T-365
6–4
Low suction pressure
Incorrect software and/or controller configuration
Check
Failed suction pressure transducer (SPT) or evaporator
pressure transducer (EPT)
Replace
Suction service valve partially closed
Open
Filter drier partially plugged
Low refrigerant charge
No evaporator air flow or restricted air flow
Excessive frost on evaporator coil
Evaporator fan(s) rotating backwards
EEV control malfunction
Replace
Failed digital unloader valve (DUV)
Replace
Suction and discharge pressures
tend to equalize when unit is oper-
ating
Compressor operating in reverse
Compressor cycling/stopped
Check
Failed digital unloader valve (DUV)
Replace
6.8
ABNORMAL NOISE OR VIBRATIONS
Condition
Possible Cause
Remedy/Refer-
ence Section
Compressor
Compressor start up after an extended shutdown
Normal
Brief chattering when manually shut down
Compressor operating in reverse
Loose mounting bolts or worn resilient mounts
Tighten/Replace
Loose upper mounting
Liquid slugging
Condenser or Evaporator Fan
Bent, loose or striking venturi
Check
Worn motor bearings
Bent motor shaft
6.9
MICROPROCESSOR MALFUNCTION
Condition
Possible Cause
Remedy/Refer-
ence Section
Will not control
Incorrect software and/or controller configuration
Check
Defective sensor
Defective wiring
Check
Low refrigerant charge
6.7
ABNORMAL PRESSURES
Condition
Possible Cause
Remedy/Refer-
ence Section
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......