AGAGC9PNS01B Gas Conversion Kit, Propane to Natural: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

10

A170131

Fig. 17 – Automatic Control Valve (Modulating) without Tower 

Pressure Ports (continued)

REMOVE LOW GAS PRESSURE SWITCH

NOTE: 

Remove  the  Low  Gas  Pressure  Switch  before  installing  the

manifold on the burner assembly.

NOTE: 

There are two ways that the Low Gas Pressure Switch (LGPS)

could  have  been  installed  during  the  original  natural  to  Propane  gas

conversion.

All 14 3/16-in Casings or Vent Passed Between Inducer 

Assembly and Burner Assembly

If the vent pipe passes between the inducer and burner assembly, or the

furnace is a 14 3/16-in. wide casing. The switch is installed as shown in

Fig. 18

.

1. Remove low gas pressure switch, brass street 90_ elbow, brass hex

nipple, brass tee and black iron street 90_ elbow from the gas valve

inlet pressure tap, see 

Fig. 18

.

NOTE: 

Use pipe dope approved for use with Propane gas. DO NOT use

PTFE thread-seal tape.

2. Apply  pipe  dope  sparingly  to  the  1/8-in.  (3  mm)  NPT  pipe  plug

(provided in kit) and install in the 1/8-in tapped inlet-pressure tap

opening  in  the  gas  valve.  DO  NOT  over-tighten.  Check  for  gas

leaks after gas supply has been turned on.

A170141

Fig. 18 – LGPS for 14-3/16 Casing or when vent passes between 

inducer and burner assembly

Casings Wider Than 14 3/16-in/Vent Does Not Pass 

Between Inducer and Burner Assembly

If the vent pipe does not pass between the inducer and burner assembly,

or  the  furnace  is  wider than  a 14  3/16-in.  wide  casing. The  switch  is

installed as shown in 

Fig. 19

.

1. Remove Low Gas Pressure Switch (LGPS), brass street tee, brass

nipple and brass street 90° elbow from the gas valve inlet  pressure

tap, see 

Fig. 19

.

NOTE: 

Use pipe dope approved for use with Propane gas. DO NOT use

PTFE thread-seal tape.

2. Apply  pipe  dope  sparingly  to  the  1/8-in.  (3  mm)  NPT  pipe  plug

(provided  in  kit)  and  install  in  the  1/8-in  (3  mm)  tapped

inlet-pressure tap opening in the gas valve. DO NOT over-tighten.

Check for gas leaks after gas supply has been turned on.

A170142

Fig. 19 – LGPS for casing wider than 14-3/16 and vent does not pass 

between inducer and burner assembly

INSTALL MANIFOLD

1. Refer to 

Fig. 2

 and 

Fig. 3

.

2. Align the orifices in the manifold assembly with the support rings

on the end of the burner.

3. Insert  the  orifices  in  the  support  rings  of  the  burners.  Manifold

mounting tabs should fit flush against the burner box.

NOTE: 

If manifold does not fit flush against the burner box, the burners

are  not  fully  seated  forward.  Remove  the  manifold  and  check  burner

positioning in the burner box assembly.

4. Attach  the  green/yellow  wire  and  ground  terminal  to  one  of  the

manifold mounting screws, see 

Fig. 2

.

1/2” NPT

INLET

1/2” NPT

OUTLET

INP

1/8” NPT INLET

PRESSURE TAP

Representative drawing only, some models may vary in appearance.

Brass Street Tee

Brass Hex Nipple

Brass Street 90

Low Gas Pressure Switch

Black Iron Street 90 Pointing

Inlet Pressure Tap with Plug

(Optional inlet pressure

tap on some models)

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury,  death,

and/or property damage. 

Never  test  for  gas  leaks  with  an  open  flame.  Use  a  commercially

available soap solution made specifically for the detection of leaks to

check all connections. A fire or explosion may result causing property

damage, personal injury or loss of life.

AVERTISSEMENT

!

