
36
Supply (Indoor) Fan Motor Protection
PERSONAL INJURY HAZARD
Failure to follow this WARNING can result in
personal injury.
Disconnect all electrical power when servicing the fan
motor. Apply appropriate lockout/tagout procedures.
!
WARNING
Motors with 2.9 and 3.7 bhp are equipped with an internal
overtemperature or protection device. The type of device
depends on the motor size. See Table 7.
The High Static option supply fan motor is equipped with
a pilot
−
circuit Thermix combination overtemperature/
overcurrent protection device. This device resets
automatically. Do not bypass this switch to correct
trouble. Determine the cause and correct it.
The Thermik device is a snap
−
action overtemperature
protection device that is embedded in the motor windings.
The Thermik can be identified by two blue wires
extending out of the motor control box. It is a pilot
−
circuit
device that is wired into the unit’s 24V control circuit.
When this switch reaches its trip setpoint, it opens the
24V control circuit and causes all unit operation to cease.
This device resets automatically when the motor windings
cool. Do not bypass this switch to correct trouble.
Determine the cause and correct it.
The External Overload Breaker is an overcurrent device
used on motors with a horsepower rating of 4.7 hp or
greater. This is a specially
−
calibrated circuit breaker that
is UL recognized as a motor overload controller. When
the current to the motor exceeds the circuit breaker
setpoint, the device opens all motor power leads to the
motor, shutting the motor down. Reset requires a manual
reset at the overload switch. This device (designated
IFCB) is located on the side of the supply fan housing,
behind the fan access panel. The Must Hold and Must Trip
values are listed on the side of the External Overload
Breaker.
Troubleshooting Supply Fan Motor Overload
Trips
The supply fan used in 48TC units is a forward
−
curved
centrifugal wheel. At a constant wheel speed, this wheel
has a characteristic that causes the fan shaft load to
DECREASE when the static pressure in the unit
−
duct
system increases and to INCREASE when the static
pressure in the unit
−
duct system decreases (and fan
airflow rate increases). Motor overload conditions
typically develop when the unit is operated with an access
panel removed, with unfinished duct work, in an
economizer
−
open mode, or a leak develops in the duct
system that allows a bypass back to unit return opening.
Table 7 – Overcurrent Device Type
Motor
Si
z
e
(bhp)
Overload
Device
Reset
1.7
Internal Linebreak
Automatic
2.4
Internal Linebreak
Automatic
2.9
Thermik
Automatic
3.7
Thermik
Automatic
4.7
External (circuit breaker)
Manual
Condenser Fan Motor Protection
The condenser fan motor is internally protected against
overtemperature.
Control Circuit, 24
−
V
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on the control
transformer TRAN. Reset is manual.
The factory
−
installed PremierLink Controller includes the
supply
−
air temperature (SAT) sensor. The outdoor air
temperature (OAT) sensor is included in the
FIOP/accessory EconoMi$er 2 package.
Refer to Fig. 44 for PremierLink
connection locations.
NOTE
: Refer to
PremierLink
Installation, Start
−
Up
and Configuration Instructions.
Have a copy of this
manual available at unit start
−
up.
Summary of Contents for 48TC 17 Series
Page 39: ...39 C10818 Fig 45 RTU OPEN Control Module ...
Page 83: ...83 APPENDIX IV WIRING DIAGRAMS cont C12616 Fig 74 48TC D17 D28 Power Diagram 208 230 3 60 ...
Page 84: ...84 APPENDIX IV WIRING DIAGRAMS cont C12266 Fig 75 48TC D17 D28 Power Diagram 460 3 60 ...
Page 85: ...85 APPENDIX IV WIRING DIAGRAMS cont C12618 Fig 76 48TC D17 D28 Power Diagram 575 3 60 ...
Page 92: ...92 APPENDIX IV WIRING DIAGRAMS cont C13767 Fig 83 RTU OPEN Wiring Diagram ...
Page 93: ...93 APPENDIX IV WIRING DIAGRAMS cont C13768 Fig 84 RTU OPEN Wiring Diagram with Humidi MiZer ...