3 to 25 Ton Modulating ERV
The modulating ERV is an intelligent ERV with variable speed
fan motors. The ERV can provide a variety of volumes of out-
side air and offset it with different exhaust speeds. CO
2
sensors
can also be tied into it for demand controlled ventilation
(DCV) operation. The modulating ERV will operate based on
occupancy and the rooftop’s operating mode, the following
sections explain operation in detail. Refer to Fig. 15 for the
overview flow diagram of a modulating ERV operation.
Fig. 15 — Modulating ERV Control and Operation Flow Chart
YES
NO
YES
NO
YES
NO
Notes:
* Min CFM represents the minimum outside air CFM requirement based on CO
2
values and setpoints.
** Occupied also means being in the unoccupied period but configured to run.
NO
YES
Is there
frost on the
wheel?
YES
NO
Is unit
occupied**
and IDF on?
NO
YES
ERV Mode = OFF
Wheel = off
ERV 2POS Damper = Closed
OA CFM = 0
Ex CFM = 0
ERV Mode = Test
User sets ERV to desired values for
testing purposes
OAU OA Fan Speed Test→OA.OF
OAU PE Fan Speed Test→OA.XF
OAU 2-position Damper Test→OA.DM
OAU
Wheel
Test→WHL
ERV Mode = Free Cooling
Wheel = stop-jog
ERV 2POS Damper = Open
OA CFM = Between Min CFM*
and 100 dependent on Econ Pos
Ex CFM = OA CFM - Ex CFM offset
ERV Mode = Defrost
Wheel = On
ERV 2POS Damper = Open
OA CFM = 0
Ex CFM = Min CFM* in effect
- Ex CFM offset
ERV Mode = ERV or DCV Mode
Wheel = On
ERV 2POS Damper = Open
OA CFM = Min CFM*
Ex CFM = OA CFM - Ex CFM offset
START
TEST
(RTU in test
mode)
COOL
(RTU in
Cool)
VENT
(RTU in Heat,
or Vent)
Is
economizer
open> than
5%?
Summary of Contents for /50HC 04-28
Page 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Page 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Page 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Page 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Page 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Page 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Page 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Page 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Page 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Page 141: ......