RISQUE D’EXPLOSION ET D’INCENDIE

Le non-respect des avertissements de sécurité pourrait d’entraîner des

blessures graves, la mort ou des dommages matériels.

Ne jamais utiliser une flamme nue por vérifier la présence des fuites de

gaz. Pour la vérification de tous les joints, utiliser plutôt une solution

savonneuse commerciale fabriquée spécifiquement pur la détection des

fuites  de  gaz.  Un  incendie  ou  une  explosion  peut  entraîner  des

dommages matériels, des blessures ou la mort.

Brass Street 90

Brass Nipple

Low Gas Pressure Switch

Inlet Pressure Tap

Brass Street Tee

with plug

(Optional inlet

pressure

tap on some

models)

Summary of Contents for AGAGC9PNS01B

Page 1: ...o follow this warning could result in personal injury or death This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide could result causing pr...

Page 2: ...urn electric switch on gas valve to OFF A190014 Fig 1 Representative Furnace Drawing MANIFOLD ORIFICE BURNER REMOVAL NOTE Use a back up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner box 1 Disconnect the gas pipe from gas valve and remove pipe from the furnace casing see Fig 1 2 Disconnect the connector harness from gas valve Disco...

Page 3: ...line to point of intersection to find orifice size and manifold pressure settings For Modulating Furnaces Follow Steps 1 and 2 above For Step 3 use Table 6 for all sizes 20 000 BTUH Max Heat 8 000 BTUH Min Heat per burner except 60 000 BTUH models in a 21 in wide cabinet Table 7 for 60 000 BTUH models in a 21 in wide cabinet 20 200 BTUH Max Heat 8 000 BTUH Min Heat per burner 1 For both tables fol...

Page 4: ...No High Low No High Low 900 43 3 8 1 6 42 3 2 1 4 42 3 3 1 4 42 3 4 1 4 0 925 43 3 6 1 5 43 3 7 1 6 43 3 8 1 6 42 3 2 1 4 0 950 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 43 3 7 1 6 975 44 3 7 1 6 44 3 8 1 6 43 3 4 1 5 43 3 6 1 5 to 1000 44 3 5 1 5 44 3 6 1 5 44 3 8 1 6 43 3 4 1 4 1025 44 3 3 1 4 44 3 5 1 5 44 3 6 1 5 44 3 7 1 6 2000 1050 44 3 2 1 3 44 3 3 1 4 44 3 4 1 4 44 3 5 1 5 610 1075 45 3 7 1 6 45 3 ...

Page 5: ... 3 3 0 50 44 3 4 0 55 44 3 5 0 55 44 3 6 0 55 2743 775 45 3 7 0 60 44 3 2 0 50 44 3 3 0 50 44 3 4 0 55 9001 600 42 3 3 0 55 42 3 4 0 55 42 3 6 0 55 42 3 7 0 60 2744 625 43 3 7 0 60 42 3 2 0 50 42 3 3 0 55 42 3 4 0 55 650 43 3 5 0 55 43 3 6 0 55 43 3 7 0 60 43 3 8 0 60 675 44 3 7 0 60 44 3 8 0 60 43 3 4 0 55 43 3 5 0 55 10000 700 44 3 4 0 55 44 3 5 0 55 44 3 7 0 60 44 3 8 0 60 3048 725 44 3 2 0 50 ...

Page 6: ...any time specifications and designs without notice and without obligations 6 SINGLE STAGE GAS VALVE A200248 A200249 Fig 5 Conversion Kit Rating Plate 40 000 BTUH to 140 000 BTUH ONLY Single Stage Furnace TWO STAGE GAS VALVE A200250 A200251 Fig 6 Conversion Kit Rating Plate 40 000 BTUH to 140 000 BTUH ONLY Two Stage Furnace ...

Page 7: ...o plug the hole in the burner when the mixer screws are removed A11460 Fig 8 Mixer Screw Location REINSTALL BURNER ASSEMBLY To reinstall burner assembly 1 Attach flame sensor to burner assembly 2 Insert one piece burner in slot on sides of burner box and slide burner back in place 3 Reattach HSI wires to HSI 4 Verify igniter to burner alignment see Fig 9 Fig 10 A11405 Fig 9 Igniter Position Back V...

Page 8: ... or improper operation DO NOT use this kit if the gas valve has a green label 26 000 BTUH model on it The 26 000 BTUH model uses a different conversion kit available from your distributor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in unit damage The gas valve must be converted and pre adjusted before operating on propane gas If not converted and pre adjusted sooting and c...

Page 9: ...r for the modulating gas valve is very small Needle nose pliers are required to remove the jumper from the valve If the jumper is not removed the valve will not operate properly on natural gas pressures 1 Locate the round LP GAS sticker on the top of the gas valve 2 Peel the sticker off and discard 3 Note the small square opening in the top of the gas valve 4 Note the two jumper pins inside the mo...

Page 10: ...ided in kit and install in the 1 8 in 3 mm tapped inlet pressure tap opening in the gas valve DO NOT over tighten Check for gas leaks after gas supply has been turned on A170142 Fig 19 LGPS for casing wider than 14 3 16 and vent does not pass between inducer and burner assembly INSTALL MANIFOLD 1 Refer to Fig 2 and Fig 3 2 Align the orifices in the manifold assembly with the support rings on the e...

Page 11: ...alve switch to OFF position 5 Turn gas supply manual shutoff valve to OFF position 6 Turn off furnace power supply 7 Remove manometer and on some models remove pressure tap fitting 8 On some models apply pipe dope sparingly to end of inlet gas pipe plug and install into unused end of 1 8 in 3 mm tee Use a small back up wrench on tee when tightening gas inlet pipe plug Or on some models tighten set...

Page 12: ...ARNESS CONNECTOR TRANSFORMER 24 VAC CONNECTIONS 3 AMP FUSE STATUS AND COMM LED LIGHTS SW1 SETUP SWITCHES AND BLOWER OFF DELAY MODEL PLUG CONNECTOR AIR CONDITIONING A C AIRFLOW SETUP SWITCHES COMMUNICATION CONNECTOR CONTINUOUS FAN CF AIRFLOW SETUP SWITCHES OUTDOOR AIR TEMP CONNECTOR HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX FLASH UPGRADE CONNECTOR FACTORY ONLY SW4 SETUP SWITCHES SOFTWARE VERSION PART ...

Page 13: ... to 2000 ft 610 M In the U S A the input rating for altitudes above 2000 ft 610M must be reduced by 2 percent for each 1000 ft 305 M above sea level In Canada the input rating must be derated by 5 percent for altitudes of 2000 ft 610 M to 4500 ft 1372 M above sea level The Conversion Kit Rating Plate accounts for high altitude derate SET GAS INPUT RATE A11461 Fig 24 Burner Flame Single Stage Gas V...

Page 14: ... opening Or on some models tighten set screw on manifold tower pressure tap with a 3 32 in hex wrench see Fig 6 20 Turn on furnace power supply 21 Set room thermostat to call for heat 22 Check pressure tap plug for gas leaks when main burners ignite 23 Check for correct burner flame 24 After making the required manifold pressure adjustments check and adjust the furnace temperature rise per the fur...

Page 15: ...ed on the furnace rating plate Determine air temperature rise as follows 1 Place thermometers in return and supply ducts as near furnace as possible Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings This practice is particularly important with straight run ducts 2 When thermometer readings stabilize subtract return air temperature from supply air temperat...

Page 16: ...oor of furnace Date name and address of organization making this conversion are required see Fig 26 2 Attach Conversion Rating Plate Label 346162 201 204 206 207 208 or 209 to outer door of furnace see Fig 5 Fig 6 or Fig 7 3 Attach Gas Control Conversion Label 346162 202 to gas valve Do not use 346162 203 which is similar CHECKOUT 1 Observe unit operation through two complete heating cycles 2 See ...

Reviews: