Installation Guide
8
69-2565—05
Installer setup
Continued on next page
Setup
Number
Setup Name
Settings & Options (factory default in bold)
0346
Unoccupied Cooling
Setpoint (only when remote
setback is enabled)
80
80°F (27°C)
[Options: 75–90
°F (24–32°C)
]
0347
Fan Ramping
1
ON
0 OFF (Lo, Med, Hi)
0348
Fan Mode
0
User can choose Cycle or Constant 3 speed:
Low, Med, High, Auto
1 Cycle Only - Auto only
0349
Auto Fan Reset
0
OFF
1 Reset back to Auto after 2 hours
2 Reset back to Auto after 4 hours
0535
Temporary Occupied
Duration Limit
3
hours
[Other options: 0–12 hours]
0540
Number of Periods
4
4 Periods
2 2 Periods
0580
Minimum Compressor Off
Time
3
3 minutes
4 4 minutes
5 5 minutes
0600
Heat Temperature Range
Stops
90
90°F (32°C)
[Options: 40–90
°F (4–32°C)
]
0610
Cool Temperature Range
Stops
50
50°F (10°C)
[Options: 50–99
°F (10–37°C)
]
0640
Clock Format
12
12 Hour
24 24 Hour
0650
Extended Fan-on time Heat
0
Off
90 90 seconds
0660
Extended Fan-on time Cool
0
Off
40 40 seconds
0670
Keypad Lockout
0
Unlocked
1 Partial Lockout 1: Locks out schedule and system
changes
2 Partial Lockout 2: Locks out schedule, system,
and fan changes
3 Partial Lockout 3: Locks out schedule, system,
fan, and up/down arrow changes
4 Fully Locked: Entire interface locked/non-func-
tional
0680
Temperature Control Heat
2
Standard
1 Less Aggressive
3 More Aggressive
0685
Recovery Heat Ramp Rate
5
5°F (2.8°C)/hour
[Options: 0–20°F (0–11°C)]
0690
Temperature Control Cool
2
Standard
1 Less Aggressive
3 More Aggressive