![Carrier 50JC04-06 Service And Maintenance Instructions Download Page 5](http://html1.mh-extra.com/html/carrier/50jc04-06/50jc04-06_service-and-maintenance-instructions_2562344005.webp)
5
5. Using the UP and DOWN arrow keys highlight
SETTINGS and then press ENTER.
6. Use the DOWN arrow key highlight the UNIT CONFIG
-
URATIONS menu then press ENTER.
7. Highlight UNIT CONFIGURATIONS then press ENTER.
8. Highlight INDOOR FAN and then press ENTER.
9. Refer to the job specifications to set the following, deter
-
mining the values per the RPM Calculator label (see Fig. 7).
Use the UP and DOWN arrow keys and the BACK key to
set the values. Press ENTER after setting each value to
continue to the next selection.
• IDF VENT SPD
• IDF HEAT SPD
• IDF LOW COOL SPD
• IDF HIGH SPD
• IDF FREE COOL SPD
For further details see the following manual: 48/50JC 04-06 Ultra
High Efficiency Single Package Rooftop Units with SystemVu™
Controls Version X.X Controls, Start-up, Operation and Trouble
-
shooting Instructions.
NOTE: Values in the Field Accessories section are VDC adders.
Fig. 7 — Example of Fan Speed Set Up Labels for SystemVu™ Controls
Field Accessories:
2500
Economizer
ESP in. wg
RPM
Calculator
CFM
0.2
1301
1381
1463
1548
1633
1720
1808
1897
1987
1500
1625
1750
1875
2000
2125
2250
2375
66
80
107
0.4
1477
1544
1615
1688
1764
1842
1921
2003
2068
66
0.6
1639
1699
1763
1828
1897
1967
2040
2115
2191
0.8
1788
1843
1902
1962
2025
2090
2157
2227
2298
66
1.0
1925
1976
2031
2087
2146
2208
2271
2336
66
1.2
2054
2101
2152
2206
2262
2320
2380
66
1.4
2174
2220
2268
2318
2372
66
1.6
1.8
2.0
2289
2332
2378
66
66
80
80
80
80
80
80
80
107
107
107
107
107
107
107
1 Stage E Heat
2 Stage E Heat
UNIT MODEL
NUMBER