Carrier 59SP2A Product Data Download Page 8

8

Venting System Length Calculations

The Total Equivalent Vent Length (TEVL) for

EACH

combustion air or vent pipe equals the length of the venting system, plus the equivalent

length of elbows used in the venting system from Table 2.
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer’s data for equivalent lengths of flexible vent pipe or other termination systems.

DO NOT ASSUME

that one

foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Tables 1 and 3.

Example 1

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M). Venting system includes,

FOR EACH PIPE

, 100 feet (30 M) of vent pipe,

95 feet (28 M) of combustion air inlet pipe, (3) 90

_

long radius elbows, (2) 45

_

long radius elbows and a factory accessory concentric vent

kit.
Can this application use 2--in. (50 mm ND) PVC/ABS DWV vent piping?

Measure the required linear length of air inlet and vent pipe; insert the

longest of the two here:

100 ft

Use length of the longer of the vent

or air inlet piping system

Add equiv length of (3) 90º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

3

x

3 ft

=

9 ft.

From Table 2

Add equiv length of (2) 45º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

2

x

1.5 ft

=

3 ft.

From Table 2

Add equiv length of vent termination

0 ft.

From Table 2

Add correction for flexible vent pipe, if any

0 ft.

From Vent Manufacturer’s instructions;

zero for PVC/ABS DWV

Total Equivalent Vent Length (TEVL)

112 ft.

Add all of the above lines

Maximum Equivalent Vent Length (MEVL)

127 ft.

For 2” pipe from Table 1

Is TEVL less than MEVL?

YES

Therefore, 2” pipe may be used

Example 2

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) Venting system includes,

FOR EACH PIPE

, 100 feet (30 M) of vent pipe,

95 feet (28 M) of combustion air inlet pipe, (3) 90

_

long radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6.1

M) of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
Assume that one meter of flexible 60 mm or 80 mm polypropylene pipe equals 1.8 meters of PVC/ABS pipe.

VERIFY FROM VENT

MANUFACTURER’S INSTRUCTIONS.

Can this application use 60 mm (O.D.) polypropylene vent piping? If not what size piping can be used?

Measure the required linear length of air inlet and vent pipe; insert the

longest of the two here:

100 ft

Use length of the longer of the vent

or air inlet piping system

Add equiv length of (3) 90º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

3

x

3 ft

=

9 ft.

From Vent Manufacturer’s instructions

Add equiv length of (2) 45º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

0

x

=

0 ft.

From Vent Manufacturer’s instructions

Add equiv length of vent termination

9 M

x

3 ft/M

=

18 ft.

From Vent Manufacturer’s instructions

Add correction for flexible vent pipe, if any

1.8

x

20 ft

=

36 ft.

From Vent Manufacturer’s instructions

Total Equivalent Vent Length (TEVL)

163 ft.

Add all of the above lines

Maximum Equivalent Vent Length (MEVL)

127 ft.

For 2” pipe from Table 1

Is TEVL less than MEVL?

NO

Therefore, 60mm pipe may NOT be used;

try 80 mm

Maximum Equivalent Vent Length (MEVL)

250 ft.

For 3” pipe from Table 1

Is TEVL less than MEVL?

YES

Therefore, 80 mm pipe may be used

59SP5A

Summary of Contents for 59SP2A

Page 1: ...tible humidity control system S ComfortFan technology allows control of continuous fan speed from a compatible thermostat S Ideal height 35 889 mm cabinet short enough for taller coils but still allows enough room for service S Silicon Nitride Power Heat Hot Surface Igniter S External Media Filter Cabinet included S 4 way multipoise design for upflow downflow or horizontal installation with unique...

Page 2: ...nhancement for select Carrier air conditioner or heat pump systems It uses less electrical power than its PSC counterpart and also has a wider range of speeds Reliable Heat Exchanger Design The aluminized steel clam shell primary heat exchanger was re engineered to achieve greater efficiency out of a smaller size The first two passes of the heat exchanger are based on the current 80 product a desi...

Page 3: ...r Certified Watt Data KGAWF1506UFR Electrical Data 040 10 040 12 060 12 060 14 080 16 080 20 100 20 120 22 Input Voltage Volts Hertz Phase 115 60 1 Operating Voltage Range Min Max 104 127 Maximum Input Amps Amps 7 4 7 4 7 5 9 1 9 1 11 6 11 7 11 7 Unit Ampacity Amps 10 3 10 3 10 4 12 4 12 4 15 5 15 6 15 6 Minimum Wire Size AWG 14 14 14 14 14 12 12 12 Maximum Wire Length Minimum Wire Size Feet 36 36...

Page 4: ...20 120 000 BTU 140 140 000 BTU Not all familes have these models Example of Model Number 0 90 AFUE 2 92 AFUE 3 93 AFUE 5 95 AFUE 6 96 AFUE 7 97 AFUE A12373 FURNACE COMPONENTS RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS VALVE MAIN LIMIT SWITCH BEHIND GAS VALVE REPRESENTATIVE DRAWING ONLY SOME MODELS MAY VARY IN APPEARANCE ELECTRICAL JUNCTION BOX IF REQUIRED LOCATION MAY VARY MEDIA CABINET OPE...

