
NOTE:
For horizontal applications, the top-most flange may be
bent past 90 degrees to allow the evaporator coil to hang on the
flange temporarily while the remaining attachment and sealing of
the coil are performed.
Downflow Furnaces
Connect supply-air duct to supply-air outlet on furnace. Bend
flange inward past 90° with wide duct pliers. (See Fig. 14.) The
supply-air duct must be connected to ONLY the furnace supply-
outlet or air conditioning coil casing (when used). When installed
on combustible material, supply-air duct must be connected to
ONLY the accessory subbase, KGASB0201ALL, or a factory
approved air conditioning coil casing. DO NOT cut main furnace
casing to attach supply side air duct, humidifier, or other accesso-
ries. All accessories MUST be connected to duct external to
furnace casing.
Return Air Connections
FIRE HAZARD
Failure to follow this warning could cause a fire, personal
injury, or death.
Never connect return-air ducts to the back of the furnace.
Follow instructions below.
Downflow Furnaces
The return-air duct must be connected to return-air opening
(bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and most
horizontal furnaces. Bypass humidifier connections should be
made at ductwork or coil casing sides exterior to furnace. (See Fig.
19.)
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace
casing as shown in Fig. 1. Bypass humidifier may be attached into
unused return air side of the furnace casing. (See Fig. 18 and 20.)
Not all horizontal furnaces are approved for side return air
connections. (See Fig. 20.)
GAS PIPING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test
for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning coud result in personal injury,
death, and/or property damage.
Use proper length of pipe to avoid stress on gas control
manifold and a gas leak.
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S. and the
NSCNGPIC in Canada.
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
NOTE:
In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed
plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are
used, they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by
the state of Massachusetts.
Table 5—Air Delivery - CFM (With Filter)* (Continued)
FURNACE
SIZE
RETURN-AIR
INLET
SPEED
EXTERNAL STATIC PRESSURE (IN. WC)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
048135
Bottom
or
Side(s)
High
Med-High
Med-Low
Low
2090
1790
1545
1325
2010
1755
1525
1320
1930
1705
1500
1295
1835
1640
1450
1265
1710
1550
1380
1210
1590
1465
1315
1150
1470
1360
1215
995
1335
1210
1005
865
1025
945
855
745
835
785
670
540
066135
Bottom
Only
High
Med-High
Med-Low
Low
2485
2195
1880
1640
2400
2150
1850
1635
2310
2090
1820
1615
2215
2000
1780
1585
2110
1920
1715
1530
2000
1825
1635
1465
1880
1720
1540
1370
1725
1565
1415
1255
1535
1405
1290
1150
1355
1255
1160
1040
Bottom Sides or
1 Side & Bottom
High
Med-High
Med-Low
Low
--
2180
1880
1640
--
2145
1850
1635
2385
2060
1820
1615
2305
2010
1780
1585
2195
1945
1715
1530
2085
1865
1635
1465
1960
1765
1540
1370
1825
1660
1415
1255
1670
1515
1290
1150
1465
1325
1160
1040
1 Side Only
High
Med-High
Med-Low
Low
2320
2125
1845
1640
2250
2065
1825
1620
2155
1995
1765
1580
2055
1910
1710
1540
1970
1815
1650
1485
1855
1710
1570
1410
1725
1610
1475
1330
1600
1490
1370
1220
1450
1340
1240
1080
1280
1175
1100
960
060155
Bottom
Only
High
Med-High
Med-Low
Low
2465
2115
1800
1570
2430
2105
1790
1565
2375
2075
1770
1550
2305
2030
1735
1525
2230
1980
1695
1495
2110
1910
1640
1445
2000
1830
1570
1370
1865
1725
1465
1270
1725
1590
1345
1175
1545
1425
1225
1070
Both Sides Or
1 Side & Bottom
High
Med-High
--
2155
--
2135
2375
2095
2285
2040
2200
1975
2105
1895
1995
1790
1870
1685
1730
1550
1570
1400
1 Side Only
High
Med-High
--
2140
--
2095
2260
2040
2180
1975
2085
1890
1975
1810
1865
1705
1740
1595
1605
1480
1455
1325
*A filter is required for each return-air inlet. Airflow performance included 1-in. washable filter media such as contained in factory-authorized accessory filter rack. To
determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--
Indicates unstable operating conditions.
17
→
→
→
Summary of Contents for 58CTA
Page 57: ...55 ...