27
Table 10 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
†Indicates standard motor and drive package.
**Indicates alternate drive package only.
††Indicates high-static motor and drive package.
Table 11A — Electric Heater Static Pressure* (in. wg) — 50TFQ008-012
*The static pressure must be added to external static pressure. The sum and the evaporator
entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.
Table 11B — EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg) — 50TFQ008-012
*The static pressure must be added to external static pressure. The sum and the outdoor
entering-air cfm should then be used in conjunction with the Fan Performance tables to
determine blower rpm and watts.
UNIT
50TFQ
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
008†
840
815
790
765
740
715
690
665
635
615
590
—
—
008**
935
910
885
860
835
810
785
760
735
710
685
—
—
008††
1080
1025
1007
988
970
952
933
915
897
878
860
—
—
009†
935
910
885
860
835
810
785
760
735
710
685
—
—
009††
1080
1025
1007
988
970
952
933
915
897
878
860
—
—
012†
935
910
885
860
835
810
785
760
735
710
685
—
—
012**
1085
1060
1035
1010
985
960
935
910
885
860
835
—
—
012††
1130
1112
1087
1062
1037
1012
987
962
937
912
887
862
830
COMPONENT
CFM
2250
2500
3000
3500
4000
4500
5000
5500
6000
6250
1 Heater Module
0.02
0.03
0.05
0.07
0.08
0.10
0.12
0.14
0.16
0.17
2 Heater Modules
0.03
0.05
0.07
0.09
0.12
0.14
0.16
0.19
0.21
0.20
COMPONENT
CFM
2250 2500
2750
3000 3250 3500 3750 4000 4250 4500 4750
5000 5250 6250
Vertical EconoMi$er IV and EconoMi$er2
0.06 0.075
0.09
0.115 0.13
0.15
0.17 0.195 0.22
0.25 0.285 0.325 0.36
—
Horizontal EconoMi$er IV and EconoMi$er2
—
0.1
0.125
0.15
0.18
0.21
0.25 0.275
0.3
0.34 0.388
—
—
—