140
Table 36 — Electrical Data — Premium Efficiency EISA Compliant Motors (cont)
ODP/OPSB T-FRAME MOTORS - 1200 RPM
LEGEND
TEFC T-FRAME MOTORS - 1200 RPM
NOTES:
1. Approximate motor full load amps listed. Actual motor full load
amps can be found on the motor nameplate.
2. Motor voltage and availability is controlled by
AHU
Builder
®
program.
Motor Nameplate Data
The 39 Series air-handling unit nameplates do not contain fan mo
-
tor electrical data. The units as manufactured, are certified to meet
all requirements, including unit markings, of UL1995 “Standard
For Safety-Heating and Cooling Equipment.”
The motor nameplate should be relied on to carry the motor elec
-
trical data. Here are several reasons the motor data is not on an ex
-
ternal nameplate, separate from the motor:
1. Many units are shipped without motors, and the installing
contractor provides field-supplied motors.
2. Typically, the motors provided are triple voltage motors and
may be wired at the job site for 208, 230, or 460-volt power,
as necessary.
3. The motor nameplate, which contains all necessary electrical
information, is easily accessible inside the fan section.
4. Motor changes are quite often required during testing and bal
-
ancing to meet actual job conditions. External nameplates
could easily be left unchanged by the installing contractor.
NOTE: Where field wiring of motor is required, wire per instruc
-
tions located in motor terminal box or on motor nameplate. See
Fig. 117.
Fig. 117 —
Field Wiring Instructions for
Motor with 12 Leads
MOTOR
HP
FLA FOR 3-PHASE, 60 HZ
VOLTAGES
EFF.
(%)
NEMA
FRAME
208
230
460
575
1
3.9
3.6
1.8
—
82.5
145T
1.5
5.1
5.0
2.5
—
87.5
182T
2
7.5
6.8
3.4
—
88.5
184T
3
9.3
8.8
4.4
—
88.5
213T
5
15.2
14.8
7.4
—
89.5
215T
7.5
23.0
22.4
11.2
—
90.2
254T
10
30.0
28.6
14.3
—
91.7
256T
15
42.0
41.0
20.5
—
91.7
284T
20
56.0
54.0
27.0
—
92.4
286T
25
70.0
68.0
34.0
—
93.0
324T
30
80.0
76.0
38.0
—
93.6
326T
40
110.0
104.0
51.0
—
94.1
364T
50
132.0
124.0
62.0
—
94.1
365T
EFF.
—
Efficiency
EISA
—
Energy Independence and Security Act of 2007
FLA
—
Full Load Amps
NEMA
—
National Electrical Manufacturers Association
ODP
—
Open Drip Proof
OPSB
—
Open Slotted Band
TEFC
—
Totally Enclosed Fan Cooled
MOTOR
HP
FLA FOR 3-PHASE, 60 HZ
VOLTAGES
EFF.
(%)
NEMA
FRAME
208
230
460
575
1
3.9
3.6
1.8
1.4
82.5
145T
1.5
5.0
4.8
2.4
1.9
87.5
182T
2
7.7
7.0
3.5
2.8
88.5
184T
3
10.2
9.2
4.6
3.7
89.5
213T
5
15.3
14.6
7.3
5.8
89.5
215T
7.5
22.6
21.4
10.7
—
91.0
254T
10
30.0
28.8
14.4
—
91.0
256T
15
42.0
42.0
21.0
—
91.7
284T
20
56.0
54.0
27.0
—
91.7
286T
25
70.0
64.0
32.0
—
93.0
324T
30
83.0
78.0
39.0
—
93.0
326T
40
109.0
98.8
49.4
—
94.1
364T
50
133.0
123.0
61.7
—
94.1
365T
MOTOR WIRING INSTRUCTIONS
INSIDE JUNCTION BOX
NOTES:
1. If the motor has 12 leads and wiring diagrams for both Wye and
Delta OR Start and Run connections, ALWAYS wire to the RUN
or DELTA connections with an across-the-line motor starter or
VFD. Failure to do so will result in motor and/or starter/VFD
damage.
2. Low-voltage motors include 190, 200, 208, and 230-v.
3. High-voltage motors include 380, 400, 460, and 480-v.
WIRE
VOLTS
OR
VOLTAGE
CONNECTION
2 Y
LOW
START
LOW
WYE
2
LOW
RUN
DELTA
1 Y
HIGH
START
HIGH
WYE
1
HIGH
RUN
DELTA
a39-4179