APPLICATION DATA
Condensate trap
⎯
A 2--in. condensate trap must be field supplied.
1” (25mm) MIN.
2” (50mm) MIN.
TRAP
OUTLET
C99013
Ductwork
⎯
Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge
⎯
Units are equipped
with factory--installed inserts in the downflow openings. Remove
the inserts similar to removing an electrical knockout.
Maximum cooling airflow
⎯
To minimize the possibility of con-
densate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm/ton.
Minimum cooling airflow
⎯
The minimum cooling airflow is 350
cfm/ton.
Minimum cooling ambient operating temperature
⎯
All stan-
dard units have a minimum ambient operating temperature of 40
_
F
(4.4
_
C). With accessory low ambient temperature kit, units can op-
erate at temperatures down to 0
_
F (--17.7
_
C).