51
Table 16 – Maximum Equivalent Vent Length -- Ft. (M)
NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows.
Use Table 17 - Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
Single Stage 92%
Unit Size
40,000
Outlet choke
required under 10
ft. TEVL
60,000
80,000
100,000
120,000
140,000
A
lti
tude
(fe
et
)
Pipe Dia.
(in)
1 ½
2
2 ½
1 ½
2
2 ½
3
1 ½
2
2 ½
3
4
2
2 ½
3
4
2 ½
3
4
2 ½
3
4
0-2000
20
85
185
20
100
175
200
15
50
130 175
200
20
80
175
200
10
75
185
5
65
155
2001-3000
15
80
175
95
165
185
10
45
125
165
185
15
75
165
185
70
175
N/A
60
140
3001-4000
70
160
15
90
155
175
115
155
175
155
175
5
65
165
120
4001-4500
10
65
155
85
150
170
40
110
150
165
10
70
170
N/A
60
160
50
110
4501-5000
60
145
80
165
145
160
65
150
165
45
100
5001-6000
55
130
75
140
155
35
100
135
150
140
155
155
35
80
6001-7000
5
45
120
10
70
130
145
N/A
30
90
125
140
60
135
145
50
140
30
65
7001-8000
40
110
65
120
135
120
125
N/A
55
125
135
45
130
25
45
8001-9000
N/A
30
95
5
60
115
125
25
80
110
115
50
115
125
40
120
15
30
9001-10000
25
85
N/A
55
105
115
20
75
100
105
45
100
115
30
115
10
15
Meters / MM
Single Stage 92% - Metric
Unit Size
40,000
Outlet choke
required under 10
ft. TEVL
60,000
80,000
100,000
120,000
140,000
A
lti
tude
(me
te
rs
)
Pipe Dia.
(mm)
38
51
64
38
5
64
76
38
51
64
76
102
51
64
76
102
64
76
102
64
76
102
0-610
6
26
57
6.5
31
54
61
2
16
40
54
61
6
25
54
61
3
23
57
1.5
21
48
611-914
4.5
24
53
29
51
57
3
15
38
51
57
5
23
51
57
21
54
N/A
18
42
915-1219
22
49
5
27
48
54
36
48
53
48
54
1.5
20
51
36
1220-1370
3
20
47
26
46
52
13
34
46
51
3
22
52
N/A
19
50
16
33
1371-1524
19
45
24
51
45
50
21
46
51
14
31
1525-1829
17
41
82
43
47
11
31
42
46
43
48
48
11
25
1830-2134
1.5
15
37
3
22
40
44
N/A
10
27
39
42
19
41
45
16
43
9
20
2135-2438
12
34
20
37
42
36
39
N/A
18
38
42
14
40
7
15
2439-2743
N/A
10
30
1.5
19
35
38
8
26
34
36
15
36
39
13
38
5
10
2744-3048
8
26
N/A
17
33
36
7
24
31
33
14
34
36
12
35
3.5
5
Long
Medium
Mitered
Concentric
Standard 2-in., 3-in., or
optional 4-in. termination.
ELBOW CONFIGURATIONS
VENT TERMINAL CONFIGURATIONS
A13110
Table 17 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)
Pipe Diameter (in):
1-1/2
2
2-1/2
3
4
Mitered 90º Elbow
8
(2.4)
8
(2.4)
8
(2.4)
8
(2.4)
8
(2.4)
Medium Radius 90º Elbow
5
(1.5)
5
(1.5)
5
(1.5)
5
(1.5)
5
(1.5)
Long Radius 90º Elbow
3
(0.9)
3
(0.9)
3
(0.9)
3
(0.9)
3
(0.9)
Mitered 45º Elbow
4
(1.2)
4
(1.2)
4
(1.2)
4
(1.2)
4
(1.2)
Medium Radius 45º Elbow
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
2.5
(0.8)
Long Radius 45º Elbow
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
1.5
(0.5)
Tee
16
(4.9)
16
(4.9)
16
(4.9)
16
(4.9)
16
(4.9)
59SC
2C