ECONOMIZER SYSTEMS
EconoMi$er2
The unit may be equipped with a factory-installed or accessory
(field-installed) EconoMi$er
®
2 system. See Fig. 54 for compo
-
nent locations.
Economizers use direct-drive damper actuators.
Fig. 54 —
EconoMi$er2 Component Locations
Fig. 55 —
EconoMi$er2 with 4 to 20 mA Control Wiring
IMPORTANT: Any economizer that meets the economizer
requirements as laid out in California’s Title 24 mandatory
section 120.2 (fault detection and diagnostics) and/or
prescriptive section 140.4 (life-cycle tests, damper leakage,
5 year warranty, sensor accuracy, etc), will have a label on
the economizer. Any economizer without this label does
not meet California’s Title 24. The five year limited parts
warranty referred to in section 140.4 only applies to factory
installed economizers. Please refer to your economizer on
your unit.
IMPORTANT: The optional EconoMi$er
®
2 does not
include a controller. The EconoMi$er2 is operated by a 4
to 20 mA signal from an existing field-supplied control
-
ler. See Fig. 55 for wiring information.
ECONOMI$ER2 PLUG
OUTSIDE AIR
TEMPERATURE SENSOR
4
3
5
2
8
6
7
1
10
11
9
12
PINK
VIOLET
BLACK
BLUE
YELLOW
RUN
RED
WHITE
ECONOMI$ER2 PLUG
DIRECT DRIVE
ACTUATOR
4-20mA
S
IGNAL
OAT
S
EN
S
OR
ACTUATOR
CONTROL
(4-20mA)
ACTUATOR
FEEDBACK
(2-10VDC)
TRAN
S
FORMER
GROUND
ORANGE
500 OHM
RE
S
I
S
TOR