![Carrier 48TM016 Installation, Start-Up And Service Instructions Manual Download Page 5](http://html.mh-extra.com/html/carrier/48tm016/48tm016_installation-start-up-and-service-instructions-manual_2561514005.webp)
5
NOTES:
1. Dimensions in (
) are in millimeters.
2. Refer to Fig. 4-6 for unit operating weights.
3. Remove boards at ends of unit and runners prior to rigging.
4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from
damage. Use bumper boards for spreader bars on all units.
5. Weights do not include optional economizer. Add 90 lb (41 kg) for economizer weight.
6. Weights given are for aluminum evaporator and condenser coil plate fins.
All panels must be in place when rigging.
Fig. 3 — Rigging Details
UNIT
48TM
MAXIMUM
SHIPPING WEIGHT
DIMENSIONS
A
B
lb
kg
ft-in.
mm
ft-in.
mm
016
1875
850
6-11
1
/
2
2121
4-0
1219
020
1925
873
6-11
1
/
2
2121
3-2
964
025
2035
923
6-11
1
/
2
2121
3-4
1016
028
2445
1109
6-11
1
/
2
2121
3-4
1016
Summary of Contents for 48TM016
Page 3: ...3 Fig 2A Roof Curb Details 48TM016 025 ...
Page 4: ...4 Fig 2B Roof Curb Details 48TM028 ...
Page 6: ...6 Fig 4 Base Unit Dimensions 48TM016 020 ...
Page 7: ...7 Fig 5 Base Unit Dimensions 48TM025 ...
Page 8: ...8 Fig 6 Base Unit Dimensions 48TM028 ...
Page 32: ...32 Fig 46 MoistureMi er Dehumidification Operation Diagram TXV Thermostatic Expansion Valve ...
Page 48: ...48 Fig 57 Typical Wiring Schematic 48TM016 020 208 230 V Shown ...
Page 49: ...49 Fig 58 Typical Component Arrangement ...
Page 56: ...56 Fig 60 EconoMi erIV Functional View ...
Page 59: ......