RW
16 Ice Build Recycle
ice_recy
DSABLE/ENABLE
DSABLE
RW
17 Ice Build Termin Source
0 = Temp, 1 = Contact, 2 = Both
ice_term
0 to 2
0
RW
18 Tower Fan High set point
tfh_sp
55 to 105
75
RW
19 Refrigerant Leak Option
leak_en
DSABLE/ENABLE
DSABLE
RW
20 Refrig Leakage Alarm mA
exv_opt
4 to 20
20
RW
21 Oil EXV Option
leak_ma
DSABLE/ENABLE
DSABLE
mA
RW
22 Oil Temp High Threshold
oil_high
100 to 140
120
°F
RW
23 Oil Temp Low Threshold
oil_low
90 to 130
110
°F
RW
24 Gas Torque Factor
gt_fact
0.25 to 3.0
1
°F
RW
25 Guide Vane/SRD Factor
gv_srd_f
0.7 to 1.20
0.95
RW
26 Power Recovery Timeout
pd_tcfg
0 to 60
15
min
RW
27 Evap Liquid Temp Opt
evap_ref
DSABLE/ENABLE
Enable
28 Evap App Calc Selection
Sat Temp = 0, Ref Temp = 1
evap_ref
0/1
1
RW
29 Condenser Flush Alert
cfa_opt
DSABLE/ENABLE
DSABLE
RW
30 Customer Alert Option
cusa_opt
DSABLE/ENABLE
DSABLE
RW
31 Water Flow Measurement
0 = No, 1 = Digital, 2 = Analog
wfm_opt
0-2
0
RW
32 Water Flow at 4 mA
flow4ma
0-200
0.00
GPS
RW
33 Water Flow at 20mA
flow20ma
0-200
0.00
GPS
RW
34 Evap Flow Rate Baseline
chwf_bas
0-150
0.00
GPS
RW
35 Evap Pres Drop Baseline
evpd_bas
0-20
0.00
PSI
RW
36 Cond Flow Rate Baseline
cdwf_bas
0-150
0.00
PSI
RW
37 Cond Pres Drop Baseline
cdpd_bas
0-20
0.00
PSI
RW
38 Water Pres Drop @ 20mA
wpd_20ma
0-40
10.00
PSI
RW
41 Vapor Source SV Delay
vssv_dly
0-10
5.0
min
RW
42 Max Oil Pressure Diff
opvfdmax
35-60
50
PSI
RW
43 Oil Pump VFD Max Step
opvfdstp
0-10
7
%
RW
44 Vapor Source SV Delay
vssv_dly
0-10
5
min
RW
45 Vapor Source SV Option
vssv_dly
DSABLE/ENABLE
DSABLE
RW
RW — Read/Write