![Carrier 48TF004-007 Installation, Start-Up And Service Instructions Manual Download Page 56](http://html.mh-extra.com/html/carrier/48tf004-007/48tf004-007_installation-start-up-and-service-instructions-manual_2561092056.webp)
56
LEGEND FOR FIG. 54 — TYPICAL WIRING SCHEMATIC AND COMPONENT ARRANGEMENT
IMPORTANT: Refer to unit wiring label for actual unit wiring
information.
AHA
—
Adjustable Heat Anticipator
C
—
Contactor, Compressor
CAP
—
Capacitor
CC
—
Cooling Compensator
COMP —
Compressor Motor
ECON —
Economizer
EQUIP —
Equipment
FPT
—
Freeze Up Protection Thermostat
GND
—
Ground
HPS
—
High-Pressure Switch
HS
—
Hall-Effect Sensor
I
—
Ignitor
IDM
—
Induced-Draft Motor
IFC
—
Indoor Fan Contactor
IFM
—
Indoor (Evaporator) Fan Motor
IGC
—
Integrated Gas Unit Controller
LED
—
Light-Emitting Diode
LPS
—
Low-Pressure/Loss-of-Charge Switch
LS
—
Limit Switch
MGV
—
Main Gas Valve
MTR
—
Motor
OFM
—
Outdoor (Condenser) Fan Motor
OLR
—
Overload Relay
PL
—
Plug Assembly
QT
—
Quadruple Terminal
R
—
Relay
RS
—
Rollout Switch
SAT
—
Supply-Air Thermostat
SEN
—
Sensor
SW1
—
Switch Fully Open
SW2
—
Switch Fully Closed
SW3
—
Switch Min. Vent Position
SW4
—
Switch Max. Vent Position
TC
—
Thermostat-Cooling
TDR
—
Time-Delay Relay
TH
—
Thermostat-Heating
TRAN —
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire
or its equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostat: HH07AT170, 172, 174 and P272-2783 Subbase: HH93AZ176, 178 and
P272-1882, 1883.
4. Set heat anticipator at .14 amp. For units with 2 stages of heating, set stage two anticipator at
.14 amp.
5. Use copper conductors only.
6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power supply, disconnect BLK wire
from 230-v tap (ORN) and connect to 208-v tap (RED). Insulate end of 230-v tap.
Summary of Contents for 48TF004-007