FAN PERFORMANCE (ENGLISH) — VERTICAL DISCHARGE UNITS (cont)

LEGEND

NOTES:

1. Boldface

indicates field-supplied drive required (see Note 3).

2.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a

field-supplied drive.

4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full

range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See

Evaporator-Fan Motor Performance table on page 30 for additional
information.

6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier

representative to verify.

7. To convert Watts to Bhp:

Motor Efficiency: .83

Maximum Continuous Watts: 2120

8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be added to

external static pressure before entering Fan Performance table.

LEGEND

NOTES:

1. Boldface

indicates field-supplied drive required (see Note 3).

2.

indicates field-supplied motor and drive required.

3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a

field-supplied drive.

4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full

range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or

premature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Performance table on page 30 for additional
information.

6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier

representative to verify.

7. To convert Watts to Bhp:

Motor Efficiency: .85

Maximum Continuous Watts: 3313

8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be added to

external static pressure before entering Fan Performance table.

50TFF012 (8.3 TONS) — STANDARD MOTOR (BELT DRIVE)

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts

2500

471

369

552

494

617

611

679

719

740

818

757

881

765

944

811

1034

889

1321

946

1645

2600

483

404

562

530

627

656

685

773

754

881

765

944

775

1025

825

1097

907

1429

959

1771

2700

495

449

573

575

638

710

694

827

757

944

775

1007

793

1088

848

1240

929

1528

975

1878

2800

508

485

583

620

648

755

704

881

759

1007

791

1070

808

1186

887

1357

954

1690

987

1959

2900

521

530

594

665

659

809

714

944

766

1070

807

1150

823

1339

918

1519

963

1834

999

2040

3000

532

630

605

763

670

891

725

1014

778

1148

825

1275

874

1422

926

1613

974

1920

1012

2134

3100

544

677

616

803

680

940

735

1081

787

1216

835

1353

880

1491

933

1656

983

1963

1017

2177

3200

557

716

628

859

690

998

746

1148

796

1284

844

1430

888

1569

934

1718

988

1980

1025

2230

3300

570

763

639

907

700

1064

757

1216

805

1353

854

1508

897

1648

940

1853

989

2031

1032

2282

3400

583

818

651

965

711

1123

767

1284

815

1430

863

1587

907

1744

947

1946

991

2099

1038

2318

3500

596

867

663

1031

721

1190

777

1353

826

1517

871

1665

916

1831

956

2039

997

2195

1043

2380

3600

609

924

674

1097

732

1267

787

1430

836

1595

880

1753

926

1927

966

2134

1004

2291

1045

2478

3700

622

989

686

1165

744

1335

797

1508

847

1691

890

1849

934

2015

976

2238

1013

2397

1051

2569

3800

635

1047

698

1241

755

1413

808

1595

857

1779

901

1945

943

2160

985

2344

1023

2514

1059

2688

3900

649

1123

713

1318

767

1491

818

1683

867

1866

912

2050

952

2265

994

2451

1032

2633

1068

2819

4000

662

1190

722

1396

778

1578

829

1779

878

1962

922

2203

962

2371

1003

2560

1042

2763

1078

2952

4100

675

1267

734

1482

790

1674

839

1875

888

2058

933

2309

973

2496

1011

2679

1051

2895

1087

3097

4200

689

1353

746

1569

801

1761

851

1971

898

2212

943

2424

983

2624

1021

2810

1060

3029

1090

3276

Bhp

Brake Horsepower

Watts

Input Watts to Motor

Bhp =

Watts x Motor Efficiency

746

50TFF014 (10.2 TONS) — STANDARD MOTOR (BELT DRIVE)

