49
Legend and Notes for Table 11
LEGEND:
BRKR
--- Circuit breaker
CO
--- Convenience outlet
DISC
--- Disconnect
FLA
--- Full load amps
LRA
--- Locked rotor amps
MCA
--- Minimum circuit amps
PE
--- Power exhaust
PWRD CO
--- Powered convenient outlet
UNPWR CO
--- Unpowered convenient outlet
NOTES
:
1. In compliance with NEC requirements for multimotor and
combination load equipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
3
3
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT
: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
48H
C
Summary of Contents for 48TC*D
Page 3: ...3 C10896 Fig 1 Unit Dimensional Drawing 17 Size Unit 48HC...
Page 4: ...4 C10897 Fig 1 Unit Dimensional Drawing 17 Size Unit cont 48HC...
Page 5: ...5 C10892 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units 48HC...
Page 6: ...6 C10893 Fig 2 Unit Dimensional Drawing 20 and 24 Size Units cont 48HC...
Page 7: ...7 C10900 Fig 3 Unit Dimensional Drawing 28 Size Unit 48HC...
Page 8: ...8 C10901 Fig 3 Unit Dimensional Drawing 28 Size Unit cont 48HC...
Page 11: ...11 C10954 Fig 6 Roof Curb Details 17 Size Unit 48HC...
Page 12: ...12 C10955 Fig 7 Roof Curb Details 20 and 24 Size Units 48HC...
Page 13: ...13 C10956 Fig 8 Roof Curb Details 28 Size Unit 48HC...
Page 27: ...27 C11140 Fig 38 PremierLink Wiring Schematic 48HC...
Page 28: ...28 C11141 Fig 39 PremierLink Wiring Schematic with Humidi MiZerR 48HC...
Page 37: ...37 C11142 Fig 58 RTU Open System Control Wiring Diagram 48HC...
Page 38: ...38 C11143 Fig 59 RTU Open System Control Wiring Diagram with Humidi MiZerR 48HC...
Page 51: ...51 48HC...