Motorized 2--Position Damper Hood —
1. Assemble outdoor--air hood top and side plates as
shown in Fig. 13. Install seal strips on hood top and
sides. Put aside screen retainer and screws for later
assembly.
2. Fasten hood top and side plate assembly to unit with
screws provided.
3. Slide outdoor--air screen into screen track on hood
side plates. While holding screen in place, fasten
screen retainer to hood using screws provided.
4. Replace filter access panel. See Fig. 12.
Economizer Hood —
NOTE
: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be
used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.
1. The indoor coil access panel will be used as the top of
the hood. Remove the screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 14.
2. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 15.
3. Remove the shipping tape holding the economizer ba-
rometric relief damper in place.
4. Insert the hood divider between the hood sides. See
Fig. 15 and 16. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
5. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom
filter rack (hood divider). Push the filter into position
past the open filter clips. Close the filter clips to lock
the filter into place. See Fig. 16.
6. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 14.
7. Replace the filter access panel.
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
CAULK
HERE
TOP
SIDE
PANEL
C06025
Fig. 14 -- Indoor Coil Access Panel Relocation
B
TOP
PANEL
INDOOR COIL
ACCESS PANEL
19 1/16”
SCREW
HOOD DIVIDER
LEFT
HOOD
SIDE
33 3/8”
(848mm)
(483mm)
C06026
Fig. 15 -- Economizer Hood Construction
DIVIDER
BAROMETRIC
RELIEF
CLEANABLE
ALUMINUM
FILTER
FILTER
HOOD
FILTER
CLIP
OUTSIDE
AIR
C06027
Fig. 16 -- Economizer Filter Installation
50H
T