ECONOMIZER SYSTEM
EconoMi$er2
The unit may be equipped with a factory-installed or accessory
(field-installed) EconoMi$er2 system. See Fig. 61 for compo
-
nent locations.
Economizers use direct-drive damper actuators.
Fig. 61 —
EconoMi$er2 Component Locations
Fig. 62 —
EconoMi$er2 with 4 to 20 mA Control Wiring
IMPORTANT: Any economizer that meets the econo
-
mizer requirements as laid out in California’s Title 24
mandatory section 120.2 (fault detection and diagnostics)
and/or prescriptive section 140.4 (life-cycle tests, damper
leakage, 5 year warranty, sensor accuracy, etc), will have
a label on the economizer. Any economizer without this
label does not meet California’s Title 24. The five year
limited parts warranty referred to in section 140.4 only
applies to factory installed economizers. Please refer to
your economizer on your unit.
IMPORTANT: The optional EconoMi$er
®
2 does not
include a controller. The EconoMi$er2 is operated by a 4 to
20 mA signal from an existing field-supplied controller. See
Fig. 62 for wiring information.
ECONOMI$ER2 PLUG
OUTSIDE AIR
TEMPERATURE SENSOR
4
3
5
2
8
6
7
1
10
11
9
12
PINK
VIOLET
BLACK
BLUE
YELLOW
RUN
RED
WHITE
ECONOMI$ER2 PLUG
DIRECT DRIVE
ACTUATOR
4-20mA
S
IGNAL
OAT
S
EN
S
OR
ACTUATOR
CONTROL
(4-20mA)
ACTUATOR
FEEDBACK
(2-10VDC)
TRAN
S
FORMER
GROUND
ORANGE
500 OHM
RE
S
I
S
TOR
Summary of Contents for 48JC04-06
Page 15: ...15 Fig 26 Condenser Fan Assembly Screw Pattern Sequence 1 2 3 4 5 NO SCREW Blank Tab...
Page 30: ...30 Fig 52 Integrated Gas Controller IGC Board RED LED STATUS...
Page 64: ...64 APPENDIX D WIRING DIAGRAMS Fig B 48JC 04 06 Control Wiring Diagram...
Page 65: ...65 APPENDIX D WIRING DIAGRAMS Fig C 48JC 04 06 Power Wiring Diagram 208 230 460 3 60...