101
APPENDIX D — NETWORK CONFIGURATION (cont)
Table C — BACnet Object Table (cont)
OBJECT NAME
OBJECT ID
OPTION
READ/WRITE
DESCRIPTION
SETPOINT_EWT_OPT
BV:39
RW
EWT Control Option
SETPOINT_ice_sp
AV:112
RW
Ice Build Setpoint
SETPOINT_lcdw_sp
AV:111
RW
Heating LCDW Setpoint
SETPOINT_lcw_sp
AV:109
RW
Cooling LCW Setpoint
TEMP_cond_app
AV:15
IR RO
Condenser
Approach
TEMP_COND_SAT
AV:16
COV, IR
RO
Cond Sat Refrig Temp
TEMP_DGT
AV:17
COV, IR
RO
Comp Discharge Temp
TEMP_DSH
AV:18
RO
Discharge Superheat
TEMP_ECDW
AV:10
COV, IR
RO
Entering Condenser Water
TEMP_ECW
AV:8
COV, IR
RO
Entering Chilled Water
TEMP_evap_app
AV:14
IR RO
Evaporator
Approach
TEMP_EVAP_SAT
AV:12
COV, IR
RO
Evap Sat Refrig Temp
TEMP_EVAP_T
AV:13
COV, IR
RO
Evap Refrig Liquid Temp
TEMP_LCDW
AV:11
COV, IR
RO
Leaving Condenser Water
TEMP_LCW
AV:9
COV, IR
RO
Leaving Chilled Water
TEMP_MTRB
AV:20
COV, IR
RO
Thrust Bearing Temp
TEMP_MTRB_OIL
AV:19
IR
RO
Thrust Bearing Oil Temp
TEMP_MTRB1
AV:21
COV, IR
RO
Low Speed ME Brg Temp
TEMP_MTRB2
AV:22
COV, IR
RO
Low Speed CE Brg Temp
TEMP_MTRB3
AV:23
COV, IR
RO
High Speed ME Brg Temp
TEMP_MTRB4
AV:24
COV, IR
RO
High Speed CE Brg Temp
TEMP_MTRW1
AV:25
COV, IR
RO
Motor Winding 1 Temp
TEMP_MTRW2
AV:26
COV, IR
RO
Motor Winding 2 Temp
TEMP_MTRW3
AV:27
COV, IR
RO
Motor Winding 3 Temp
TEMP_OILT_DIS
AV:29
COV, IR
RO
Oil Supply Temp
TEMP_OILT_SMP
AV:28
COV, IR
RO
Oil Sump Temp
LEGEND
AV
— Analog Value
BV
— Binary Value
CMD — Commandable
COV — Change of Value
IR
— Intrinsic Reporting
RO — Read Only
RW — Read/Write