50HJ004---007

50HE003---006

Single---Package Rooftop Electric Cooling

Units with Optional Electric Heat

Installation Instructions

TABLE OF CONTENTS

Page

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 1--Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . .

ROOF CURB

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SLAB MOUNT

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ALTERNATE UNIT SUPPORT

2

. . . . . . . . . . . . . . . . .

Step 2--Field Fabricate Ductwork

2

. . . . . . . . . . . . . . . . . . .

Step 3--Install External Trap for Condensate Drain

2

. . . . . . .

Step 4--Rig and Place Unit

4

. . . . . . . . . . . . . . . . . . . . . . . . .

POSITIONING

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Step 5 — Make Electrical Connections

8

. . . . . . . . . . . . . . . .

FIELD POWER SUPPLY

8

. . . . . . . . . . . . . . . . . . . . . .

FIELD CONTROL WIRING

8

. . . . . . . . . . . . . . . . . . . .

HEAT ANTICIPATOR SETTINGS

8

. . . . . . . . . . . . . . .

Step 6 — Adjust Factory-Installed Options

29

. . . . . . . . . . .

COBRA

ENERGY RECOVERY UNITS

29

. . . . . . .

HUMIDI-MIZER

ADAPTIVE

DEHUMIDIFICATION SYSTEM

29

. . . . . . . . . . . . . .

DISCONNECT SWITCH

29

. . . . . . . . . . . . . . . . . . . . .

MANUAL OUTDOOR-AIR DAMPER

29

. . . . . . . . . .

CONVENIENCE OUTLET

29

. . . . . . . . . . . . . . . . . . .

NOVAR CONTROLS

29

. . . . . . . . . . . . . . . . . . . . . . . .

PREMIERLINK

CONTROL

31

. . . . . . . . . . . . . . . . .

OPTIONAL ECONOMI$ER IV AND

ECONOMI$ER2

34

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

ECONOMI$ER IV STANDARD SENSORS

35

. . . . . .

ECONOMI$ER IV CONTROL MODES

36

. . . . . . . . .

Step 7 — Adjust Evaporator-Fan Speed

41

. . . . . . . . . . . . . .

PRE--START--UP

58

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP

58

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SERVICE

62

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

67

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP CHECKLIST

72

. . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.

Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of

cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working

on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety

precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use

quenching cloth for unbrazing operations. Have fire extinguishers

available for all brazing operations.
Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the furnace and in

instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard
which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to

highlight suggestions which

will

result in enhanced installation,

reliability,or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause personal

injury or death.
Before performing service or maintenance operations

on unit, turn off main power switch to unit and install

lockout tag. Ensure electrical service to rooftop unit

agrees with voltage and amperage listed on the unit

rating plate.

!

WARNING

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert

to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in

basepan of unit with insulation-side down. Seals around

openings must be tight. (See Fig. 1.)

Summary of Contents for 50HE003

Page 1: ...ng on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and...

Page 2: ...discharge units Do not connect ductwork to unit For horizontal applications field supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to t...

Page 3: ...e 7 Direction of airflow 8 Connector packages CRBTMPWR001A01 and 002A01 are for thru the curb type gas Packages CRBTMPWR003A01 and 004A01 are for thru the bottom type gas connections CONNECTOR PKG ACC...

Page 4: ...that the following clearances are maintained 1 4 in clearance between the roof curb and the base rail inside the front and rear 0 0 in clearance between the roof curb and the base rail inside on the...

Page 5: ...Humidi MiZer system C06111 Fig 6 Rigging Details UNIT 50HE OPERATING WEIGHT DIMENSIONS A B C lb kg in mm in mm in mm 003 435 197 73 69 1872 35 50 902 33 31 847 004 445 202 73 69 1872 35 50 902 33 31...

Page 6: ...6 C06156 Fig 8 50HJ004 007 Base Unit Dimensions 50HE HJ...

Page 7: ...7 C06157 Fig 9 50HE003 006 Base Unit Dimensions 50HE HJ...

Page 8: ...icable Carrier warranty NOTE If accessory thru the bottom connections and roof curb are used refer to the Thru the Bottom Accessory Installation Instructions for information on wiring the unit Field C...

Page 9: ...rame Size Std 48 48 56 56 Hi Static 56 56 56 56 Fan Rpm Range Std 680 1044 770 1185 1035 1460 1035 1460 1120 1585 Hi Static 1075 1455 1075 1455 1300 1685 1300 1685 Motor Bearing Type Ball Ball Ball Ba...

Page 10: ...5 Fan Rpm Range Std 400 1000 680 1044 770 1185 1035 1460 Hi Static 1075 1455 1075 1455 1300 1685 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 1620 2100 2100 2100 Motor Pulley Pitch Diameter...

Page 11: ...ock 208 230 1 60 575 3 60 SIZES 006 AND 007 208 230 3 60 SIZES 004 AND 005 208 230 3 60 460 3 60 SIZES 006 AND 007 575 3 60 SIZES 004 AND 005 460 3 60 SIZES 004 AND 005 C06158 Fig 12 Power Wiring Conn...

Page 12: ...NO 187 254 1 10 3 77 0 1 0 7 4 9 NONE 18 5 18 5 25 25 18 18 90 90 001A00 3 3 4 0 9 2 10 6 18 5 19 4 25 25 18 18 90 90 002A00 4 9 5 8 13 6 15 6 23 1 25 7 25 30 21 24 90 90 003B00 6 5 8 0 18 1 20 9 28 8...

Page 13: ...0 0 007A00 8 1 10 6 16 5 20 0 15 0 60 0 008A00 10 6 13 8 20 5 25 0 19 0 60 0 009A00 12 9 16 8 24 3 25 0 22 0 60 0 YES 414 508 1 5 1 39 0 1 0 4 2 6 NONE 12 1 15 0 12 0 62 0 006A00 5 5 7 2 15 6 20 0 14...

Page 14: ...115 004 004 16 19 3 43 8 50 5 65 8 74 3 70 80 62 69 115 115 HS NO 187 254 1 14 1 95 0 1 1 5 5 8 NONE 24 9 24 9 30 30 25 25 140 140 002A00 4 9 5 8 13 6 15 6 24 9 26 8 30 30 25 25 140 140 003B00 6 5 8 0...

Page 15: ...68 004B00 7 9 9 6 21 9 25 3 34 6 38 8 35 40 32 36 168 168 005A00 12 0 14 7 33 4 38 5 48 9 55 4 50 60 45 51 168 168 004 004 15 8 19 3 43 8 50 5 62 0 70 4 70 80 57 65 168 168 004 005 19 9 24 3 55 2 63 8...

Page 16: ...38 8 40 0 36 0 102 0 008 009 23 4 30 1 41 8 45 38 102 YES 414 508 1 8 4 70 0 1 0 8 3 4 NONE 17 4 20 0 17 0 104 0 006A00 5 5 7 2 17 4 20 0 17 0 104 0 008A00 10 6 13 8 24 9 25 0 22 0 104 0 009A00 12 9...

Page 17: ...2 10 6 18 5 19 4 25 25 18 18 90 90 002 4 9 5 8 13 6 15 6 23 1 25 7 25 30 21 24 90 90 003 6 5 8 0 18 1 20 9 28 8 32 3 30 35 26 30 90 90 004 7 9 9 6 21 9 25 3 33 5 37 7 35 40 31 35 90 90 002 002 9 8 14...

Page 18: ...20 13 48 007 8 1 10 6 18 7 20 17 48 008 10 6 13 8 22 7 25 21 48 009 12 9 16 8 26 5 30 24 48 HS NO 414 508 1 5 1 39 1 0 4 2 6 9 4 20 9 60 006 5 5 7 2 12 3 20 11 60 007 8 1 10 6 16 5 20 15 60 008 10 6 1...

Page 19: ...1 111 005 12 14 7 33 4 38 5 52 8 59 2 60 60 50 55 111 111 004 004 16 19 3 43 8 50 5 65 8 74 3 70 80 62 69 111 111 HS NO 187 254 1 13 5 93 1 0 7 5 8 23 4 23 4 30 30 23 23 136 136 002 4 9 5 8 13 6 15 6...

Page 20: ...04 005 19 9 24 3 55 2 63 8 81 3 91 9 90 100 76 86 173 173 HS NO 187 254 1 17 3 123 1 1 5 7 5 30 6 30 6 35 35 30 30 187 187 002 4 9 5 8 13 6 15 6 30 6 30 6 35 35 30 30 187 187 004 7 9 9 6 21 9 25 3 36...

