T-365
6–2
6.3
UNIT RUNS BUT HAS INSUFFICIENT COOLING
Condition
Possible Cause
Remedy/Refer-
ence Section
Refrigeration system
Abnormal pressures
Abnormal temperatures
Abnormal currents
Controller malfunction
Evaporator fan or motor defective
Compressor service valves or liquid line shutoff valve par-
tially closed
Open valves
completely
Frost on coil
Digital unloader valve stuck open
Electronic expansion valve
6.4
UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING
Condition
Possible Cause
Remedy/Refer-
ence Section
No operation of any kind
Start
−
Stop switch OFF or defective
Check
Circuit breaker OFF or defective
Check
External power source OFF
Turn ON
No control power
Circuit breaker or fuse defective
Replace
Control Transformer defective
Replace
Evaporator fan internal motor protector open
Heat relay defective
Check
Heater termination thermostat open
Unit will not heat or has insufficient
heat
Heater(s) defective
Heater contactor or coil defective
Replace
Evaporator fan motor(s) defective or running backwards
Evaporator fan motor contactor defective
Replace
Controller malfunction
Defective wiring
Replace
Loose terminal connections
Tighten
Low line voltage
Summary of Contents for 69NT40-561-300
Page 2: ......
Page 4: ......
Page 10: ......
Page 14: ......
Page 22: ......
Page 34: ......
Page 108: ......
Page 116: ......
Page 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Page 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Page 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Page 168: ......
Page 172: ......
Page 173: ......