AGAGC9PNS01D Gas Conversion Kit, Propane to Natural: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

12

Two-Stage Gas Valve

A200178

Representative drawing only, some models may vary in appearance.

L14F003

Representative drawing only, some models may vary in appearance.

A221035A

Representative drawing only, some models may vary in appearance.

Fig. 21 – Example of Two-Stage Speed Furnace Control for VCA or 

VCT Blower Motor

1. Enable two-stage thermostat on control board by:

a. For boards with DIP switches, turn SW1-2 on furnace control 

ON, see 

Fig. 21

.

b. For boards with 3 digit display, navigate to (

Htt

) and select 

(

2st

), see 

Fig. 21

. See furnace installation manual for additional 

instructions.

2. Jumper R-W/W1 and R-W2 thermostat connections on control.

3. When main  burners  ignite,  confirm inlet  gas  pressure is  between

4.5-in. w.c. and 13.6-in. w.c.

4. Remove jumper across R-W/W1 and R-W2 thermostat connections

to terminate call for heat.

5. Turn furnace gas valve switch to OFF position.

6. Turn gas supply manual shutoff valve to OFF position.

7. Turn off furnace power supply.

8. Remove  manometer  and  on  some  models  remove  pressure  tap

fitting.

9. On some models, apply pipe dope sparingly to the end of inlet gas

pipe plug and install into unused end of 1/8-in. (3 mm) tee. Use a

small back-up wrench on tee when tightening gas inlet pipe plug.

Or, on some models, tighten set screw on inlet tower pressure tap

with a 3/32-in. hex wrench, see 

Fig. 13

 or 

Fig. 14

.

Fixed Speed Blower (FCT), Two-Stage Gas Valve

A200177

Representative drawing only, some models may vary in appearance.

A200176

Representative drawing only, some models may vary in appearance.

Fig. 22 – Example of PSC or Discrete Tap Two-Stage Furnace 

Control

24-V THERMOSTAT 

TERMINALS 

PL2 

 HOT SURFACE 

IGNITER & INDUCER 

MOTOR CONNECTOR 

115-VAC (L2) NEUTRAL 

CONNECTIONS  

115-VAC (L1) LINE 

VOLTAGE  CONNECTIONS  

EAC-1 TERMINAL 

 (115-VAC 1.0 AMP MAX.)  

PL1 

 LOW VOLTAGE MAIN 

HARNESS CONNECTOR 

AND ECM BLOWER 

HARNESS CONNECTOR 

TRANSFORMER 24-VAC 

CONNECTIONS  

3-AMP FUSE  

STATUS AND COMM 

LED LIGHTS  

SW1 SETUP 

SWITCHES AND 

BLOWER OFF-

DELAY 

MODEL PLUG 
CONNECTOR 

AIR CONDITIONING 

(A/C) AIRFLOW 

SETUP SWITCHES 

COMMUNICATION 

CONNECTOR 

CONTINUOUS FAN 

(CF) AIRFLOW 

SETUP SWITCHES 

OUTDOOR 

AIR TEMP 

CONNECTOR 

HUMIDIFIER 

TERMINAL (24-VAC 

0.5 AMP MAX. 

FLASH 

UPGRADE 

CONNECTOR 

(FACTORY 

ONLY) 

SW4 SETUP 

SWITCHES 

SOFTWARE 

VERSION  

PART NUMBER AND 

DATE CODE WWYY  

24-V THERMOSTAT 

TERMINALS 

PL2 – HOT SURFACE 

IGNITER & INDUCER 

MOTOR CONNECTOR 

115-VAC (L2) NEUTRAL 

CONNECTIONS  

115-VAC (L1) LINE 

VOLTAGE  CONNECTIONS  

EAC-1 TERMINAL 

(115-VAC 1.0 AMP MAX.)

PL1 – LOW VOLTAGE MAIN 

HARNESS CONNECTOR  

TRANSFORMER 24-VAC 

CONNECTIONS  

3-AMP FUSE  

STATUS AND COMM 

LED LIGHTS  

SW1 SETUP 

SWITCHES AND 

BLOWER OFF-

DELAY 

MODEL PLUG 
CONNECTOR 

COMMUNICATION 

CONNECTOR 

AIR CONDITIONING (A/C) & 

CONTINUOUS FAN (CF) 

AIRFLOW SETUP SWITCHES 

OUTDOOR 

AIR TEMP 

CONNECTOR 

HUMIDIFIER 

TERMINAL (24-VAC 

0.5 AMP MAX.) 

ACRDJ – AIR 

CONDITIONING 

RELAY DISABLE 

JUMPER

FLASH

UPGRADE 

CONNECTOR 

(FACTORY 

ONLY) 