Page 21: ...8 78 4 89 1 80 90 72 82 219 219 YES 187 254 1 20 5 156 1 1 4 7 5 40 5 40 5 45 45 39 39 224 224 002 4 9 5 8 13 6 15 6 40 5 40 5 45 45 39 39 224 224 004 7 9 9 6 21 9 25 3 41 7 45 9 45 50 39 43 224 224 0...

Page 22: ...267 267 011 18 6 22 8 51 7 59 7 77 9 87 8 80 90 72 81 267 267 012 24 0 29 4 66 7 77 0 96 6 109 5 100 110 89 101 267 267 012 017 31 8 38 9 88 4 102 0 123 7 140 8 125 150 114 129 267 267 YES 187 254 2 1...

Page 23: ...0 32 7 44 4 45 41 91 YES 518 632 2 4 8 34 2 0 6 2 8 17 0 20 18 93 018 17 0 16 4 26 6 30 24 93 019 34 0 32 7 44 4 45 43 93 HS NO 518 632 2 4 8 34 2 0 6 3 3 15 3 20 16 101 018 17 0 16 4 24 6 25 23 101 0...

Page 24: ...6 301 301 011 18 6 22 8 51 7 59 7 77 9 87 8 80 90 72 81 301 301 012 24 0 29 4 66 7 77 0 96 6 109 5 100 110 89 101 301 301 012 017 31 8 38 9 88 4 102 0 123 7 140 8 125 150 114 129 301 301 YES 187 254 2...

Page 25: ...32 7 44 4 45 41 111 YES 518 632 2 6 4 44 2 0 6 2 8 20 6 25 21 113 018 17 0 16 4 26 6 30 24 113 019 34 0 32 7 44 4 45 43 113 HS NO 518 632 2 6 4 44 2 0 6 3 3 18 9 25 20 121 018 17 0 16 4 24 6 25 23 12...

Page 26: ...012 24 0 29 4 66 7 77 0 102 1 115 0 110 125 94 106 364 364 012 017 31 8 38 9 88 4 102 0 129 2 146 3 150 150 119 135 364 364 012 010 37 5 45 9 104 2 120 3 149 0 139 0 150 175 137 156 364 364 YES 187 2...

Page 27: ...018 17 0 16 4 27 2 30 25 135 019 34 0 32 7 45 0 50 43 135 018 019 51 0 49 1 55 8 60 62 135 HS NO 518 632 2 6 3 50 2 0 6 5 6 21 0 25 22 139 018 17 0 16 4 27 4 30 25 139 019 34 0 32 7 47 9 50 44 139 018...

Page 28: ...13 45 9 60 1 69 4 80 78 197 YES 414 508 2 9 70 2 0 7 7 4 31 8 35 33 199 016 12 8 16 7 33 5 40 33 199 013 15 2 19 8 36 8 40 34 199 015 30 3 39 7 61 6 70 57 199 014 016 38 3 50 2 74 6 80 69 199 015 013...

Page 29: ...tween the thermidistat and the Humidi Mizer circuit recommended relay HN612KK324 See Fig 17 The relay coil is connected between the DEHUM output and C common of the unit The relay controls the Humidi...

Page 30: ...V Unit Shown ROOF TOP UNIT R C Y1 Y2 G W1 W2 PINK PINK RED 24V FROM HUMIDI MIZER SYSTEM LLSV R1 TS TATWIRES LCT R C Y1 Y2 G W1 W2 DEHUM OC R1 HUMIDI MIZER SYSTEM PINK LTLO CB 3 2 AMPS LEGEND CB Circu...

Page 31: ...the supply air duct as required by local codes Drill or punch a 1 2 in hole in the flange or duct Use two field supplied self drilling screws to secure the sensor probe in a horizontal orientation NOT...

Page 32: ...upply Air Temperature sensor 33ZCSENSAT and Outdoor Air Temperature sensor CRTEMPSN001A00 Included with factory installed PremierLink control field supplied and field installed with field installed Pr...

Page 33: ...12 1 2 3 4 5 6 7 8 9 10 11 12 PNK PNK VIO VIO GRA ORN PNK PNK GRA GRA GRA SAT BRN ORN BLK RED Space Temp Set Point Adjustment Indoor Air Quality Sensor OAT PNK VIO YEL YEL BLU BLU Economi er2 4 20mA...

