amount of heat absorbed from the outside air. So, to maintain
energy--efficient operation, your unit has an automatic defrost

mode.
The defrost mode starts at a preset time interval of 60 minutes,

although, it may be reset to 30, 90 or 120 minutes. Defrost will

start at the preset time only if the ice is sufficient to interfere with
normal heating operation.
After the ice is melted from the coil, or after a maximum of 10
minutes in defrost mode, the unit automatically switches back to

normal heating operation.
Do not be alarmed if steam or fog appears at the outdoor unit
during defrost mode. Water vapor from the melting ice may

condense into a mist in the cold outside air.
During certain weather conditions such as heavy snow and freezing

rain it is not uncommon for ice to build up on the unit grille. This

is normal for these weather conditions. Do not attempt to remove
the ice from the unit grille. This condition will not affect the proper

function of the unit and will clear within a few days.

Emergency Heating Mode

In the event of primary unit heat failure, the emergency heat mode

allows your supplemental heating source to keep your home or

office warm until your unit can be serviced. Contact your dealer in
the event of primary unit heat failure.

MAINTENANCE AND SERVICE

This section discusses maintenance that should be performed by
your dealer and care you, as the owner, may wish to handle for

your new unit.

Routine Maintenance

All routine maintenance should be handled by skilled, experienced
personnel. Your dealer can help you establish a standard procedure.
To assure proper functioning of the unit, flow of condenser air
must not be obstructed from reaching the unit. Clearance from the

top of the unit is 48 in. (1219 mm). Clearance of at least 36 in.

(914 mm) is required on sides except the power entry side (42 in.
[1067 mm] clearance) and the duct side (12

in. [305 mm]

minimum clearance).

Maintenance and Care for the Equipment Owner

Before proceeding with those things you might want to maintain
yourself, please carefully consider the following:

FIRE, EXPLOSION, ELECTRICAL SHOCK, CUT

HAZARD

Failure to follow this warning could result in personal

injury, death or property damage.

1. TURN OFF ELECTRICAL POWER TO YOUR UNIT

BEFORE

SERVICING

OR

PERFORMING

MAINTENANCE AND INSTALL A LOCK--OUT
TAG. THERE MAY BE MORE THAN ONE DISCON-
NECT SWITCH.

2. When

removing

access

panels

or

performing

maintenance functions inside your unit, be aware of

sharp sheet metal parts and screws. Although special care
is taken to reduce sharp edges to a minimum, be
extremely careful when handling parts or reaching into

the unit.

!

WARNING

Air Filters

The air filter(s) should be checked every 3 or 4 weeks and changed

or cleaned whenever it becomes dirty. Dirty filters produce

excessive stress on the blower motor and can cause the motor to
overheat and shut down.
This unit must have an air filter in place before it can be operated.
These filters should be located in at least one of two places. In

many applications, the installer will provide return air filter grilles

mounted on the wall or ceiling of the conditioned structure. In the
instance of filter grilles, the filters can simply be removed from the

grille and replaced.
The other typical application is an accessory filter rack installed

inside the unit itself. The following information is given to assist in

changing filters used in these internal filter racks.
Filter kits are available as a purchased accessory or a factory

installed option. The same filter kit is included with the accessory
economizers and factory installed economizers.

Table 1 – Replacement Filter Sizes

50EZ Unit Size

Filter Size

24

2 each 20 x 12 x 1

(508 x 305 x 25 mm)

30---36

2 each 20 x 12 x 1

(508 x 305 x 25 mm)

42-48

1 each 24 x 14 x 1 (610 x 356 x 25 mm),

24 x 16 x 1 (610 x 406 x 25 mm)

60*

1 each 24 x 16 x 1 (610 x 406 x 25 mm),

24 x 18 x 1 (610 x 457 x 25 mm)

*Units with bent indoor coil.

50VT Unit Size

Filter Size

24

2 each 20 x 12 x 1

(508 x 305 x 25 mm)

30

2 each 20 x 12 x 1

(508 x 305 x 25 mm)

36-42

1 each 24 x 14 x 1 (610 x 356 x 25 mm),

24 x 16 x 1 (610 x 406 x 25 mm)

48---60*

1 each 24 x 16 x 1 (610 x 406 x 25 mm),

24 x 18 x 1 (610 x 457 x 25 mm)

*Units with bent indoor coil.

To replace or inspect filters in accessory filter rack:

1. Remove the filter access panel (See Fig. 3) using a 5/16--in.

nut driver.

2. Remove the filter(s) by pulling it out of the unit. If the

filter(s) is dirty, clean or replace with a new one.

When installing the new filter(s), note the direction of the airflow
arrows on the filter frame.
If you have difficulty locating your air filter(s) or have questions
concerning proper filter maintenance, contact your dealer for

instructions. When replacing filters, always use the same size and

type of filter that was supplied originally by the installer. See Table
1 for filter sizes supplied with accessory filter rack.

Access Panels

Filter Access Panel

For Accessory Filter Rack

A09044

Fig. 2 -- Accessory Filter Rack Access Panel

Summary of Contents for 50VT-B

Page 1: ...tem require maintenance or service UNIT INFORMATION Model _____________________________________ Serial ______________________________________ ACCESSORIES List type and model _____________________________________________ _____________________________________________ _____________________________________________ INSTALLATION INFORMATION Date Installed ________________________________ DEALERSHIP CONT...

Page 2: ... Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicing furnaces CAUTION OPERATING YOUR UNIT The operation of your heat pump system is controlled by the indoor thermostat You simply adjust the thermostat and it maintains the indoor temp...

Page 3: ...els or performing maintenance functions inside your unit be aware of sharp sheet metal parts and screws Although special care is taken to reduce sharp edges to a minimum be extremely careful when handling parts or reaching into the unit WARNING Air Filters The air filter s should be checked every 3 or 4 weeks and changed or cleaned whenever it becomes dirty Dirty filters produce excessive stress o...

Page 4: ...all 24 x 16 x 1 610 x 406 x 25 filter When installing the new filters note the direction of the airflow arrows on the filter frame which should be pointing at the indoor coil 3 Reinstall filter access door ensuring opening is air and watertight Fans and Fan Motor Periodically check the condition of fan wheels and housings and fan motor shaft bearings Contact your dealer for the required annual mai...

Page 5: ...ssure proper connection 8 Inspection for leaks in the refrigerant circuit Pressure and temperature check to determine appropriate refrigerant charge 9 Operational check of the unit to determine working conditions Repair or adjustment should be made at this time Your servicing dealer may offer an economical service contract that covers seasonal inspections Ask for further details Complete service i...

Page 6: ...p S 7310 W Morris St S Indianapolis IN 46231 Edition Date 09 14 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No OM50EZ VT 04 Replaces OM50EZ VT 03 ...

Reviews: