Copyright 2001 Carrier Corporation

Form 50TFQ-2PD

Single-package standard efficiency
rooftop heat pumps with:
• State-of-the-art defrost system
• Dependable 4-way valve operation
• Refrigerant filter strainer and

accumulator

• Field-installed electric heaters

available

• Advanced hermetic compressors

mounted on vibration isolators

• Factory-installed Apollo communi-

cating controls, non-fused discon-
nect switch, and convenience 
outlet available

Features/Benefits

The 50TFQ standard 
efficiency rooftop product 
line combines advanced 
technology with 
serviceability, performance, 
and flexibility.

State-of-the-art defrost system 

uses time and temperature to keep the 
outdoor coil frost-free for economical, 
dependable operation.

Dependable 4-way valve opera-
tion 

safely and efficiently accom-

plishes cycle reversals, defrost, and 
normal operation.

Refrigerant filter strainer and ac-
cumulator 

ensure performance 

dependability and circuit protection.

Field-installed electric heaters 
available 

in a wide range of capaci-

ties. Single-point wiring kit makes 
installation simple.
NOTE: Some electric heater applica-
tions not available for use with 
factory-installed disconnect switch.

50TFQ004-012

Single-Package

Standard Efficiency

Rooftop Heat Pump Units

3 to 10 Nominal Tons

Product
Data

50TFQ004-007

50TFQ008-012

Summary of Contents for 50TFQ004-007

Page 1: ...ceability performance and flexibility State of the art defrost system uses time and temperature to keep the outdoor coil frost free for economical dependable operation Dependable 4 way valve opera tion safely and efficiently accom plishes cycle reversals defrost and normal operation Refrigerant filter strainer and ac cumulator ensure performance dependability and circuit protection Field installed...

Page 2: ...y of biological growth and is in conform ance of ASHRAE American Society of Heating Refrigeration and Air Conditioning Engineers Standard 62 to meet many Indoor Air Quality IAQ specifications The condensate drain pan offers both bottom and end drain capability to minimize roof penetra tions The bottom drain can be used in conjunction with the thru the bottom connections An external trap must be fi...

Page 3: ...Inter net ready communicating control is de signed specifically for Constant Volume and Variable Volume and Temperature applications This comprehensive con trols system allows all Carrier 3 to 25 ton rooftops to be daisy chained to gether on a roof to create a fully func tional HVAC heating ventilation and air conditioning automation system Model number nomenclature 50 TFQ 004 Z 5 0 1 AA 50 Electr...

Page 4: ...F wb outdoor entering air temperature UNIT 50TFQ NOMINAL TONS STANDARD CFM COOLING HEATING High Temp SOUND RATING Bels Capacity Btuh SEER Capacity Btuh HSPF Belt Drive Direct Drive 004 3 1200 35 600 10 20 10 00 34 400 6 7 8 4 005 4 1600 46 500 10 00 9 70 46 500 7 0 8 0 006 5 2000 57 000 10 00 9 90 57 000 7 5 8 2 UNIT 50TFQ NOMINAL TONS STANDARD CFM COOLING HEATING High HEATING Low IPLV SOUND RATIN...

Page 5: ...c 56 56 56 56 Nominal Rpm High Low Std 860 800 1075 970 1075 970 Alt 1620 1620 1725 High Static 1725 1725 1725 1725 Fan Rpm Range Std 1070 1460 Alt 760 1000 835 1185 900 1300 High Static 1075 1455 1075 1455 1300 1685 1300 1685 Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min Max in Std 2 8 3 8 Alt 1 9 2 9 1 9 2 9 2 4 3 4 High Static 2...

Page 6: ... 1725 1725 1725 Fan Rpm Range Std 590 840 685 935 685 935 Alt 685 935 835 1085 High Static 860 1080 860 1080 830 1130 Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min Max in Std 2 4 3 4 2 8 3 8 2 8 3 8 Alt 2 8 3 8 3 4 4 4 High Static 4 0 5 0 4 0 5 0 2 8 3 8 Nominal Motor Shaft Diameter in Std 5 8 5 8 5 8 Alt 5 8 7 8 High Static 7 8 7 8 7 8 Fan ...

Page 7: ...programmable thermostat provides efficient tem perature control by allowing you to program heating and cooling set backs and set ups with provisions for weekends and holidays Accessory remote sensing package is also available to provide tamperproof control in high traffic spaces Used in conjunction with factory installed Apollo control this thermostat provides a 5 minute recycle timer between mode...

Page 8: ...sted for 100 outdoor air or any proportions of mixed air Like the base unit the economizer is easily converted for horizontal discharge applications Accusensor economizer controls help provide efficient economical economizer operation Accusensor II solid state enthalpy control includes the logic and one sensor to calculate both dry and wet bulb of the outdoor air to provide an accurate enthalpy re...

Page 9: ...roprocessor based con trol gear drive damper system low pressure drop characteristics built in spring return for close upon power loss and an integral barometric damper Also available with optional power exhaust NOTE EconoMi er is available for vertical ductwork applications factory installed A horizontal EconoMi er is available for field installation HAIL GUARD OUTDOOR COIL SALT SPRAY PROTECTION ...

Page 10: ...nit power shutoff May not be used with cer tain electric heat sizes CONVENIENCE OUTLET Factory installed internally mounted and externally accessible 115 v female receptacle Includes 15 amp GFI receptacle with independent fuse protection Voltage required to operate con venience outlet is provided by a factory installed step down transformer ...