Page 34: ...in high outdoor air enthalpy state Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy 3 Remove sensor mounted on back of control and locate in outside air stream C0601...

Page 35: ...ef damper in place 6 Insert the hood divider between the hood sides See Fig 32 and 33 Secure hood divider with 2 screws on each hood side The hood divider is also used as the bottom filter rack for th...

Page 36: ...nstalled Differential Dry Bulb CRTEMPSN002A00 Single Enthalpy HH57AC078 Differential Enthalpy HH57AC078 and CRENTDIF004A00 CO2 for DCV Control using a Wall Mounted CO2 Sensor 33ZCSENCO2 CO2 for DCV Co...

Page 37: ...R ASSEMBLY RED WHITE ECONOMISER2 PLUG DIRECT DRIVE ACTUATOR 2 NOTES 1 Switch on actuator must be in run position for economizer to operate 2 PremierLink control requires that the standard 50HJ540569 o...

Page 38: ...ame mounting location See Fig 27 Mount the return air enthalpy sensor in the return air duct See Fig 42 Wiring is provided in the EconoMi er IV wiring harness See Fig 34 The outdoor enthalpy changeove...

Page 39: ...oss terminals TR and TR1 5 Carefully adjust the minimum position potentiometer until the measured supply air temperature matches the calculated value 6 Reconnect the mixed air sensor to terminals T an...

Page 40: ...In order to have the CO2 sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to...

Page 41: ...remove the humidity loads for most commercial applications If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level an energy recovery unit and or a dehumidificat...

Page 42: ...20 mA 0 1100 1100 50 5 Proportional 20 0 10V 4 20 mA 0 900 900 50 6 Exponential 15 0 10V 4 20 mA 0 1100 1100 50 7 Exponential 20 0 10V 4 20 mA 0 900 900 50 8 Health Safety Proportional 0 10V 4 20 mA 0...

Page 43: ...75 0 004 Single 1 20 1000 208 230 4 9 Three 1 20 1000 208 230 4 9 460 2 2 575 2 2 005 Single 1 20 1000 208 230 4 9 Three 1 20 1000 208 230 4 9 460 2 2 575 2 2 006 Single 1 30 1650 208 230 9 2 Three 2...

Page 44: ...rmula bhp watts input x motor efficiency 746 GENERAL FAN PERFORMANCE NOTES 1 Values include losses for filters unit casing and wet coils See Table 13 and 14 and Fig 46 for accessory FIOP static pressu...

Page 45: ...able 17 Fan Performance 50HJ004 50he004 Vertical Discharge Units High Static Motor Belt Drive AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts R...

Page 46: ...hp Watts 1200 666 0 25 252 778 0 36 361 873 0 48 476 956 0 60 594 1031 0 72 718 1300 701 0 30 300 809 0 42 418 902 0 54 540 983 0 67 665 1057 0 80 796 1400 737 0 36 355 842 0 48 481 932 0 61 610 1012...

Page 47: ...38 1 29 1148 1900 944 0 71 633 1037 0 87 774 1120 1 04 925 1197 1 22 1084 2000 983 0 81 723 1073 0 98 870 1154 1 16 1026 2100 1023 0 92 821 1110 1 10 975 1189 1 28 1137 2200 1063 1 05 929 1147 1 23 10...

Page 48: ...1 32 1174 1223 1 52 1346 1296 1 72 1526 1364 1 93 1712 1428 2 15 1905 2500 1185 1 48 1311 1262 1 68 1490 1333 1 89 1676 1399 2 10 1868 1462 2 33 2067 AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 1 2 1 4...

Page 49: ...90 1333 1 89 1676 1399 2 10 1868 1462 2 33 2067 AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1224 1 18 1045...

Page 50: ...1303 1265 1 70 1510 1339 1 93 1717 1406 2 17 1926 2600 1224 1 63 1448 1303 1 87 1663 1375 2 12 1878 1442 2 36 2095 2700 1264 1 81 1604 1342 2 06 1828 1412 2 31 2051 2800 1305 1 99 1772 1381 2 26 2003...

Page 51: ...g 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1304 1 51 1337 1365 1 69 1503 1422 1 88 1674 1477 2 08 1848 1528 2 28 2025 1900 1335 1 64 1454 1395 1 8...

Page 52: ...Fan Performance 50HJ004 50HE004 Horizontal Discharge Units High Static Motor Belt Drive AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp...

Page 53: ...atts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0 23 233 762 0 35 344 860 0 46 459 944 0 58 579 1020 0 71 705 1300 674 0 28 276 791 0 40 395 887 0 52 517 970 0 65 645 1045 0 78 777 1400 706 0 33 324 820 0 4...

Page 54: ...6 1201 1 23 1096 2000 892 0 67 599 986 0 82 729 1072 0 98 870 1151 1 15 1022 2100 927 0 77 680 1017 0 92 815 1101 1 08 960 1178 1 26 1116 2200 962 0 87 769 1050 1 02 909 1131 1 19 1059 2300 997 0 97 8...

Page 55: ...2 1 83 1625 2500 1069 1 22 1084 1149 1 39 1239 1223 1 58 1403 1293 1 77 1576 1360 1 98 1757 AIRFLOW CFM EXTERNAL STTIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm...

Page 56: ...e field supplied drive is required 2 Maximum continuous bhp is 2 90 3 See general fan performance notes LEGEND Bhp Brake Horsepower Watts Input Watts to Motor Motor drive range 1300 to 1685 rpm All ot...

Page 57: ...9 2900 1204 1 77 1572 1281 2 00 1779 1353 2 24 1989 1419 2 48 2202 1482 2 72 2419 3000 1240 1 94 1725 1315 2 18 1939 1385 2 43 2156 1451 2 68 2376 AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1...

Page 58: ...it Preparation Make sure that the unit has been installed in accordance with installation instructions and applicable codes Step 2 Return Air Filters Make sure the correct filters are installed in the...

Page 59: ...installed as the outdoor air damper opens and closes the power exhaust fans will be energized and deenergized If field installed accessory CO2 sensors are connected to the EconoMi er IV control a dema...

Page 60: ...75_F S OAT must be less than SPT S Enthalpy must be LOW may be jumpered if and enthalpy sensor is not available S Economizer position is NOT forced 68 69 70 71 72 73 74 75 SPACE TEMPERATURE TIME TEMPE...

Page 61: ...erates under the normal sequence of operation the compressors will cycle to maintain indoor conditions See Fig 51 The Humidi MiZer adaptive dehumidification system includes a factory installed Motorma...

Page 62: ...tion SERVICE ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death When sevicing unit shut off all electrical power to unit and install lockout tag WARNING Step 1...

Page 63: ...utdoor Air Inlet Screen Clean the screen with steam or hot water and a mild detergent Do not use disposable filters in place of screens Step 2 Lubrication Compressor The compressor is charged with the...

Page 64: ...are required when using the superheat charging method for evaluating the unit charge Do not use mercury or small dial type thermometers because they are not adequate for this type of measurement C061...

Page 65: ...ine solenoid valve MUST be energized to use the charging charts and the outdoor motor speed controller jumpered to run the fan at full speed The charts reference a liquid pressure psig and temperature...

Page 66: ...s 50HE 2 TON CHARGING CHART 65 0 70 0 75 0 80 0 85 0 90 0 95 0 100 0 105 0 42 52 62 72 Suction Line Temp deg F Suction Line Pressure psig 448 0 498 0 548 0 598 0 648 0 698 0 5 5 10 5 15 5 20 5 25 5 Su...

Page 67: ...P1 4 Disconnect wires at T and T1 Place 5 6 kilo ohm resistor across T and T1 5 Jumper TR to 1 6 Jumper TR to N 7 If connected remove sensor from terminals SO and Connect 1 2 kilo ohm 4074EJM checkou...

Page 68: ...he Enthalpy potentiometer to A The Free Cool LED turns on The actuator should drive to between 20 and 80 open 3 Remove the 5 6 kilo ohm resistor and jumper T to T1 The actuator should drive fully open...

Page 69: ...ce Restriction in refrigerant system Locate restriction and remove Compressor Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermos...

Page 70: ...id coil defective replace 2 Solenoid valve stuck closed replace Low refrigerant charge or frosted evaporator coil 1 Check charge amount Charge per Fig 59 62 2 Evaporator coil frosted check and replace...

Page 71: ...71 C06053 Fig 70 EconoMi er IV Functional View 50HE HJ...

Page 72: ...EDGES j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS III START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3 TEMPERATURES OU...

Reviews: