59CU5A: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
55
Electrical Controls and Wiring
The electrical ground and polarity for 115-v wiring must be properly
maintained. See field wiring information, see
, and for furnace
wiring information, see
NOTE:
If the polarity is not correct, the STATUS LED on the control
will flash rapidly and prevent the furnace from heating. The control
system also requires an earth ground for proper operation of the control
and flame-sensing electrode.
The 24-v circuit contains an automotive-type, 3-amp. fuse located on the
control, see
. Any shorts of the 24-v wiring during installation,
service, or maintenance will cause this fuse to blow. If fuse replacement
is required, use ONLY a 3-amp. fuse. The control LED will display a 24
flash code when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls. The
control in this furnace is equipped with a Status Code LED
(Light-Emitting Diode) to aid in installation, servicing, and
troubleshooting. The furnace control LED is either ON continuously,
rapid flashing or displaying a code composed of 2 digits. The first digit
is the number of short flashes, the second digit is the number of long
flashes.
For an explanation of status codes, refer to service booklet located on
blower access door (see
), or the Service guide at the end of this
manual.
The stored status code will not be erased from the control memory, if
115- or 24-v power is interrupted. The control will store up to the last 7
Status Codes in order of occurrence.
1. To retrieve status code, proceed with the following:
NOTE:
NO thermostat signal may be present at control, and all
blower-OFF delays must be completed.
a. Leave 115-v power to furnace turned on.
b. Look into blower access door sight glass for current LED status.
c. Remove blower door.
NOTE:
The Status Codes cannot be retrieved by disconnecting the limit
switch. To retrieve Status Codes, follow the procedure below:
2. Turn Setup Switch, SW1-1 “ON.”
3. Manually close blower door switch.
4. Control will flash up to 7 Status Codes.
5. The last Status Code, or 8
th
Code, will be status code 11.
6. Turn SW1-1 “OFF.”
7. Amber LED will be ON continuous which indicated proper
opertation.
8. Release blower door switch, install blower door and refer to the
SERVICE label on the blower door for more information.
A200311
Fig. 70 – Service Label Information
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than one electrical supply to the furnace. Check
accessories and cooling unit for additional electrical supplies that must
be shut off during furnace servicing. Lock out and tag switch with a
suitable warning label.