TO LIGHT UNIT

(Units with Electro-Mechanical Control)

See Fig. 1 for location of gas valve. Refer to Fig. 2 while

proceeding with the following steps.

Step 1 —

Set room thermostat to the lowest temperature

setting and set SYSTEM switch to OFF position.

Step 2 —

Close the shutoff valve on the gas supply piping.

Step 3 —

Turn off the electrical supply to the unit and

install lockout tag.

Step 4 —

Open the heat section access panel.

Step 5 —

Move ON/OFF switch on the internal main gas

valve to the OFF position and wait 5 minutes.

Step 6 —

Move ON/OFF switch on internal main gas valve

to ON position.

Step 7 —

Close the heat section access panel.

Step 8 —

Remove lockout tag and turn on the electrical

supply to unit.

Step 9 —

Open the shutoff valve on the gas supply piping.

Step 10 —

Set room thermostat selector slightly above

room temperature and set system switch to HEAT position to
start the unit. The induced-draft combustion air fan will start.
Main burners light within 30 seconds. Indoor blower will start
within 60 to 90 seconds of main gas ignition.

Step 11 —

Set the temperature selector on room thermostat

to desired setting.

TO LIGHT UNIT

(Units With

ComfortLink™ Control)

See Fig. 1 for location of gas valve. Refer to Fig. 3 while

proceeding with the following steps.

Step 1 —

Turn off the unit by using the Scrolling Marquee

to put the unit into Service Test mode. The Scrolling Marquee
is located on the front of the unit control box behind the control
box and compressor access door. Thermostat inputs and remote
network commands are ignored when Service Test mode is
ON.
a. A password may be required to change Service Test

values depending on previous settings configured in the
unit. Default password is “1111.”

b. Press the

key until a blank screen is shown.

c. Use the arrow keys to scroll the red LED on the display

to the “Service Test” position and press

.

d. The control will display the Field Service Test Mode

(TEST) setting. Press

once to select the TEST

setting for configuration. Press

again for

“OFF” to begin flashing.

e. Use the arrow keys to change the configuration from

“OFF” to “ON,” then press

and

to

save the setting.

Step 2 —

Close the shutoff valve on the gas supply piping.

Step 3 —

Turn off the electrical supply to the unit and

install lockout tag.

Step 4 —

Open the heat section access panel.

Step 5 —

Move ON/OFF switch on the internal gas valve to

the OFF position and wait 5 minutes.

Step 6 —

Move ON/OFF switch on internal gas valve to

ON position.

Step 7 —

Close the heat section access panel.

1. Do not turn off the electrical power to unit without

first turning off the gas supply.

2. Before attempting to start the gas heating section,

familiarize yourself with all the procedures that must
be followed.

3. Never attempt to manually light the burners on the

unit with a match, lighter, or any other flame. If the
electric sparking device fails to light the burners, refer
to the shutdown procedures, then call your dealer as
soon as possible.

If you do not follow these instructions exactly, a fire or

explosion may result, causing property damage, injury, or
loss of life.

If the main burners fail to light, or the blower fails to come
on, shut down gas heating section and call your dealer for
service. Failure to follow these requirements could result in
serious personal injury.

1. Do not turn off the electrical power to unit without

first turning off the gas supply.

2. Before attempting to start the gas heating section,

familiarize yourself with all the procedures that must
be followed.

3. Never attempt to manually light the burners on the

unit with a match, lighter, or any other flame. If the
electric sparking device fails to light the burners, refer
to the shutdown procedures, then call your dealer as
soon as possible.

If you do not follow these instructions exactly, a fire or

explosion may result, causing property damage, injury, or
loss of life.

ESCAPE

ENTER

ENTER

ENTER

ENTER

ESCAPE

INDUCED
DRAFT
MOTOR

COMBUSTION
FAN HOUSING

MAIN GAS
VALVE

MAIN BURNER SECTION

HEAT EXCHANGER
SECTION

Fig. 1 — Typical Gas Heating Section

Summary of Contents for 48PG03

Page 1: ...mostat control use the Electro Mechanical Control procedures in this book For units with third party controls connected to the thermostat inputs refer to the third party con trol instructions for proc...

Page 2: ...ST setting Press once to select the TEST setting for configuration Press again for OFF to begin flashing e Use the arrow keys to change the configuration from OFF to ON then press and to save the sett...

Page 3: ...MAIN O F F ON C HI M R E P L A C E S C R EW L O O F F ON C HI M R E P L A C E S C R EW L O STEP 1 Fig 2 To Light Unit Units with Electro Mechanical Control STEP 5 STEP 4 STEP 3 STEP 2 STEP 8 STEP 7 S...

Page 4: ...s Inputs Outputs Configuration Time Clock Operating Modes Alarms Alarm Status ENTER MODE ESCAPE STEP 1 Fig 3 To Light Unit Units with ComfortLink Control STEP 5 STEP 4 STEP 3 STEP 2 STEP 8 STEP 7 STEP...

Page 5: ...unit control box behind the control box and compressor access door see Fig 6 Thermostat inputs and remote network commands are ignored when Service Test mode is ON a A password may be required to cha...

Page 6: ...6 STEP 1 Fig 4 To Shut Unit Off Units with Electro Mechanical Control STEP 7 STEP 6 STEP 5 STEP 4 STEP 3 STEP 2 LOCK OUT TAG ON OFF MAIN STEP 3 O F F ON C HI M R E P L A C E S C R EW L O...

Page 7: ...EP 7 STEP 6 STEP 5 STEP 4 STEP 3 STEP 2 LOCK OUT TAG ON OFF MAIN STEP 3 O F F ON C HI M R E P L A C E S C R EW L O Run Status Service Test Temperature Pressures Setpoints Inputs Outputs Configuration...

Page 8: ...d from the original installation Units with outdoor air capability have cleanable screens for the outdoor air These screens should be checked annually and cleaned as necessary Table 1 Indoor Air Filte...

Page 9: ...bearings so no field lubrica tion is necessary Indoor Fan Belt and Pulleys Periodically check the condition of the fan wheel s pulleys fan belt and the belt tension If there is any loose part or belt...

Page 10: ...open and unobstructed If these checks do not reveal the cause call your servicing dealer If your unit is not operating at all check the following list for easy solutions If using a thermostat check t...

Page 11: ......

Page 12: ...e or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 04 53480006 01 Printed in U S A Form 48PG 5SO Pg 12 8 05 Replaces 48PG 4SO Book 1 4...

Reviews: