6. Move the switch on the gas valve to the ON position.
7. Replace the gas section access panels.
8. Turn on the electrical supply to the units.
9. Open the field-installed manual gas valve.

10. Using the BACview controller, enable the unit to run us-

ing the following procedure:

a. On the BACview MAIN screen, press ENTER.

The LOGIN screen will be shown.

b. Enter the PASSWORD (the default admin pass-

word is 1111) and press OK. The DECR and INCR

buttons will appear on the bottom of the screen and

the Shutdown command will flash.

c. Press the DECR button, then press the OK button.

The unit will start after 10 seconds. Shutdown

[OFF] will be shown on the main screen.

11. To test the operation of the gas section, use the BACview

controller to energize heating to turn on the gas. Refer to

unit Controls, Start-Up, Operation, Service and Trouble-

shooting literature for more information.

TO SHUT UNIT OFF

Refer to Fig. 4 while performing the following steps:

1. Disable unit operation by using the BACview controller.

The BACview controller is shipped in the control box

and can be mounted on the unit or at a remote location.

a. On the BACview MAIN screen, press ENTER.

The LOGIN screen will be shown.

b. Enter the PASSWORD (the default admin pass-

word is 1111) and press OK. The DECR and INCR

buttons will appear on the bottom of the screen and

the Shutdown command will flash.

c. Press the INCR button, then press the OK button.

The unit will stop immediately. Shutdown [ON]

will be shown on the main screen.

2. Close the field-installed manual gas shutoff valve.

3. Turn off the electrical power to the unit using the optional

disconnect or the field-installed disconnect and lock off

using proper lockout and tag-out procedures.

4. Remove the gas section panels.
5. Move the switch on the gas valve to the OFF position and

wait 5 minutes before doing any service in the section or

on the piping.

6. Replace gas section access panels.

7. If unit is being shut down because of a malfunction, call

your dealer as soon as possible.
If unit is being shut down because the heating season has

ended, restore electrical power to the unit and reset the

BACview controller to ensure operation of the cooling

system during the cooling season.

Do not use this unit if any part has been under water. Imme-

diately call a qualified service technician to inspect the unit and

to replace any part of the control system and gas control that

has been under water.

MAINTAINING YOUR UNIT

All maintenance should be handled by skilled, experienced

personnel. Your dealer can help you establish a standard

procedure.

For your safety, keep the area around the unit clear and free

of combustible materials, gasoline, and other flammable

liquids and vapors.

To ensure proper functioning of the unit, the flow of com-

bustion and ventilating air must not be obstructed from reach-

ing the unit. Clearance of at least 4 ft on flue and condenser

sides and 6 in. on all other sides is required.

ROUTINE MAINTENANCE AND CARE

FOR THE EQUIPMENT OWNER

Consider the following information before maintaining or

servicing equipment:

WARNING

If the main burners fail to light or the blower fails to start,

shut down gas heating section and call your dealer for ser-

vice. Failure to follow these requirements could result in

serious personal injury.

WARNING

1. Do not turn off the electrical power to unit without

first turning off the gas supply.

2. Never attempt to manually light the main burners on

unit with a match, lighter, or any other flame. If the

electric sparking device fails to light the main burners,

refer to the following shutdown procedures. Call your

dealer as soon as possible.

Failure to follow these procedures can result in serious

fire or personal injury.

IMPORTANT: Should overheating occur or the gas supply

fail to shut off, shut off the manual gas valve to the unit

before shutting off the electrical supply.

WARNING

1. TURN OFF GAS SUPPLY AND THEN ELECTRI-

CAL POWER TO YOUR UNIT BEFORE SERVIC-

ING OR PERFORMING MAINTENANCE.

2. Do not turn off electrical power to this unit without

first turning off the gas supply.

3. When removing access panels or performing mainte-

nance functions inside your unit, be aware of sharp

sheet metal parts and screws. Although special care

has been taken to reduce sharp edges inside the unit,

be extremely careful when handling parts or reaching

into the unit.

Failure to follow these procedures can result in serious

fire or personal injury.

Summary of Contents for 62DA

Page 1: ...l is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of t...

Page 2: ...CONTR OL PANEL OUTS IDE AIR INTAK E HOOD CONDENSATE DR AIN PAN GAS SECTION GAS VALVE MODULATING GAS VALVE OPTIONAL MAIN BURNER SECTION FLAME ROLLOUT SWITCH Fig 1 Typical Gas Section Fig 2 Typical Gas...

Page 3: ...T N A T ON OFF N A T N A T ON OFF STEP 1 Fig 3 To Light Unit STEP 5 STEP 4 STEP 3 STEP 2 STEP 7 STEP 6 STEP 10 STEP 8 STEP 9 a48 924tf a48 925tf a48 930tf a48 931tf a62 420 a62 424 a62 425 a62 426 a6...

Page 4: ...the BACview controller to ensure operation of the cooling system during the cooling season Do not use this unit if any part has been under water Imme diately call a qualified service technician to in...

Page 5: ...ers always use the same size and type of filter that was originally supplied by the installer Heat Exchanger To ensure dependable and efficient heating operation the heat exchanger should be checked b...

Page 6: ...l your dealer 7 Replace gas section access panels Unit Panels After performing any maintenance or service on the unit be sure all panels are securely fastened in place to prevent rain from entering un...

Page 7: ...art up procedures listed in this manual NOTE Before proceeding with the next check turn OFF the electrical power supply to the unit Remove the gas section access panels During the heating season check...

Page 8: ...ht to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53620003 01 Printed in U S A Form 62D 1SO Pg 8 1 09 Replaces New Copyri...

Reviews: