28 - COMMISSIONING
-
You can now restart the equipment and check that it is operating correctly.
-
Check the safety components.
It is recommended to note the operating readings (table below) for the equipment, indicating the serial number and all other required
data that appears on the identification plate. This enables the system efficiency to be checked and faults prevented.
Date/Time
CL2 operating readings
System start-up date:
Serial No.:
Installer:
Site of installation:
Model: 28
□
35
□
50
□
65
□
75
□
Compressor
Suction pressure
bar
Intake temperature
°C
Condensation pressure
bar
Condensing temperature
°C
Air-cooled condenser
Gas inlet temperature
°C
Liquid outlet temperature
°C
Air inlet temperature
°C
Air outlet temperature
°C
Nominal voltage
V
Voltage at terminals
V
Motor(s) input current
A
Mechanical inspection: tubes, fastenings.
Electrical connection tightness check
Clean the coil
Control check
75