3
Cooling Capacities and Efficiencies
50GL-A
NET COOLING
CAPACITIES (kW)
STANDARD CFM/
L/s
NET COOLING
CAPACITY (Btuh)
EER
kW
24
6.9
800/378
23400
9.5
6.9
30
8.6
1000/472
29200
9.5
8.6
36
10.7
1200/567
36700
9.5
10.7
48
14.4
1600/756
49300
9.2
14.4
LEGEND
dB---
Sound Levels (decibels)
db
—Dry Bulb
wb
—Wet Bulb
{
Tested in accordance with U.S. Government DOE Department of Energy)
test procedures and/or AHRI Standards 210/240---2008.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard:
80
°
F (26.7
_
C) db, 67
°
F wb (19.4
_
C) indoor entering---air
temperature and 95
°
F db (35
_
C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and effi-
ciency information available from your retailer.
A--WEIGHTED SOUND POWER LEVEL (dBA)
MODEL
50GL-A
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
125
250
500
1000
2000
4000
8000
24
75
60.4
58.3
64.8
66.9
64.3
59.8
51.8
30
75
58.2
59.2
65.8
67.7
64.8
61.8
53.6
36
75
60.4
61.6
66.9
67.8
64.6
60.7
52.8
48
78
65.2
69.7
72.7
72.9
69.8
65.8
57.9
NOTE: Tested in accordance with AHRI Standard 270 (not listed in AHRI).