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm Watts

Rpm Watts

Rpm Watts

Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts

3100

570

623

636

799

693

886

748

1044

800

1202

850

1281

901

1360

950

1474

989

1597

1000

1755

3200

584

676

649

842

705

948

759

1097

809

1281

858

1352

907

1457

960

1571

1001

1703

1006

1834

3300

598

728

662

904

717

1027

769

1158

819

1342

867

1483

914

1536

963

1668

1010

1799

1018

1940

3400

612

781

675

957

729

1115

780

1229

829

1414

876

1589

922

1606

968

1764

1018

1940

1022

2045

3500

626

873

688

1018

741

1202

792

1299

840

1483

886

1676

930

1773

975

1826

1021

2062

1039

2203

3600

640

913

702

1080

754

1290

803

1378

851

1553

896

1755

940

1913

983

1887

1026

2212

1051

2370

3700

654

1065

714

1218

767

1373

815

1514

861

1666

906

1862

950

2027

991

2202

1030

2361

1064

2512

3800

668

1129

727

1291

780

1456

827

1598

873

1751

916

1948

959

2123

1001

2299

1040

2476

1075

2638

3900

683

1194

741

1365

793

1540

839

1691

884

1836

927

2035

969

2228

1010

2405

1049

2593

1085

2773

4000

697

1267

754

1448

806

1624

851

1785

895

1931

938

2123

979

2334

1020

2521

1059

2710

1095

2901

4100

711

1340

767

1531

819

1708

864

1879

907

2035

949

2219

989

2441

1029

2638

1068

2837

1105

3028

4200

726

1423

780

1624

832

1802

877

1983

919

2149

960

2316

1000

2548

1039

2764

1077

2955

1114

3166

4300

741

1506

794

1717

845

1897

889

2096

931

2263

971

2423

1011

2647

1049

2882

1087

3092

1124

3304

4400

755

1598

808

1819

858

2000

902

2210

943

2387

983

2548

1022

2764

1059

3010

1097

3230

1133

3442

4500

770

1700

821

1923

871

2114

915

2325

955

2512

995

2683

1033

2882

1070

3138

1107

3368

1143

3590

4600

784

1794

835

2027

884

2219

928

2450

968

2638

1006

2828

1044

3010

1081

3258

1117

3516

1152

3748

4700

799

1905

849

2140

897

2343

941

2566

981

2773

1018

2964

1056

3147

1092

3387

1127

3655

1162

3897

4800

814

2009

863

2254

910

2468

954

2692

993

2919

1030

3111

1067

3304

1103

3525

1138

3804

1172

4055

4900

829

2131

877

2378

923

2602

967

2828

1006

3065

1043

3267

1079

3470

1114

3674

1149

3934

1182

4223

5000

843

2246

892

2503

937

2746

980

2964

1019

3221

1055

3424

1091

3637

1126

3822

1160

4083

1193

4382

5100

858

2378

906

2629

950

2891

993

3111

1032

3388

1068

3590

1103

3804

1137

4009

1171

4242

1204

4531

Bhp

Brake Horsepower

Watts

Input Watts to Motor

Bhp =

Watts x Motor Efficiency

746

Summary of Contents for 50TFF007-014

Page 1: ...sy maintenance Easy installation and conversion All units are shipped in the vertical dis charge configuration for fit up to standard roof curbs Two different curb sizes fit unit sizes 007 and 008 014 The contractor can order and install the roof curb early in the construction stage before decisions on size require ments are made All units feature roll formed baserail design with forklift slots on...

Page 2: ...mperature is below the control set point the supply air sensor modulates the economizer out door air damper open to achieve the set point When second stage cooling is called for the compressor is energized in addition to the economizer If the outdoor air temperature is above the set point the first stage of compression is activated and the economizer stays at minimum vent position Economizer opera...

Page 3: ...h almost any thermostat or building control system Indoor air quality begins with Carrier rooftops Sloped condensate pans minimize bio logical growth in rooftop units in accor dance with ASHRAE Standard 62 Standard 51 mm 2 in filters with optional dirty filter indicator switch pro vide for greater particle reduction in the return air The face split evaporator coils improve the dehumidification ca ...

Page 4: ... Nominal L s 1130 1230 1420 1700 1980 Motor kW 1 12 1 12 1 12 1 50 2 24 Maximum Continuous BkW 1 79 1 79 1 79 1 79 2 76 Motor Frame Size 56 56 56 56 56 Nominal r s High Low Fan r s Range 15 50 20 08 10 33 14 67 10 33 14 67 11 50 15 00 11 83 14 83 Motor Bearing Type Ball Ball Ball Ball Ball Maximum Allowable r s 35 0 26 7 26 7 26 7 26 7 Motor Pulley Pitch Diameter Min Max mm 71 97 61 86 71 97 71 97...

Page 5: ...e Belt Belt Belt Belt Belt Nominal Cfm 2000 2600 2600 3500 4200 Motor Hp 11 2 11 2 11 2 2 3 Maximum Continuous Bhp 2 40 2 40 2 40 2 40 3 70 Motor Frame Size 56 56 56 56 56 Fan Rpm Range 930 1205 620 880 620 880 690 900 710 890 Motor Bearing Type Ball Ball Ball Ball Ball Maximum Allowable Rpm 2100 1600 1600 1600 1600 Motor Pulley Pitch Diameter Min Max in 2 8 3 8 2 4 3 4 2 8 3 8 2 8 3 8 4 0 5 0 Nom...

Page 6: ...er Coil Hail Guard Assembly X Fan Filter Status X Salt Spray Protection Grille 008 014 X Logo Kit X Outdoor Air Enthalpy Sensor EconoMi er X Return Air Enthalpy Sensor EconoMi er X Return Air Temperature Sensor EconoMi er X Indoor Aair Quality CO2 Sensor EconoMi er X Options and accessories HEAD PRESSURE CONTROL The 50TFF007 014 standard units are designed to operate in cooling at outdoor temperat...

Page 7: ...ing plate on the face of the economizer controls the amount of outdoor air entering the system Closed it pro vides a leakproof seal which prevents ambient air from seep ing in or conditioned air from seeping out It can be adjusted easily for 100 outdoor air or any proportions of mixed air Like the base unit the economizer is converted easily for hor izontal discharge applications THERMOSTAT Zone t...

Page 8: ...d Accusensor III sensor compares outdoor temperature and humidity to return air temperature and humidity and determines the most economical mixture of air purchased in addition to first solid state enthalpy sensor for differential enthalpy sensing ECONOMI ER Electric heaters are available in a wide range of capacities for factory or field installation FACTORY INSTALLED APOLLO COMMUNICATING CONTROL...

Page 9: ...inches b Bottom of unit to combustible surfaces when not using curb 1 inch Bottom of base rail to com bustible surfaces when not using curb 0 inches c Condenser coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optional d Overhead 60 in to assure proper condenser fan operation e Between units control box side 42 in per NEC f Between unit and ungrounde...

Page 10: ...ter clearance is optional c Overhead 60 in to assure proper condenser fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box side 36 in per NEC f Between unit and block or concrete walls and other grounded surfaces control box side 42 in per NEC g Horizontal supply and return end 0 inches 6 With the exception of the ...

Page 11: ...uct rest on curb B C D ALT DRAIN HOLE E GAS F POWER G CONTROL CONNECTOR PKG ACCY 1 911 16 551 1 4 406 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 CRBTMPWR001A00 11 4 31 7 NPT CRBTMPWR002A00 1 2 12 7 NPT 3 4 19 NPT 1 2 12 7 CRBTMPWR003A00 3 4 19 NPT 11 4 31 7 NPT CRBTMPWR004A00 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A00 and 002A00 are for thru the ...

Page 12: ... connections B C D ALT DRAIN HOLE E GAS F POWER G CONTROL CONNECTOR PACKAGE ACCESSORY 2 87 16 827 1 1015 16 583 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 NPT CRBTMPWR001A00 11 4 31 7 NPT CRBTMPWR002A00 1 2 12 7 NPT 3 4 19 NPT 1 2 12 7 NPT CRBTMPWR003A00 3 4 19 NPT 11 4 31 7 NPT CRBTMPWR004A00 NOTES 1 Roof curb accessory is shipped disassembled 2 Insulated panels 1 thick polyurethane foam 13 4 lb de...

Page 13: ... III Select electric heat Heating load required is 18 kW Enter the Electric Heating Capacities table page 33 for the 50TFF012 at 400 3 50 The 19 3 kW heater at 400 v most closely satisfies the heating required IV Determine fan speed and power require ments at design conditions Before entering the Fan Performance tables calcu late the total static pressure required based on unit components From the...

Page 14: ... Electric Heating Capacities table page 33 for the 50TFF012 at 400 3 50 The 19 3 kW heater at 400 v most closely satisfies the heating required 19 3 x 3413 65 871 Btuh gross capacity IV Determine fan speed and power require ments at design conditions Before entering the Fan Performance tables calcu late the total static pressure required based on unit components From the given and the Pressure Dro...

Page 15: ...6 17 5 19 4 21 3 16 6 18 2 20 0 21 9 SHC 14 7 15 0 12 6 10 0 15 6 17 5 14 5 11 2 16 6 18 2 16 1 12 2 kW 4 54 4 70 4 87 5 04 4 66 4 82 4 98 5 15 4 74 4 89 5 05 5 21 32 TC 14 1 15 9 17 8 19 7 15 0 16 9 18 8 20 7 16 2 17 7 19 4 21 2 SHC 14 1 14 7 12 3 9 8 15 0 16 9 14 3 11 0 16 2 17 7 15 8 12 0 kW 4 81 4 99 5 17 5 36 4 92 5 10 5 29 5 48 5 05 5 20 5 37 5 55 35 TC 13 7 15 5 17 3 19 3 14 5 16 4 18 2 20 ...

Page 16: ...14 4 14 3 13 3 11 7 9 9 16 1 16 1 15 2 13 5 11 2 kW 7 33 7 33 7 47 7 67 7 91 7 56 7 57 7 67 7 85 8 08 50TFF008 21 5 kW cont Temp C Air Entering Condenser Edb Air Entering Evaporator L s BF 1180 0 075 1400 0 095 Air Entering Evaporator Ewb C 14 16 18 20 22 14 16 18 20 22 20 TC 21 8 22 5 23 9 25 5 27 1 22 9 23 1 24 3 26 1 27 7 SHC 21 8 20 9 18 9 16 4 13 6 22 8 22 4 20 5 17 7 14 5 kW 5 33 5 41 5 55 5...

Page 17: ... 22 0 16 0 kW 6 61 6 69 6 96 7 09 6 97 7 02 7 35 7 46 7 61 7 60 8 04 8 14 28 TC 23 0 23 2 26 5 29 6 24 7 24 7 27 5 30 3 26 4 26 4 28 4 31 0 SHC 22 5 22 0 18 7 14 6 23 9 23 9 20 1 15 2 25 0 25 0 21 8 15 9 kW 7 00 7 06 7 33 7 48 7 34 7 34 7 71 7 86 7 98 7 97 8 42 8 55 32 TC 22 3 22 4 25 5 28 7 23 7 23 7 26 3 29 4 25 6 25 6 27 3 30 2 SHC 21 7 21 4 18 4 14 3 22 8 22 8 19 7 15 0 24 2 24 2 21 5 15 7 kW ...

Page 18: ... 2 15 5 13 5 20 0 20 0 18 4 18 1 15 5 kW 10 37 10 37 10 52 10 77 11 07 10 74 10 74 10 81 10 98 11 28 50TFF012 29 2 kW cont Temp C Air Entering Condenser Edb Air Entering Evaporator L s BF 1800 0 125 1880 0 13 Air Entering Evaporator Ewb C 14 16 18 20 22 14 16 18 20 22 20 TC 31 5 31 9 33 3 35 3 37 2 31 7 23 1 33 5 35 3 37 3 SHC 31 4 30 6 27 8 24 0 19 9 31 7 31 1 28 3 24 4 20 2 kW 7 12 7 16 7 30 7 5...

Page 19: ...44 0 SHC 29 4 31 9 26 7 21 1 32 9 36 3 30 5 23 3 34 4 37 4 32 5 24 6 kW 9 78 9 94 10 12 10 27 9 95 10 08 10 22 10 39 10 15 10 10 10 25 10 42 32 TC 26 7 31 5 36 2 40 2 30 8 34 5 38 3 42 0 33 0 36 0 39 1 42 7 SHC 26 7 30 9 26 0 20 7 30 8 34 5 29 9 22 9 33 0 36 0 31 9 24 3 kW 10 20 10 42 10 64 10 85 10 40 10 59 10 76 10 96 10 49 10 65 10 82 11 01 35 TC 24 7 29 9 34 9 39 1 29 2 33 1 37 0 40 9 31 4 35 ...

Page 20: ...54 6 45 6 75 6 60 6 48 6 76 6 69 6 60 6 86 3 46 105 TC 60 4 68 1 76 2 63 0 70 4 78 6 63 5 70 8 78 8 66 7 72 0 80 1 SHC 55 7 47 2 37 5 62 2 52 4 40 8 63 2 53 4 41 3 66 7 58 6 44 1 kW 6 59 6 86 7 19 6 71 7 00 7 32 6 74 7 02 7 34 6 90 7 11 7 40 115 TC 55 9 63 4 71 1 59 0 65 4 73 2 59 7 65 6 73 5 62 5 66 8 75 0 SHC 53 2 45 4 35 9 59 0 50 6 39 0 59 7 51 6 39 6 62 7 56 8 43 0 kW 6 99 7 26 7 58 7 13 7 39...

Page 21: ... 82 6 61 7 kW 9 06 9 42 9 74 9 26 9 56 9 88 9 4 9 65 9 96 9 48 9 66 9 98 115 TC 67 4 77 2 94 2 75 6 83 8 99 0 81 3 87 4 100 6 82 8 88 4 101 0 SHC 67 3 59 1 49 5 75 6 68 9 55 1 81 2 76 3 59 0 82 7 78 7 60 1 kW 9 71 10 04 10 42 9 97 10 19 10 59 10 1 10 28 10 66 10 19 10 31 10 68 125 TC 63 2 69 2 84 4 68 5 71 8 88 8 73 1 75 0 92 3 74 2 76 0 93 0 SHC 63 2 56 0 46 0 68 5 64 3 51 9 73 0 70 9 56 9 74 2 7...

Page 22: ...STANDARD MOTOR BELT DRIVE Airflow L s External Static Pressure Pa 25 50 100 150 200 250 300 350 400 R s kW R s kW R s kW R s kW R s kW R s kW R s kW R s kW R s kW 700 12 1 0 30 13 1 0 36 14 8 0 48 16 4 0 61 17 8 0 75 18 7 0 85 18 7 0 83 17 8 0 67 16 0 0 44 750 12 8 0 36 13 7 0 42 15 5 0 56 17 0 0 68 18 4 0 84 19 5 0 98 20 1 1 05 20 0 1 23 19 1 0 85 800 13 5 0 42 14 4 0 49 16 1 0 63 17 5 0 77 18 9 ...

Page 23: ... 14 3 1 34 15 1 1 58 15 9 1 81 16 7 2 03 1400 8 8 0 66 10 0 0 86 11 1 0 98 12 0 1 10 12 9 1 22 13 7 1 33 14 5 1 47 15 4 1 67 16 2 1 90 16 8 2 12 1500 9 2 0 74 10 4 0 95 11 5 1 09 12 4 1 23 13 2 1 35 14 0 1 49 14 8 1 57 15 6 1 77 16 4 1 97 17 1 2 21 1600 9 7 0 85 10 8 1 07 11 8 1 22 12 8 1 37 13 6 1 49 14 4 1 65 15 1 1 79 15 8 1 94 16 5 2 09 17 3 2 31 1700 10 2 0 96 11 2 1 19 12 2 1 35 13 1 1 51 13...

Page 24: ...OR BELT DRIVE Airflow L s External Static Pressure Pa 25 50 100 150 200 250 300 350 400 R s kW R s kW R s kW R s kW R s kW R s kW R s kW R s kW R s kW 700 10 8 0 25 12 0 0 30 13 9 0 41 15 6 0 53 17 0 0 67 18 4 0 83 19 8 1 04 21 2 1 27 21 9 1 38 750 11 5 0 30 12 5 0 35 14 4 0 47 16 1 0 60 17 5 0 74 18 8 0 88 20 1 1 09 21 5 1 31 22 3 1 42 800 12 1 0 35 13 1 0 41 14 9 0 53 16 5 0 67 17 9 0 81 19 2 0 ...

Page 25: ...1 21 13 9 1 22 14 0 0 79 15 0 1 43 15 6 1 64 1400 8 0 0 66 9 3 0 78 10 5 0 91 11 4 1 03 12 4 1 16 13 3 1 30 14 1 1 41 14 6 1 25 15 4 1 64 16 0 1 75 1500 8 4 0 74 9 6 0 87 10 7 0 99 11 8 1 14 12 7 1 28 13 5 1 42 14 3 1 57 15 1 1 67 15 7 1 83 16 4 1 88 1600 8 8 0 85 10 0 0 96 11 1 1 10 12 1 1 25 12 9 1 40 13 8 1 55 14 5 1 70 15 3 1 88 16 0 2 00 16 7 2 09 1700 9 1 0 96 10 3 1 06 11 3 1 22 12 3 1 37 1...

Page 26: ...4 859 1163 998 1235 1156 1303 1318 1371 1499 1433 1638 1900 894 630 945 692 1037 818 1119 948 1194 1089 1266 1250 1330 1413 1396 1604 1460 1796 2000 936 708 984 771 1072 899 1154 1047 1226 1190 1297 1361 1362 1534 1422 1718 1485 1910 2100 978 795 1024 859 1108 998 1190 1156 1259 1310 1327 1473 1393 1656 1452 1840 1510 2041 2200 1021 891 1064 956 1145 1097 1225 1275 1294 1439 1359 1604 1423 1779 14...

Page 27: ...2282 3400 583 818 651 965 711 1123 767 1284 815 1430 863 1587 907 1744 947 1946 991 2099 1038 2318 3500 596 867 663 1031 721 1190 777 1353 826 1517 871 1665 916 1831 956 2039 997 2195 1043 2380 3600 609 924 674 1097 732 1267 787 1430 836 1595 880 1753 926 1927 966 2134 1004 2291 1045 2478 3700 622 989 686 1165 744 1335 797 1508 847 1691 890 1849 934 2015 976 2238 1013 2397 1051 2569 3800 635 1047 ...

Page 28: ...1019 843 1099 883 1178 1031 1249 1182 1316 1353 1382 1526 1900 802 539 854 585 953 700 1046 835 1126 965 1201 1106 1274 1275 1338 1439 1402 1621 2000 840 600 888 646 984 771 1073 907 1154 1047 1226 1190 1297 1361 1363 1534 1424 1718 2100 878 669 923 716 1015 843 1101 981 1182 1140 1252 1292 1320 1456 1388 1639 1448 1831 2200 916 739 958 795 1046 924 1129 1072 1209 1241 1280 1404 1345 1569 1410 174...

Page 29: ...52 1920 993 2014 3400 527 739 599 859 664 1006 724 1165 775 1318 827 1482 873 1639 920 1831 963 2005 1001 2091 3500 537 795 609 907 672 1064 731 1216 784 1387 833 1552 880 1718 926 1901 970 2134 1007 2221 3600 548 851 619 956 680 1114 738 1275 794 1456 840 1621 888 1805 931 1971 976 2230 1017 2362 3700 560 916 629 1014 688 1173 747 1344 802 1534 847 1700 895 1884 938 2108 981 2309 1024 2496 3800 5...

Page 30: ... 40 2 120 3 0 008 400 1 79 2 40 2 120 3 0 009 400 1 79 2 40 2 120 3 0 012 400 1 79 2 40 2 120 3 0 014 400 2 76 3 70 3 313 5 5 Bhp Brake Horsepower BkW kW x Motor Efficiency UNIT 50TFF MOTOR PULLEY TURNS OPEN 0 1 2 1 11 2 2 21 2 3 31 2 4 41 2 5 007 20 08 19 67 19 17 18 75 18 25 17 83 17 33 16 92 16 42 16 00 15 50 008 009 14 67 14 25 13 83 13 33 12 92 12 50 12 08 11 67 11 25 10 83 10 33 012 15 00 14...

Page 31: ...31 DURABLADE ECONOMIZER BAROMETRIC RELIEF DAMPER CHARACTERISTICS 50TFF007 DURABLADE ECONOMIZER BAROMETRIC RELIEF DAMPER CHARACTERISTICS 50TFF008 014 ...

Page 32: ... 4 0 5 STATIC PRESSURE in wg FLOW cfm 2 FANS OPERATING 1 FAN OPERATING ECONOMI ER OUTDOOR AIR LEAKAGE 50 40 30 20 10 0 0 0 25 0 5 0 75 1 FLOW CFM STATIC PRESSURE in wg SIZE 007 SIZES 008 014 0 25 0 20 0 15 0 10 0 05 0 00 0 500 1000 1500 2000 FLOW CFM STATIC PRESSURE in wg SIZE 007 SIZES 008 014 ECONOMI ER RETURN AIR PRESSURE DROP 0 25 0 20 0 15 0 10 0 05 0 00 1200 2000 2800 3600 4400 FLOW CFM STAT...

Page 33: ... 37 39 40 Durablade Economizer 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 EconoMi er 31 35 41 50 59 67 75 84 90 97 105 COMPONENT Cfm 1500 1600 1800 2000 2200 2400 2500 1 Heater Module 0 09 0 09 0 10 0 11 0 11 0 12 0 13 2 Heater Modules 0 16 0 16 0 17 0 17 0 17 0 18 0 18 Durablade Economizer 0 05 0 05 0 05 0 05 0 05 0 05 0 05 EconoMi er 0 13 0 15 0 19 0 24 0 29 0 35 COMPONENT Cfm 1900 2200 2500 300...