Page 11: ...g curb 0 in on horizontal discharge units with electric heat 1 in clearance to ductwork for 1 ft b Outdoor coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optional c Overhead 60 in to assure proper outdoor fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box side 36 ...

Page 12: ...rhead 60 in to assure proper outdoor fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box side 36 in per NEC f Between unit and block or concrete walls and other grounded sur faces control box side 42 in per NEC g Horizontal supply and return end 0 inches 6 With the exception of the clearance for the outdoor coil a...

Page 13: ...are in millimeters 4 Roof curb galvanized steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A00 and 002A00 are for thru the curb type gas Packages CRBTMPWR003A00 and 004A00 are for thru the bottom type gas connections CONNECTOR PKG ACCY B C D ALT DRAIN HOLE GAS POWER CONTROL CRBTMPWR001A00 1 911...

Page 14: ...NPT 3 4 19 NPT 1 2 12 7 NPT CRBTMPWR004A00 3 4 19 NPT 11 4 31 7 NOTES 1 Roof curb accessory is shipped disassembled 2 Insulated panels 1 in thick polyurethane foam 13 4 lb density 3 Dimensions in are in millimeters 4 Roof curb 16 gage steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A00 and 2A0...

Page 15: ...00 Btuh Therefore 17 000 Btuh 35 000 18 000 addi tional electric heat is required Determine additional electric heat capacity in kW Enter the Electric Heating Capacities table page 51 for 50TFQ005 at 208 230 3 phase The 6 5 kW heater at 240 v most closely satisfies the heating required To calculate kW at 230 v use the Multipli cation Factors table 6 5 kW x 92 5 98 kW 6 5 kW x 92 x 3413 20 410 Btuh...

Page 16: ... 3 65 3 54 125 TC 34 2 30 5 26 8 35 9 32 0 29 3 36 8 33 0 31 3 SHC 14 6 19 2 22 9 16 7 22 6 26 3 18 5 25 5 28 4 kW 3 88 3 68 3 49 3 97 3 77 3 62 4 02 3 83 3 74 50TFQ005 4 TONS Temp F Outdoor Entering Air Edb Indoor Entering Air Cfm BF 1200 0 11 1600 0 15 2000 0 22 Indoor Entering Air Ewb F 72 67 62 72 67 62 72 67 62 75 TC 55 5 51 9 47 4 56 9 54 6 50 3 59 3 56 5 52 1 SHC 24 5 31 2 37 4 26 0 35 2 43...

Page 17: ...34 6 20 6 53 6 36 6 31 125 TC 56 5 51 0 46 0 58 2 53 5 49 8 59 4 55 1 53 0 SHC 26 8 34 7 41 9 30 0 40 8 47 3 33 0 46 5 50 5 kW 7 03 6 87 6 65 7 07 6 96 6 82 7 13 7 03 6 96 50TFQ007 6 TONS Temp F Outdoor Entering Air Edb Indoor Entering Air Cfm BF 1800 0 10 2400 0 13 3000 0 19 Indoor Entering Air Ewb F 72 67 62 72 67 62 72 67 62 75 TC 81 1 77 6 72 1 84 0 80 3 75 2 84 2 81 1 77 8 SHC 36 2 46 9 57 0 ...

Page 18: ... 77 6 SHC 36 8 48 6 59 2 42 2 57 8 66 2 45 2 62 0 68 6 48 2 66 6 71 0 kW 9 20 8 74 8 30 9 44 8 96 8 68 9 52 9 02 8 82 9 60 9 12 8 98 50TFQ009 81 2 TONS Temp F Outdoor Entering Air Edb Indoor Entering Air Cfm BF 2400 0 06 3200 0 09 3600 0 11 4000 0 14 Indoor Entering Air Ewb F 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 111 4 102 3 91 0 115 7 108 2 97 6 117 0 110 1 100 4 118 1 111 6 102 5 SHC 51 8 64...

Page 19: ... 8 98 9 54 9 28 9 02 9 60 9 36 9 08 95 TC 121 8 112 0 102 2 126 2 117 4 107 4 127 8 119 0 109 4 130 0 121 2 112 6 SHC 58 4 73 2 87 4 63 8 83 4 101 0 66 0 87 2 104 8 69 6 93 4 110 2 kW 10 34 10 04 9 66 10 46 10 18 9 90 10 52 10 26 9 96 10 62 10 36 10 08 105 TC 116 9 107 2 97 6 122 4 112 4 102 8 123 6 113 8 105 0 124 6 115 6 108 4 SHC 56 6 71 4 85 4 63 0 82 0 98 4 65 0 85 8 101 8 67 8 91 4 106 2 kW ...

Page 20: ... 6 15 2 19 7 18 0 25 4 22 3 30 1 30 1 33 7 33 7 35 3 35 3 39 2 39 2 kW 2 29 2 51 2 68 2 97 3 22 3 41 3 50 3 70 50TFQ005 Return Air F db Cfm Standard Air Air Temperature Entering Outdoor Coil F 0 10 17 30 40 47 50 60 55 1200 Cap 22 7 19 3 26 6 24 4 30 2 27 6 37 4 32 7 43 1 43 1 47 6 47 6 49 8 49 8 57 2 57 2 kW 2 91 3 14 3 35 3 77 4 12 4 40 4 54 5 04 1600 Cap 23 1 19 7 27 2 25 0 30 8 28 1 38 2 33 5 ...

Page 21: ...ap 28 6 24 3 33 7 30 9 37 7 34 4 45 5 39 8 51 6 51 6 56 4 56 4 58 7 58 7 67 0 67 0 kW 4 55 4 73 4 88 5 17 5 42 5 62 5 72 6 09 50TFQ007 Return Air F db Cfm Standard Air Air Temperature Entering Outdoor Coil F 0 10 17 30 40 47 50 60 55 1800 Cap 37 8 32 2 43 9 40 3 48 3 44 1 58 0 50 8 66 2 66 2 72 3 72 3 75 2 75 2 86 0 86 0 kW 4 72 4 97 5 16 5 58 5 96 6 25 6 40 6 95 2400 Cap 37 9 32 2 44 0 40 4 48 5 ...

Page 22: ...0 55 2400 Cap 37 0 34 1 47 1 43 3 54 8 50 0 70 3 61 6 83 2 83 2 92 0 92 0 95 5 95 5 107 9 107 9 kW 5 30 5 81 6 18 6 92 7 56 8 11 8 27 8 92 3200 Cap 40 7 37 4 51 31 47 1 59 28 54 0 75 51 66 2 88 59 88 6 96 82 96 8 100 58 100 6 112 54 112 5 kW 5 88 6 36 6 69 7 35 7 96 8 30 8 44 8 93 3600 Cap 42 6 39 2 53 4 49 1 61 5 56 1 78 1 68 4 90 9 90 9 98 9 98 9 102 6 102 6 114 5 114 5 kW 6 29 6 75 7 07 7 70 8 ...

Page 23: ... 8 86 9 56 10 14 10 62 10 86 11 72 3500 Cap 50 6 43 0 60 2 55 2 63 2 62 2 83 2 72 8 95 2 95 2 103 8 103 8 108 0 108 0 122 8 122 8 kW 7 86 8 20 8 50 9 04 9 52 9 92 10 10 10 80 4100 Cap 51 0 43 2 60 6 55 6 68 6 62 6 83 6 73 2 95 6 95 6 104 2 104 2 108 4 108 4 123 4 123 4 kW 7 74 8 06 8 32 8 82 9 26 9 62 9 78 10 40 4400 Cap 51 0 43 4 60 8 55 8 68 8 62 6 83 8 73 4 95 8 95 8 104 4 104 4 108 6 108 6 123...

Page 24: ... 24 287 0 56 0 26 307 0 57 0 28 335 0 58 0 33 385 1200 0 51 0 26 304 0 51 0 27 323 0 52 0 29 349 0 53 0 34 397 1300 0 45 0 27 321 0 46 0 29 338 0 46 0 31 364 0 47 0 34 408 1400 0 38 0 29 338 0 41 0 30 354 0 43 0 32 378 1500 0 34 0 30 355 0 36 0 31 369 0 38 0 33 392 Bhp Brake Horsepower Input to Fan ESP External Static Pressure in wg FIOP Factory Installed Option Watts Input Watts to Motor 50TFQ004...

Page 25: ...86 0 55 547 1100 746 0 26 259 867 0 35 348 964 0 40 398 1068 0 55 547 1109 0 61 607 1200 785 0 32 318 903 0 41 408 994 0 50 497 1090 0 64 637 1156 0 68 676 1300 826 0 38 378 942 0 48 477 1047 0 60 597 1122 0 70 696 1190 0 76 756 1400 868 0 45 448 984 0 57 567 1067 0 67 666 1160 0 84 766 1237 0 85 845 1500 911 0 53 527 1029 0 66 656 1109 0 77 766 1190 1 00 855 1271 0 95 945 50TFQ004 3 TONS HIGH STA...

Page 26: ...0 35 368 761 0 42 436 818 0 48 504 912 0 61 641 957 0 69 720 1001 0 76 777 1600 681 0 33 347 735 0 40 420 790 0 47 494 845 0 54 567 920 0 68 695 931 0 76 772 1023 0 83 848 1700 718 0 39 410 768 0 46 483 836 0 54 562 873 0 61 641 965 0 76 777 1005 0 84 853 1045 0 91 930 1800 754 0 45 473 801 0 53 557 851 0 61 641 900 0 69 725 992 0 84 858 1032 0 92 940 1071 1 00 1022 1900 791 0 52 546 836 0 60 630 ...

Page 27: ...32 1313 1900 919 0 75 788 1011 0 92 967 1091 1 08 1104 1162 1 25 1277 1232 1 45 1442 2000 958 0 86 904 1046 1 03 1082 1125 1 21 1237 1195 1 38 1410 1262 1 58 1572 50TFQ005 4 TONS HIGH STATIC MOTOR BELT DRIVE cont Airflow Cfm External Static Pressure in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1083 0 74 778 1134 0 80 935 1185 0 88 965 1331 0 ...

Page 28: ...4 552 945 0 72 736 1037 0 88 899 1119 1 04 1063 1194 1 21 1237 2000 936 0 74 756 984 0 82 838 1072 0 98 1001 1154 1 16 1185 1226 1 33 1359 2100 978 0 85 869 1024 0 93 950 1108 1 10 1124 1192 1 29 1318 1259 1 47 1502 2200 1021 0 97 991 1064 1 05 1073 1145 1 22 1247 1225 1 43 1461 1294 1 62 1656 2300 1064 1 10 1124 1104 1 18 1206 1183 1 36 1390 1260 1 57 1604 1330 1 78 1819 2400 1107 1 24 1267 1145 ...

Page 29: ...65 0 76 777 1057 0 92 940 1143 1 10 1124 1212 1 26 1288 1280 1 43 1461 2000 1008 0 87 889 1096 1 04 1063 1177 1 22 1247 1247 1 40 1431 1300 1 57 1604 2100 1051 0 99 1012 1136 1 17 1196 1210 1 35 1380 1284 1 54 1574 1347 1 72 1758 2200 1095 1 12 1145 1173 1 30 1328 1245 1 49 1523 1322 1 70 1737 1380 1 89 1931 2300 1140 1 26 1288 1210 1 47 1502 1284 1 65 1686 1356 1 80 1901 1418 2 07 2115 2400 1185 ...

Page 30: ... 93 859 1108 1 10 998 1190 1 29 1156 1259 1 47 1310 2200 1021 0 97 891 1064 1 05 956 1145 1 22 1097 1225 1 43 1275 1294 1 62 1439 2300 1064 1 10 998 1104 1 18 1064 1183 1 36 1216 1260 1 57 1396 1330 1 78 1578 2400 1107 1 24 1114 1145 1 32 1182 1222 1 52 1353 1296 1 73 1534 1365 1 94 1718 2500 1150 1 39 1241 1186 1 48 1318 1262 1 68 1491 1331 1 89 1674 1400 2 12 1875 2600 1193 1 56 1387 1228 1 65 1...

Page 31: ...7 1340 1 53 1361 1428 1 66 1473 2200 1159 1 15 1081 1214 1 28 1148 1310 1 52 1353 1375 1 63 1447 1459 1 80 1595 2300 1202 1 29 1140 1248 1 38 1233 1358 1 69 1499 1410 1 72 1526 1488 1 93 1709 2400 1237 1 41 1224 1292 1 55 1378 1392 1 81 1604 1460 1 90 1683 1532 2 14 1892 2500 1272 1 53 1335 1335 1 71 1517 1427 1 94 1718 1518 2 16 1910 1575 2 35 2076 2600 1320 1 68 1482 1368 1 81 1604 1458 2 06 182...

Page 32: ... 827 1 83 1621 878 2 12 1875 2800 597 0 89 827 665 1 12 1014 733 1 40 1250 786 1 66 1473 839 1 93 1709 889 2 23 1971 2900 613 0 97 891 679 1 20 1081 745 1 50 1335 799 1 76 1560 850 2 04 1805 900 2 34 2067 3000 629 1 06 965 694 1 29 1156 759 1 59 1413 812 1 88 1665 862 2 15 1901 911 2 46 2171 3100 646 1 15 1039 709 1 39 1241 772 1 70 1508 825 1 99 1761 875 2 28 2015 923 2 58 2275 3200 662 1 25 1123...

Page 33: ... 1 63 1147 815 1 92 1700 866 2 23 1971 3100 646 1 16 1047 714 1 45 1292 773 1 74 1543 828 2 04 1805 878 2 35 2076 3200 662 1 28 1131 729 1 55 1378 787 1 86 1648 841 2 16 1910 891 2 48 2188 3300 679 1 36 1216 744 1 66 1473 801 1 98 1753 854 2 29 2023 904 2 61 2300 3400 695 1 47 1310 759 1 78 1578 816 2 10 1868 867 2 42 2136 917 2 75 2420 3500 712 1 59 1413 774 1 90 1683 830 2 23 1971 881 2 56 2257 ...

Page 34: ... 1901 911 2 46 2171 3100 646 1 15 1039 709 1 39 1241 772 1 70 1508 825 1 99 1761 875 2 28 2015 923 2 58 2275 3200 662 1 25 1123 724 1 50 1335 785 1 80 1595 840 2 11 1866 887 2 41 2128 934 2 71 2386 3300 679 1 35 1207 740 1 61 1430 798 1 91 1691 854 2 24 1980 900 2 54 2240 946 2 85 2504 3400 696 1 46 1301 756 1 73 1534 811 2 02 1788 868 2 37 2093 914 2 69 2369 959 3 00 2629 3500 712 1 57 1396 771 1...

Page 35: ... 1578 816 2 10 1958 867 2 42 2136 917 2 75 2420 3500 712 1 59 1413 774 1 90 1683 830 2 23 1971 881 2 56 2257 930 2 90 2546 3600 729 1 71 1517 790 2 03 1796 845 2 37 2093 895 2 71 2386 943 3 05 2670 3700 745 1 84 1630 805 2 17 1919 860 2 52 2223 909 2 87 2521 956 3 22 2807 3750 754 1 91 1691 813 2 24 1980 868 2 59 2283 917 2 95 2587 963 3 30 2870 3800 762 1 98 1753 821 2 31 2041 875 2 66 2343 924 3...

Page 36: ...779 878 2 22 1962 922 2 44 2203 4100 675 1 42 1267 734 1 67 1482 790 1 89 1674 839 2 12 1875 888 2 33 2058 933 2 56 2309 4200 689 1 52 1353 746 1 77 1569 801 1 99 1761 851 2 23 1971 898 2 45 2212 943 2 69 2424 4300 702 1 61 1430 759 1 88 1665 813 2 11 1866 862 2 34 2067 908 2 58 2326 953 2 81 2533 4400 715 1 72 1526 772 1 99 1761 825 2 22 1962 873 2 46 2221 919 2 71 2442 963 2 94 2651 4500 729 1 8...

Page 37: ...63 0 26 307 0 64 0 28 335 0 65 0 33 385 1200 0 57 0 26 304 0 58 0 27 323 0 56 0 29 349 0 59 0 34 397 1300 0 51 0 27 321 0 53 0 29 338 0 53 0 31 364 0 54 0 34 408 1400 0 44 0 29 338 0 46 0 30 354 0 47 0 32 378 1500 0 39 0 30 355 0 41 0 31 369 0 43 0 33 392 Bhp Brake Horsepower Input to Fan ESP External Static Pressure in wg FIOP Factory Installed Option Watts Input Watts to Motor 50TFQ004 3 TONS AL...

Page 38: ...477 1100 670 0 16 189 812 0 29 288 914 0 35 348 1005 0 43 428 1100 0 52 527 1200 710 0 23 229 840 0 32 318 938 0 40 398 1038 0 50 497 1136 0 59 577 1300 752 0 27 269 868 0 37 368 963 0 45 448 1061 0 56 557 1172 0 65 647 1400 776 0 31 308 891 0 42 418 983 0 51 507 1071 0 60 597 1208 0 70 706 1500 816 0 38 378 924 0 48 477 1014 0 58 577 1097 0 68 676 1245 0 74 776 50TFQ004 3 TONS HIGH STATIC MOTOR B...

Page 39: ... 0 55 578 836 0 62 651 875 0 70 730 913 0 77 809 1004 0 94 988 1046 1 03 1082 1088 1 12 1177 50TFQ005 4 TONS ALTERNATE MOTOR BELT DRIVE cont Airflow Cfm External Static Pressure in wg 1 0 1 1 1 2 1 4 1 6 1 8 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 999 0 66 674 1018 0 67 685 1036 0 68 695 1073 0 71 756 1109 0 75 794 1138 0 79 851 1300 1025 0 74 756 1...

Page 40: ... 929 0 32 0 89 990 0 36 0 89 1018 0 64 0 96 1073 0 71 0 99 1101 0 86 1 06 1183 2200 0 05 0 86 959 0 19 0 92 1023 0 21 0 92 1058 0 50 1 00 1111 0 58 1 02 1138 0 75 1 10 1222 2300 0 08 0 95 1057 0 08 0 95 1097 0 34 1 03 1149 0 39 1 06 1176 0 57 1 13 1261 2400 0 24 1 07 1187 0 29 1 09 1213 0 49 1 17 1300 2500 0 15 1 10 1225 0 15 1 12 1251 0 34 1 20 1340 Bhp Brake Horsepower Input to Fan ESP External ...

Page 41: ...9 1 04 1093 1194 1 21 1271 1266 1 40 1471 2000 984 0 82 862 1072 0 98 1030 1154 1 16 1219 1226 1 33 1397 1297 1 53 1608 2100 1024 0 93 977 1108 1 10 1156 1192 1 29 1355 1259 1 47 1545 1327 1 66 1744 2200 1064 1 05 1103 1145 1 22 1282 1225 1 43 1503 1294 1 62 1702 1359 1 80 1902 2300 1104 1 18 1240 1183 1 36 1429 1260 1 57 1650 1330 1 78 1870 1392 1 97 2070 2400 1145 1 32 1387 1222 1 45 1524 1296 1...

Page 42: ...795 1046 1 01 924 1129 1 19 1072 1209 1 39 1241 2300 954 0 89 827 993 0 96 883 1079 1 13 1022 1160 1 31 1173 1237 1 51 1344 2400 993 1 00 916 1029 1 07 973 1112 1 25 1123 1190 1 43 1275 1264 1 63 1447 2500 1031 1 13 1022 1066 1 20 1081 1145 1 39 1241 1220 1 57 1396 1292 1 77 1569 2600 1070 1 26 1131 1103 1 34 1199 1179 1 52 1353 1251 1 71 1517 1322 1 92 1700 2700 1109 1 41 1258 1140 1 48 1318 1212...

Page 43: ...340 1 66 1473 1397 1 86 1648 2400 1174 1 37 1224 1245 1 57 1396 1305 1 63 1447 1373 1 84 1630 1440 1 95 1726 2500 1201 1 50 1335 1284 1 65 1465 1338 1 75 1552 1402 1 99 1761 1469 2 04 1805 2600 1246 1 67 1482 1312 1 76 1560 1366 1 96 1735 1435 2 10 1858 1494 2 19 1936 2700 1285 1 80 1595 1354 1 95 1726 1403 2 14 1892 1474 2 21 1954 1536 2 46 2171 2800 1304 1 85 1639 1374 2 12 1875 1459 2 25 1989 1...

Page 44: ...1 57 1396 813 1 84 1630 3000 559 0 83 779 637 1 09 989 704 1 35 1207 765 1 66 1473 823 1 94 1718 3100 572 0 90 835 648 1 17 1056 715 1 43 1275 775 1 74 1543 832 2 05 1814 3200 585 0 96 883 660 1 24 1114 727 1 52 1353 785 1 83 1321 841 2 15 1901 3300 598 1 03 940 671 1 32 1182 739 1 62 1439 795 1 91 1691 851 2 26 1997 3400 610 1 10 998 682 1 41 1258 750 1 72 1526 806 2 01 1779 860 2 36 2084 3500 62...

Page 45: ...927 3100 636 1 11 1006 704 1 39 1241 764 1 69 1499 818 1 97 1744 870 2 29 2023 3200 652 1 21 1089 718 1 49 1327 778 1 90 1595 831 2 09 1849 882 2 40 2119 3300 668 1 31 1173 732 1 59 1413 793 1 92 1700 844 2 21 1954 894 2 53 2232 3400 684 1 41 1258 747 1 70 1508 807 2 04 1805 857 2 35 2076 907 2 66 2343 3500 701 1 53 1361 762 1 82 1613 821 2 16 1010 871 2 48 2188 919 2 80 2462 3600 717 1 65 1465 77...

Page 46: ...3 940 671 1 32 1182 739 1 62 1439 795 1 91 1691 851 2 26 1997 3400 610 1 10 998 682 1 41 1258 750 1 72 1526 806 2 01 1779 860 2 36 2084 3500 623 1 17 1056 694 1 50 1335 761 1 82 1613 817 2 11 1866 870 2 47 2180 3600 636 1 25 1123 707 1 60 1422 772 1 93 1709 828 2 23 1971 880 2 57 2266 3700 649 1 33 1190 720 1 71 1517 783 2 03 1796 840 2 35 2076 890 2 69 2369 3750 655 1 37 1224 727 1 77 1569 789 2 ...

Page 47: ... 2 66 2343 3500 701 1 53 1361 762 1 82 1613 821 2 16 1910 871 2 48 2188 919 2 80 2462 3600 717 1 65 1465 777 1 94 1718 835 2 29 2023 885 2 63 2317 932 2 95 2587 3700 733 1 77 1569 792 2 07 1831 849 2 42 2136 899 2 78 2445 945 3 11 2718 3750 742 1 84 1630 800 2 14 1892 856 2 49 2197 907 2 86 2512 952 3 20 2719 3800 750 1 90 1683 807 2 21 1954 863 2 56 2257 914 2 93 2571 958 3 28 2854 3900 767 2 04 ...

Page 48: ...43 789 1 95 1726 841 2 18 1927 4300 628 1 56 1387 690 1 63 1447 747 1 83 1621 798 2 05 1814 849 2 30 2032 4400 639 1 67 1482 701 1 73 1534 757 1 92 1700 807 2 16 1910 858 2 41 2177 4500 651 1 78 1578 712 1 84 1630 767 2 02 1788 817 2 27 2006 866 2 51 2265 4600 662 1 91 1691 722 1 95 1726 777 2 13 1884 827 2 38 2102 874 2 62 2362 4700 674 2 03 1796 733 2 07 1831 787 2 24 1980 836 2 50 2256 882 2 73...

Page 49: ...7 0 32 0 39 0 45 0 53 COMPONENT CFM 2250 2500 3000 3500 4000 4500 5000 5500 6000 6250 1 Heater Module 0 02 0 03 0 05 0 07 0 08 0 10 0 12 0 14 0 16 0 17 2 Heater Modules 0 03 0 05 0 07 0 09 0 12 0 14 0 16 0 19 0 21 0 20 Durablade Economizer 0 02 0 02 0 03 0 04 0 05 0 06 0 07 0 08 0 09 0 09 EconoMi er 0 07 0 09 0 13 0 18 0 23 0 30 0 36 UNIT 50TFQ MOTOR PULLEY TURNS OPEN 0 1 2 1 11 2 2 21 2 3 31 2 4 ...

Page 50: ...TING 1 FAN OPERATING 0 25 0 20 0 15 0 10 0 05 0 00 0 500 1000 1500 2000 FLOW CFM STATIC PRESSURE in wg 3 TO 6 TON 7 1 2 TO 10 TON DURABLADE ECONOMIZER BAROMETRIC RELIEF DAMPER CHARACTERISTICS 50TFQ004 007 ECONOMI ER BAROMETRIC RELIEF DAMPER CHARACTERISTICS DURABLADE ECONOMIZER BAROMETRIC RELIEF DAMPER CHARACTERISTICS 50TFQ008 012 ECONOMI ER POWER EXHAUST PERFORMANCE 50TFQ004 007 ECONOMI ER POWER E...

Page 51: ... 5 14 0 005 208 230 single phase 4 4 8 7 13 0 17 4 21 0 208 230 3 phase 6 5 8 7 16 0 21 0 460 3 phase 6 0 11 5 14 0 23 0 006 208 230 single phase 6 5 8 7 13 0 17 4 21 0 208 230 3 phase 6 5 10 5 16 0 21 0 26 5 460 3 phase 6 0 11 5 14 0 23 0 25 5 UNIT 50TFQ UNIT VOLTAGE 60 Hz ACCESSORY kW 007 208 230 3 phase 6 5 10 5 16 0 21 0 26 5 460 3 phase 6 0 11 5 14 0 23 0 25 5 008 009 208 230 3 phase 10 5 16 ...

Page 52: ...RAW 004 Standard 208 230 0 34 440 3 3 460 1 8 575 1 8 Alternate 208 230 1 00 1000 5 1 460 2 2 575 2 2 High Static 208 230 2 40 2120 6 1 460 2 7 575 2 7 005 Standard 208 230 0 75 850 3 1 460 1 9 575 1 9 Alternate 208 230 1 00 1000 5 1 460 2 2 575 2 2 High Static 208 230 2 40 2120 6 1 460 2 7 575 2 7 006 Standard 208 230 1 20 1340 6 2 460 3 4 575 3 4 Alternate 208 230 1 30 2 40 2120 9 2 6 1 460 2 7 ...

Page 53: ... 3 60 STD 414 508 4 8 40 0 0 8 1 7 8 1 15 8 45 6 0 7 2 12 1 20 16 52 8 8 10 6 21 4 25 20 55 11 5 13 8 25 4 30 24 59 14 0 16 8 29 1 30 27 62 ALT 414 508 4 8 40 0 0 8 2 1 8 9 15 9 48 6 0 7 2 17 9 20 17 55 8 8 10 6 22 2 25 21 59 11 5 13 8 26 2 30 25 62 14 0 16 8 29 9 30 28 65 HIGH STATIC 414 508 4 8 40 0 0 8 2 6 9 4 15 9 62 6 0 7 2 18 4 20 18 70 8 8 10 6 22 7 25 22 73 11 5 13 8 26 7 30 25 76 14 0 16 ...

Page 54: ...4 15 8 21 0 76 0 87 5 143 5 157 9 150 175 135 149 298 309 208 230 3 60 STD 187 254 15 4 124 0 1 5 5 9 26 7 26 7 30 30 26 26 138 138 4 9 6 5 13 6 15 6 43 7 46 2 45 50 42 44 152 154 7 9 10 5 21 9 25 3 54 0 58 3 60 60 51 55 160 163 12 0 16 0 33 3 38 5 68 3 74 8 70 80 65 70 171 177 15 8 21 0 43 9 50 5 81 5 89 8 90 90 77 84 182 189 19 9 26 5 55 2 63 8 95 7 106 4 100 110 90 100 193 202 ALT 187 254 15 4 ...

Page 55: ... 34 118 14 0 16 8 39 4 40 37 121 23 0 27 7 53 0 60 50 132 25 5 30 7 56 7 60 53 135 575 3 60 STD 518 632 9 1 58 4 0 7 2 6 14 0 15 14 76 HIGH STATIC 518 632 9 1 58 4 0 7 3 4 14 7 15 14 84 008 71 2 Tons 208 230 3 60 STD 187 254 13 4 91 0 1 4 5 8 38 8 38 8 40 40 41 41 229 229 7 8 10 5 21 7 25 0 65 9 70 0 70 80 66 69 251 254 12 0 16 0 33 3 38 5 80 4 86 9 90 90 79 85 262 268 18 6 24 8 51 6 59 7 103 3 11...

Page 56: ... 80 74 78 317 320 12 0 16 0 33 3 38 5 88 9 95 4 90 100 88 94 328 334 24 0 32 0 66 6 77 0 130 6 143 6 150 150 126 138 362 372 31 8 42 4 88 3 102 0 157 7 174 8 175 175 151 167 383 397 37 6 50 0 104 4 120 3 177 8 167 6 200 175 170 188 399 415 ALT 187 254 17 2 124 0 1 4 7 5 49 0 49 0 50 50 51 51 314 314 7 8 10 4 21 7 25 0 76 1 80 8 80 90 76 80 336 389 12 0 16 0 33 3 38 5 90 6 97 1 100 100 90 96 347 35...

Page 57: ...460 3 60 STD 414 508 4 8 40 0 0 8 1 7 10 3 15 10 47 6 0 7 2 19 3 20 19 54 8 8 10 6 23 5 25 23 58 11 5 13 8 27 5 30 26 61 14 0 16 8 31 3 35 30 64 ALT 414 508 4 8 40 0 0 8 2 1 11 1 15 11 50 6 0 7 2 20 1 25 20 57 8 8 10 6 24 3 25 24 61 11 5 13 8 28 3 30 27 64 14 0 16 8 32 1 35 31 67 HIGH STATIC 414 508 4 8 40 0 0 8 2 6 11 6 15 12 65 6 0 7 2 20 6 25 20 72 8 8 10 6 24 8 25 24 75 11 5 13 8 28 8 30 28 78...

Page 58: ...8 21 0 76 0 87 5 143 5 157 9 150 175 135 149 298 309 208 230 3 60 STD 187 254 15 4 124 0 1 5 5 9 31 5 31 5 35 35 32 32 143 143 4 9 6 5 13 6 15 6 48 5 51 0 50 60 47 50 157 159 7 9 10 5 21 9 25 3 58 8 63 1 60 70 57 61 165 168 12 0 16 0 33 3 38 5 73 1 79 6 80 90 70 76 176 181 15 8 21 0 43 9 50 5 86 3 94 6 90 100 82 90 187 193 19 9 26 5 55 2 63 8 100 5 111 2 110 125 95 105 198 207 ALT 187 254 15 4 124...

Page 59: ... 0 16 8 41 5 45 40 124 23 0 27 7 55 2 60 52 134 25 5 30 7 58 9 60 56 137 575 3 60 STD 518 632 9 1 58 4 0 7 2 6 15 8 20 16 78 HIGH STATIC 518 632 9 1 58 4 0 7 3 4 16 4 20 16 85 008 71 2 Tons 208 230 3 60 STD 187 254 13 4 91 0 1 4 5 8 43 6 43 6 45 45 46 46 234 234 7 8 10 5 21 7 25 0 70 7 74 8 80 80 71 75 256 259 12 0 16 0 33 3 38 5 85 2 91 7 90 100 85 91 267 272 18 6 24 8 51 6 59 7 108 1 118 2 110 1...

Page 60: ...3 4 80 90 80 84 322 325 12 0 16 0 33 3 38 5 93 7 100 2 100 110 93 99 333 338 24 0 32 0 66 6 77 0 135 4 148 4 150 150 132 144 366 377 31 8 42 4 88 3 102 0 162 5 179 6 175 200 157 172 388 402 37 6 50 0 104 4 120 3 182 6 172 4 200 200 175 193 404 420 ALT 187 254 17 2 124 0 1 4 7 5 53 8 53 8 60 60 57 57 319 319 7 8 10 4 21 7 25 0 80 9 85 1 90 90 82 86 341 344 12 0 16 0 33 3 38 5 95 4 101 9 100 110 93 ...

Page 61: ...n 2 Use the following formula to determine the percent of voltage imbalance Voltage Imbalance Example Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 457 Determine maximum deviation from average voltage AB 457 452 5 v BC 464 457 7 v AC 457 455 2 v Maximum deviation is 7 v Determine percent of voltage imbalance Voltage Imbalance 100 x 1 53 This amount of phase imbalance is satisfactory as it ...

Page 62: ...62 Typical piping and wiring VERTICAL DISCHARGE DUCTING HORIZONTAL DISCHARGE DUCTING LEGEND NEC National Electrical Code ...

Page 63: ...RVS Reversing Valve Solenoid SAT Supply Air Thermostat ST Start Thermistor SW1 Switch Fully Open SW2 Switch Fully Closed SW3 Switch Min Vent Position SW4 Switch Max Vent Position TB Terminal Block TC Thermostat Cooling TH Thermostat Heating TRAN Transformer Field Splice Marked Wire Terminal Marked Terminal Unmarked Terminal Block Splice Splice Marked Factory Wiring Field Control Wiring Field Power...

Page 64: ...oor Fan Motor IFMOVL Indoor Fan Motor Overload Switch LPS Low Pressure Switch LSM Limit Switch Manual Reset MCA Minimum Circuit Amps MTR Motor OAT Outdoor Air Thermostat OFC Outdoor Fan Contactor OFM Outdoor Fan Motor P Plug PL Plug Assembly R Relay RVS Reversing Valve Solenoid SAT Supply Air Thermostat SW1 Switch Fully Open SW2 Switch Fully Closed SW3 Switch Min Vent Position SW4 Switch Max Vent ...

Page 65: ...es the fully open position or until the supply air temperature drops below 52 F When the supply air temperature falls to between 57 F and 52 F the damper will remain at an intermediate open position If the supply air temperature falls below 52 F the damper will modulate closed until it reaches the minimum position or until the supply air temperature is above 52 F When the thermostat is satisfied t...

Page 66: ...e EconoMi er inte grates free cooling with mechanical cooling This is accom plished by the strategies below NOTE Compressors have a 2 minute Minimum On Mini mum Off and Interstage delay timer 1 If Y1 is energized and the room thermostat calls for Y2 2 stage thermostat compressor no 1 and OFM are energized The EconoMi er damper is main tained at its current position 2 If Y1 is energized for more th...

Page 67: ...ensed by the defrost thermostat DFT2 and the defrost timer is at the end of a timed period adjustable at 30 50 or 90 minutes revers ing valve solenoids RVS1 and RVS2 are energized and the OFC is deenergized This switches the position of the reversing valves and shuts off the outdoor fan The electric heaters if installed will be energized The unit continues to defrost until the coil temperature as ...

Page 68: ...WIRING LEGEND C Contactor NOTE Refer to Product Support Bulletin No 93 005 or contact your local Carrier representative for shielded wire applications when wiring the thermostat to the Apollo control and for all communication bus wir ing connections ...

Page 69: ... 50TFQ008 012 UNITS LEGEND C Contactor NC Normally Closed CHAS Ground NO Normally Open COM Common OAT Outdoor Air Thermostat DX Direct Expansion SAT Saturated Air Temperature ECON Economizer VVT Variable Volume Variable GND Ground Temperature HT Heat ...

Page 70: ...cation whether they are in the same building or lo cated throughout town The TEMP System s inherently flexible modular base design supports the exact number of independent single zone systems you require no more no less no compromises Ideal for department stores small office buildings fast food chains schools and hotels a TEMP System is a cost effective way to maintain comfortable building environ...

Page 71: ...ontrols continually monitor and adjust their operation to ensure uninterrupted and personalized comfort for all occupants Through the use of communicating electronic controls VVT Systems are able to provide the comfort of a multiple zone system while using the installation operation and maintenance economics of single zone equipment virtual ly putting an end to the cost vs comfort compromise ...

Page 72: ...bbase are used Airflow Units are draw thru on cooling and blow thru on heating Maximum airflow To minimize the possibility of con densate blow off from indoor coil airflow through units should not exceed 500 cfm ton on 004 012 units Minimum airflow For cooling minimum airflow is 300 cfm ton For 50TFQ units with electric heating required minimum cfm is 900 for 50TFQ004 1200 for 50TFQ005 1500 for 50...

Page 73: ...de filter access with tool less removal 7 Unit shall have standard thru the bottom power connection capability C Fans 1 Indoor blower shall be of the direct or belt driven double inlet forward curved centrifugal type Belt drive shall include an adjustable pitch motor pulley 2 Indoor blower shall be made from steel with a corrosion resistant finish and shall be dynamically balanced 3 Bearings shall...

Page 74: ...eight b Allows for installing and securing ductwork to curb prior to mounting unit on the curb 4 Integrated Economizers a Integrated integral modulating type capable of simultaneous economizer and compressor operation b Includes all hardware and controls to provide cooling with outdoor air c Equipped with low leakage dampers not to exceed 3 leakage at 1 in wg pressure differ ential Durablade econo...

Page 75: ...ure and humidity from one location Automatic humidity control adjusts indoor humidity based on the outdoor tempera ture sensor 18 Outdoor Coil Hail Guard Assembly Hail guard shall protect against damage from hail and flying debris 19 Alternate Motors and or Drives 004 006 008 012 Alternate motors and drives shall be factory installed to provide additional performance range 20 High Static Motor s a...

Page 76: ...at any time specifications or designs without notice and without incurring obligations New Pg 76 Catalog No 525 00011 Printed in U S A PC 111 Form 50TFQ 2PD Replaces 50TFQ 1PD Book 1 4 Tab 5a 5a Carrier Corporation Syracuse New York 13221 1 01 Book 1 Tab OP3b ...