Page 5: ...N42011SP D D D D D D D D Gas Orifice Kit 42 Nat Gas LH32DB207 D D D D D D D D Gas Orifice Kit 43 Nat Gas LH32DB202 D D D D D D D D Gas Orifice Kit 44 Nat Gas LH32DB200 D D D D D D D D Gas Orifice Kit 45 Nat Gas LH32DB205 D D D D D D D D Gas Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D D Gas Orifice Kit 47 Nat Gas LH32DB078 D D D D D D D D Gas Orifice Kit 48 Nat Gas LH32DB076 D D D D D D D D Gas ...

Page 6: ...5 Yellow 1810 1760 1725 1685 1640 1600 1555 1520 1480 1415 Blue 1385 1340 1285 1240 1200 1140 1090 1050 995 950 Orange 1560 1520 1475 1430 1385 1335 1295 1240 1200 1150 Red 1055 985 910 860 795 750 680 615 565 495 100 20 BOTTOM or TWO SIDES 4 5 Gray 2340 2295 2250 2195 2110 2030 1935 1835 1725 1605 Yellow 1950 1900 1855 1800 1755 1705 1655 1605 1560 1485 Blue 1750 1700 1650 1605 1555 1500 1455 139...

Page 7: ...A NA 60 000 23 7 0 119 36 3 210 64 0 235 71 6 NA 80 000 15 4 6 59 18 0 155 47 2 210 64 0 232 70 7 100 000 NA 19 5 8 98 29 9 211 64 3 236 71 9 120 000 NA NA 8 2 4 86 26 2 224 68 3 140 000 4 NA NA NA 79 24 1 158 48 2 4001 to 4500 1219 to 1370 40 000 36 11 0 177 53 9 205 62 5 NA NA 60 000 21 6 4 115 35 1 204 62 2 228 69 5 NA 80 000 14 4 3 56 17 1 150 45 7 202 61 6 224 68 3 100 000 NA 17 5 2 94 28 7 2...

Page 8: ...nt Vent Length TEVL 112 ft Add all of the above lines Maximum Equivalent Vent Length MEVL 127 ft For 2 pipe from Table 1 Is TEVL less than MEVL YES Therefore 2 pipe may be used Example 2 A direct vent 60 000 Btuh furnace installed at 2100 ft 640 M Venting system includes FOR EACH PIPE 100 feet 30 M of vent pipe 95 feet 28 M of combustion air inlet pipe 3 90_ long radius elbows and a polypropylene ...

Page 9: ...8 63 19 2 8001 to 9000 2438 to 2743 40 000 10 3 0 121 36 9 130 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51 8 120 000 NA NA NA 56 17 1 164 50 0 140 000 4 NA NA NA 23 7 0 42 12 8 9001 to 10 000 2743 to 3048 40 000 5 1 5 110 33 5 115 35 1 NA NA 60 000 NA 76 23 2 142 43 3 156 47 5 NA 80 000 NA 31 9 4 103 31 4 1...

Page 10: ...0 2 33 8 27 1 6 1 21 3 47 9 40 5 32 6 20 30 Ft 20 25 23 14 1 20 70 94 77 57 20 70 113 94 71 M 6 1 7 6 7 0 4 3 0 3 6 1 21 3 28 7 23 5 17 4 6 1 21 3 34 4 28 7 21 6 40 40 Ft 20 14 12 3 0 20 70 71 56 38 20 70 86 70 50 M 6 1 4 3 3 7 0 9 0 0 6 1 21 3 21 6 17 1 11 6 6 1 21 3 26 2 21 3 15 2 100000 20 10 Ft N A 25 99 89 78 N A 25 110 233 265 N A 25 110 235 229 M N A 7 6 30 2 27 1 23 8 N A 7 6 33 5 71 0 80 ...

Page 11: ...PPLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sides of Supply Plenum 1 in 25 mm Sides 0 0 mm Vent 0 0 mm Top of Furnace 1 in 25 mm Recommended Consult your local building codes COMBUSTION AIR PIPE FOR NON DIRECT 1 PIPE VENT APPLICATION FIELD SUPPLI...

Page 12: ... 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the plenum dimensions shown above Concentric Vent Kit A93086 A concentric vent kit allows vent and combustion air pipes to terminate through a single exit in a roof or side wall One pipe runs inside the ot...

Page 13: ...D SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y te...

Page 14: ...NSIONS IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendations for equivalent diameters a For 800 CFM 16 in 406 mm round or 14 1 2 x 12 in 368 x 305 mm rectangle b For 1200 CFM 20 in 508 mm round or 14 1 2 x 19 1 2 in 368 x 495 mm rectan...

Page 15: ...e as an option _____________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted galvanized steel Draft Inducer Motor Draft inducer motor shall be single speed PSC design Primary Heat Exchangers Primary heat exchangers shall be 3 Pass corrosion resistant aluminized steel of fold and crimp sectional design and applied operating under negative pressure Secondary Heat Exchange...

Page 16: ...S 7310 W Morris St S Indianapolis IN 46231 Edition Date 05 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 59SP5A 05PD Replaces 59SP5A 04PD 59SP5A ...

Reviews: