41
FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS (cont)
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils. See
page 49 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous watts
are 2562. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Indoor-Fan Motor Performance table
on page 52 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
50TFQ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
789
0.40
420
896
0.53
557
990
0.67
704
1072
0.83
872
1153
1.00
1051
1600
826
0.46
483
931
0.61
641
1020
0.75
788
1101
0.91
956
1178
1.09
1145
1700
865
0.54
567
966
0.69
725
1051
0.84
883
1133
1.01
1061
1205
1.18
1240
1800
905
0.62
661
1002
0.78
820
1084
0.93
977
1163
1.10
1156
1235
1.29
1355
1900
945
0.72
757
1037
0.88
925
1119
1.04
1093
1194
1.21
1271
1266
1.40
1471
2000
984
0.82
862
1072
0.98
1030
1154
1.16
1219
1226
1.33
1397
1297
1.53
1608
2100
1024
0.93
977
1108
1.10
1156
1192
1.29
1355
1259
1.47
1545
1327
1.66
1744
2200
1064
1.05
1103
1145
1.22
1282
1225
1.43
1503
1294
1.62
1702
1359
1.80
1902
2300
1104
1.18
1240
1183
1.36
1429
1260
1.57
1650
1330
1.78
1870
1392
1.97
2070
2400
1145
1.32
1387
1222
1.45
1524
1296
1.73
1818
1365
1.94
2038
1426
2.15
2259
2500
1186
1.48
1555
1262
1.68
1765
1331
1.89
1986
1400
2.12
2227
1461
2.34
2459
50TFQ006 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1221
1.17
1229
1256
1.30
1366
1283
1.32
1387
1303
1.22
1282
1345
1.34
1390
1600
1252
1.27
1334
1311
1.45
1524
1340
1.58
1660
1330
1.61
1692
1373
1.77
1834
1700
1278
1.37
1439
1345
1.57
1650
1397
1.76
1849
1424
1.89
1986
1470
2.08
2153
1800
1303
1.48
1555
1371
1.69
1776
1433
1.90
1996
1480
2.09
2196
1528
2.30
2381
1900
1330
1.59
1671
1396
1.80
1902
1460
2.03
2133
1517
2.25
2364
1566
2.47
2563
2000
1362
1.73
1818
1422
1.94
2038
1485
2.16
2270
1544
2.40
2522
1594
2.64
2734
2100
1393
1.87
1965
1452
2.08
2185
1510
2.31
2427
1570
2.55
2674
1620
2.80
2905
2200
1423
2.02
2122
1483
2.24
2354
1538
2.46
2585
1594
2.71
2821
1645
2.98
3087
2300
1454
2.18
2291
1515
2.41
2532
1571
2.64
2758
1623
2.88
2976
1675
3.17
3280
2400
1485
2.36
2480
1544
2.59
2721
1604
2.84
2947
1657
3.07
3152
1710
3.38
3497
2500
1518
2.55
2679
1574
2.78
2905
1633
3.03
3134
1692
3.28
3345
1746
3.61
3736
Bhp
—
Brake Horsepower Input to Fan
FIOP —
Factory-Installed Option
Watts —
Input Watts to Motor