SOFTWARE 

VERSION  

TEST / TWIN

HUM

PL
T

PL
1

W
2

Y1

D

H

U

M

G

C

O

M

W
/W
1
Y/
Y2

R

24V

FUSE 3-- AMP

EAC-- 2

EAC-- 1

L1

BL--1 XFMR

L2

COM

HI HT

COOL

LO H T

SPARE 1

2

4

V

M

TR

TA
P

S

BLOWER SPEED
TERMINALS

115--VAC (L2)
NEUTRAL
CONNECTIONS

LED OPERATION
& DIAGNOSTIC LIGHT

3--AMP FUSE

24--V THERMOS TAT
TERMINALS

SET UP SWITCHES
THERMOSTAT TYPE (TT)
AND HEAT OFF--DELAY

TWINNING AND/OR
COMPONENT TEST
TERMINAL

HUMIDIFIER TERMINAL
(24 VAC 0.5 AMPS MAX)

TRANSFORMER
24 VAC CONNECTIONS

P--1 LOW VOLTAGE

P2 -- HOT SURFACE
IGNITER/INDUCE R
MOTOR CONNECTION

115 VA C
BLOWER POWER (BL1)
CONNECTION

115 VAC LINE (L1)

TT
OFF
DLY

ON

OF

F

123

ID
R

HS
IR

ID
M

IH
I/L
O

R

PL
2

1

HSI

HI

LO

1

EAC TERMINAL
115 VAC 1.0 AMP
MAX

115 VA C
TRANSFORMER
PRIMARY

SPARE 2

HUM

115 VAC HUM

COM/BLUE 24VAC/RED

CO

M

24V

24VAC

TEST / TWIN

HUM

PL
T

SEC-2

SEC-1

COM

24VAC

PL1

W2        Y

      DHUM    G       COM   W/W1   Y/Y2       R  

24V

FUSE 3-AMP

EAC-2

EAC-1

L1

BL-1

PR-1

L2

COM

HI HT

COOL

LO HT

SPARE 2

  

  

 

R

T

  

  

 

V

4

2

T

APS

BLOWER SPEED
TERMINALS

115-VAC (L2)
NEUTRAL
CONNECTIONS

LED OPERATION
& DIAGNOSTIC LIGHT

3-AMP FUSE

24-V THERMOSTAT
TERMINALS

SET UP SWITCHES
LOW HEAT ONLY 
AND BLOWER 
OFF-DELAY 

TWINNING AND/OR
COMPONENT TEST
TERMINAL

ACRDJ - AIR CONDITIONING 
RELAY DISABLE JUMPER

HUMIDIFIER TERMINAL
(24 VAC  0.5 AMPS MAX)

TRANSFORMER
24 VAC CONNECTIONS

PL1-LOW VO LTAGE
MAIN HARNESS CONNEC TOR

PL2 - HOT SURFACE
IGNITER/INDUCE R
MOTOR CONNECTION

115 VAC
BLOWER POWER (BL1)
CONNECTION

115 VAC LINE (L1)
INPUT

LHT
OFF
DLY

ON

OFF

1  2  3

IDR

HSIR

IDM

IHI/L

OR

PL2

1

HSI     HI    LO

1

EAC TERMINAL
115 VAC 1.0 AMP MAX

115 VAC
TRANSFORMER
PRIMARY

SPARE 1

Summary of Contents for AGAGC9PNS01D

Page 1: ...n personal injury or death This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide could result causing property damage personal injury or los...

Page 2: ...o OFF A190014 Fig 1 Representative Furnace Drawing MANIFOLD ORIFICE BURNER REMOVAL NOTE Use a back up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box 1 Disconnect the gas pipe from gas valve and remove pipe from the furnace casing see Fig 1 2 Disconnect the connector harness from gas valve Disconnect wires from Hot Surface Ignit...

Page 3: ...line to point of intersection to find orifice size and manifold pressure settings For Modulating Furnaces Follow Steps 1 and 2 above For Step 3 use Table 6 for all sizes 20 000 BTUh Max Heat 8 000 BTUh Min Heat per burner except 60 000 BTUh models in a 21 in wide cabinet Table 7 for 60 000 BTUh models in a 21 in wide cabinet 20 200 BTUh Max Heat 8 000 BTUh Min Heat per burner 1 For both tables fol...

Page 4: ...No High Low No High Low 900 43 3 8 1 6 42 3 2 1 4 42 3 3 1 4 42 3 4 1 4 0 925 43 3 6 1 5 43 3 7 1 6 43 3 8 1 6 42 3 2 1 4 0 950 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 975 44 3 7 1 6 44 3 8 1 6 43 3 4 1 5 43 3 6 1 5 to 1000 44 3 5 1 5 44 3 6 1 5 44 3 8 1 6 43 3 4 1 4 1025 44 3 3 1 4 44 3 5 1 5 44 3 6 1 5 44 3 7 1 6 2000 1050 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 44 3 5 1 5 610 1075 45 3 7 1 6 45 3 ...

Page 5: ... 3 3 0 50 44 3 4 0 55 44 3 5 0 55 44 3 6 0 55 2743 775 45 3 7 0 60 44 3 2 0 50 44 3 3 0 50 44 3 4 0 55 9001 600 42 3 3 0 55 42 3 4 0 55 42 3 6 0 55 42 3 7 0 60 2744 625 43 3 7 0 60 42 3 2 0 50 42 3 3 0 55 42 3 4 0 55 650 43 3 5 0 55 43 3 6 0 55 43 3 7 0 60 43 3 8 0 60 675 44 3 7 0 60 44 3 8 0 60 43 3 4 0 55 43 3 5 0 55 10000 700 44 3 4 0 55 44 3 5 0 55 44 3 7 0 60 44 3 8 0 60 3048 725 44 3 2 0 50 ...

Page 6: ...y time specifications and designs without notice and without obligations 6 SINGLE STAGE GAS VALVE A221025 A221025FR Fig 5 Conversion Kit Rating Plate 40 000 BTUh to 140 000 BTUh ONLY Single Stage Furnace TWO STAGE GAS VALVE A221024 A221024FR Fig 6 Conversion Kit Rating Plate 40 000 BTUh to 140 000 BTUh ONLY Two Stage Furnace ...

Page 7: ...to plug the hole in the burner when the mixer screws are removed A11460 Fig 8 Mixer Screw Location REINSTALL BURNER ASSEMBLY To reinstall burner assembly 1 Attach flame sensor to burner assembly 2 Insert one piece burner in slot on sides of burner box and slide burner back in place 3 Reattach HSI wires to HSI 4 Verify igniter to burner alignment see Fig 9 Fig 10 A11405 Fig 9 Igniter Position Back ...

Page 8: ... or improper operation DO NOT use this kit if the gas valve has a green label 26 000 BTUh model on it The 26 000 BTUh model uses a different conversion kit available from your distributor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in unit damage The gas valve must be converted and pre adjusted before operating on propane gas If not converted and pre adjusted sooting and c...

Page 9: ...r for the modulating gas valve is very small Needle nose pliers are required to remove the jumper from the valve If the jumper is not removed the valve will not operate properly on natural gas pressures 1 Locate the round LP GAS sticker on the top of the gas valve 2 Peel the sticker off and discard 3 Note the small square opening in the top of the gas valve 4 Note the two jumper pins inside the mo...

Page 10: ...ided in kit and install in the 1 8 in 3 mm tapped inlet pressure tap opening in the gas valve DO NOT over tighten Check for gas leaks after gas supply has been turned on A170142 Fig 19 LGPS for casing wider than 14 3 16 and vent does not pass between inducer and burner assembly INSTALL MANIFOLD 1 Refer to Fig 2 and Fig 3 2 Align the orifices in the manifold assembly with the support rings on the e...

Page 11: ...rmostat connections to terminate call for heat 4 Turn furnace gas valve switch to OFF position 5 Turn gas supply manual shutoff valve to OFF position 6 Turn off furnace power supply 7 Remove manometer and on some models remove pressure tap fitting 8 On some models apply pipe dope sparingly to end of inlet gas pipe plug and install into unused end of 1 8 in 3 mm tee Use a small back up wrench on te...

Page 12: ...TIONING A C AIRFLOW SETUP SWITCHES COMMUNICATION CONNECTOR CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES OUTDOOR AIR TEMP CONNECTOR HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX FLASH UPGRADE CONNECTOR FACTORY ONLY SW4 SETUP SWITCHES SOFTWARE VERSION PART NUMBER AND DATE CODE WWYY 24 V THERMOSTAT TERMINALS PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR 115 VAC L2 NEUTRAL CONNECTIONS 115 VAC L1 LINE VOLTAGE C...

Page 13: ... than one full turn with the 3 32 in hex wrench 3 Attach manometer to manifold pressure tap on gas valve see Fig 11 Fig 12 Fig 13 Fig 14 or Fig 17 4 Turn gas supply manual shutoff valve to ON position 5 Turn furnace gas valve switch to ON position 6 Check all threaded pipe connections for gas leaks 7 Turn on furnace power supply GAS INPUT RATE INFORMATION See furnace rating plates see Fig 5 Fig 6 ...

Page 14: ...crease input rate or clockwise in to increase input rate 12 Replace caps that conceal gas valve regulator adjustment screws 13 When correct input is obtained main burner flame should be clear blue almost transparent see Fig 24 14 Remove jumper across R W1 and W2 after high heat adjustment to terminate call for heat 15 Turn setup switch SW1 TT on furnace control to OFF position 16 Turn furnace gas ...

Page 15: ...sure table on Conversion Kit Rating Plate 4 To adjust the Minimum Heat manifold pressure Slowly turn the rotary adjustment switch counterclockwise to decrease manifold pressure or clockwise to increase manifold pressure 5 Turn rotary adjustment switch no more than one click per second until you obtain the required manifold pressure This adjustment will not affect the previous Maximum Heat adjustme...

Page 16: ...to Blower Access Door of furnace Date name and address of organization making this conversion are required see Fig 26 2 Attach Conversion Rating Plate Label 348712 201 204 206 207 208 or 209 to outer door of furnace see Fig 5 Fig 6 or Fig 7 3 Attach Gas Control Conversion Label 348712 202 to gas valve Do not use 348712 203 which is similar CHECKOUT 1 Observe unit operation through two complete hea...