Page 34: ...A FLA FLA Nominal kW FLA MCA MOCP FLA LRA 007 400 3 phase 360 440 9 9 72 0 0 6 2 6 18 4 25 18 109 4 2 7 2 18 4 25 18 8 0 13 8 18 4 25 18 9 7 16 8 20 8 25 19 16 0 27 8 32 1 35 30 17 7 30 7 34 6 35 32 008 400 3 phase 360 440 8 9 42 0 0 6 2 6 23 8 30 25 103 9 7 13 9 23 8 30 25 11 5 16 5 23 9 25 25 19 3 27 8 38 1 40 35 22 9 33 1 44 6 45 41 29 0 41 8 55 5 60 51 009 400 3 phase 360 440 8 3 69 0 0 6 2 6 ...

Page 35: ...iping and wiring 50TFF007 014 sizes 008 014 shown CONDENSER FAN DISCHARGE AIR TOOL LESS FILTER ACCESS DOOR VERTICAL DISCHARGE DUCTING HORIZONTAL DISCHARGE DUCTING LEGEND NEC National Electrical Code U S A Standard ...

Page 36: ...36 Typical wiring schematic 50TFF008 014 shown ...

Page 37: ...al R Relay SAT Supply Air Thermostat SEN Sensor SW1 Switch Fully Open SW2 Switch Fully Closed SW3 Switch Min Vent Position SW4 Switch Max Vent Position TB Terminal Block TC Thermostat Cooling TH Thermostat Heating TRAN Transformer Field Splice Marked Wire Terminal Marked Terminal Unmarked Terminal Block Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Option...

Page 38: ... er damper modulates to minimum position The compressor contac tor is energized to start the compressor and outdoor con denser fan motor OFM After the thermostat is satisfied the damper modulates to the fully closed position when the IFM is deenergized When the OAT is below the ECON SP setting and the room thermostat calls for Stage 1 cooling R to G Y1 the EconoMi er modulates to the minimum posit...

Page 39: ... 2 5 If compressor no 1 is energized and the thermostat is satisfied compressor no 1 the OFM and IFM are deenergized and the EconoMi er modulates closed When the OAT is below the MECH CLG LOCKOUT set point the compressors remain off Heating units with economizer If Accessory Heater is Installed When the room thermostat calls for heat through terminal W1 the evaporator fan contac tor and heater con...

Page 40: ...s continually monitor and adjust their operation to ensure uninterrupted and personalized comfort for all occupants Through the use of communicating electronic controls VVT Systems are able to provide the comfort of a multiple zone system while using the installation operating and maintenance economics of single zone equipment virtu ally putting an end to the cost vs comfort compromise Controls co...

Page 41: ...eating to cooling changeover All units are auto matic changeover from heating to cooling when automatic changeover thermostat and subbase are used Airflow Units are draw thru on cooling and blow thru on heating Maximum airflow To minimize the possibility of con densate blow off from evaporator airflow through units should not exceed 67 L s per kW 500 cfm ton Minimum airflow For cooling minimum air...

Page 42: ...ging and forklift slots shall be provided to facilitate maneuvering 5 Unit shall have a factory installed sloped con densate drain pan made of a non corrosive material providing a minimum 19 mm 3 4 in connection with both vertical and horizontal drains and shall comply with ASHRAE 62 6 Unit shall have factory installed filter access panel to provide filter access with tool less removal 7 Unit shal...

Page 43: ...er strip and capable of supporting entire unit weight b Allows for installing and securing ductwork to curb prior to mounting unit on the curb 3 Integrated Economizer a Integrated integral modulating type capable of simultaneous economizer and compressor operation b Includes all hardware and controls to provide cooling with outdoor air c Equipped with low leakage dampers not to exceed 3 leakage at...

Page 44: ... after shutdown 17 Salt Spray Protection Package 008 014 Coil guard protects coil from corrosion in coastal areas and in areas with high sulfur emissions 18 Fan Filter Status Switch Provides status of indoor fan ON OFF or filter CLEAN DIRTY Status shall be dis played over communication bus when used with direct digital controls or with an indica tor light at the thermostat 19 Unit Mounted Disconne...

Reviews: