Fig. 21 —
Cooling Charging Chart - 4 Ton
Fig. 22 —
Cooling Charging Chart - 4 Ton with Hot
Gas Reheat (Humidi-MiZer
®
System) Option
Fig. 23 —
Cooling Charging Chart - 5 Ton
Fig. 24 —
Cooling Charging Chart - 5 Ton with Hot
Gas Reheat (Humidi-MiZer System) Option
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
-6.6
4.5
15.6
26.7
37.8
48.9
60.0
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure, [psig/Kpa]
4 Ton JC
R410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Cooling test compressor
speed to 4500)
Remove Charge if Below the
Curve
48TC004276 REV -
Add Charge if Above the Curve
Outdoor Coil
Leav
ing
Temperature, [°C/°F]
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
-6.6
4.5
15.6
26.7
37.8
48.9
60.0
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure, [psig/Kpa]
4 Ton JC Humidimizer
R410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Humidimizer test
compressor speed to 4500)
Remove Charge if Below the
Curve
48TC004273 REV -
Add Charge if Above the Curve
Outdoor Coil
Leav
ing
Temperature, [°C/°F]
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
-6.6
4.5
15.6
26.7
37.8
48.9
60.0
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure, [psig/Kpa]
5 Ton JC
R410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Cooling test compressor
speed to 4100)
Remove Charge if Below the
Curve
48TC004275 REV -
Add Charge if Above the Curve
Outdoor Coil
Leav
ing
Temperature, [°C/°F]
1034
1379
1723
2068
2413
2758
3102
3447
3792
4136
-6.6
4.5
15.6
26.7
37.8
48.9
60.0
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
Compressor Discharge Pressure, [psig/Kpa]
5 Ton JC Humidimizer
R410A Refrigerant Charging Chart
(Unit must be put in Test Mode and set the Humidimizer test
compressor speed to 4100)
Remove Charge if Below the
Curve
48TC004272 REV -
Add Charge if Above the Curve
Outdoor Coil
Leav
ing
Temperature, [°C/°F]