background image

Cooling Cycle —

When operating in the cooling cycle,

your dual fuel heat pump will run until the indoor tempera-
ture is lowered to the level you have selected. On extremely
hot days, your dual fuel heat pump will run for longer pe-
riods at a time and have shorter ‘‘off’’ periods than on mod-
erate days.

The following are typical conditions that add extra heat

and/or humidity to your home. Your heat pump will work
longer to keep your home comfortable under these
conditions:

• Entrance doors are frequently opened and closed
• Laundry appliances are being operated
• A shower is running
• More than the usual number of people are present in the

home

• More than the normal number of electric lights are in

use

• Drapes are open on the sunny side of the home

Heating Cycle —

With the SYSTEM switch of your in-

door thermostat set to the HEAT position, the dual fuel heat
pump will operate in its heating mode until room tempera-
ture is raised to the level you have selected. Of course, the
heating unit will have to operate for longer periods to main-
tain a comfortable environment on colder days and nights
than on moderate ones.

DEFROST CYCLE — When your dual fuel heat pump is
providing heat to your home and the outdoor temperature
drops below 45 degrees Fahrenheit, moisture may begin to
freeze on the surface of the outdoor coil. If allowed to build
up, this ice would impede airflow across the coil and reduce
the amount of heat absorbed from the outside air. So, to main-
tain energy-efficient operation, your dual fuel heat pump has
an automatic defrost cycle.
Depending on which model you have, the defrost cycle starts
at a preset time interval of 30, 50, or 90 minutes. However,
it may be reset. Defrost will start at the preset time only if
the ice is sufficient to interfere with normal heating
operation.
After the ice is melted from the outdoor coil, or after a maxi-
mum of 10 minutes in the Defrost mode, the unit will au-
tomatically switch back to normal heating operation.
Do not be alarmed if steam or fog appears at the outdoor
unit during the defrost cycle. Water vapor from the melting
ice may condense into a mist in the cold outside air.

EMERGENCY HEAT — The EMERGENCY HEAT setting
on your thermostat refers to supplementary gas heating that
is included in your home comfort system. Operation of the
EMERGENCY HEAT source may be required if the heat
pump malfunctions.

The red light on your thermostat will glow if the

SYSTEM switch is moved from HEAT to the EMER-
GENCY HEAT setting. This indicates that the heat pump is
off and the supplemental gas heating is selected for
operation.

Also, your particular model of heat pump may include a

Service Sentry™ circuit, which is used with a thermostat that
includes a red warning light. The red warning light will glow
if the compressor malfunctions. Call your dealer for imme-
diate service if you suspect trouble.

TO LIGHT UNIT

Your dual fuel heat pump is equipped with an automatic

direct spark ignition and power combustion blower.

Do not attempt to light by hand; personal injury may
result.

1. Do not turn off the electrical power to unit without

first turning off the gas supply.

2. Before attempting to start the gas heating section, fa-

miliarize yourself with all the procedures that must
be followed.

If you do not follow these instructions exactly, a fire or
explosion may result, causing property damage, injury,
or loss of life.

Refer to Fig. 2. See Fig. 3 for location of gas valve. Refer

to Fig. 4 while proceeding with the following steps.

Step 1 —

Set the temperature selector on room thermo-

stat to the lowest temperature setting and set SYSTEM switch
to EM HEAT.

Step 2 —

Close the external manual shutoff valve.

Step 3 —

Turn off the electrical supply to the unit.

Step 4 —

Remove the burner access panel with a

5

16

-in.

nut driver.

Step 5 —

Turn the control dial on the internal gas valve

counterclockwise

to the OFF position and wait

5 minutes.

Step 6 —

Turn the control dial on the internal gas valve

clockwise

to the ON position.

Step 7 —

Replace the burner access panel.

Step 8 —

Turn on the electrical supply to unit.

Step 9 —

Open the external manual shutoff valve.

Fig. 1 — Typical Thermostat

3

Summary of Contents for 48HX

Page 1: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions...

Page 2: ...lectronic air cleaners and or humidifiers offer the added benefits of having the air continuously cleaned year round and humidi fied during the winter season Your dual fuel heat pump will remove humid...

Page 3: ...on Do not be alarmed if steam or fog appears at the outdoor unit during the defrost cycle Water vapor from the melting ice may condense into a mist in the cold outside air EMERGENCY HEAT The EMERGENCY...

Page 4: ...on the internal gas valve counterclockwise to the OFF position Step 6 Replace the burner access panel Step 7 Restore electrical power to the unit and set SYS TEM switch to COOL to ensure operation of...

Page 5: ...poke sticks screwdrivers or any other object into revolving fan blades Severe bodily injury may result The fan must be kept free of all obstructions to en sure proper cooling Contact your dealer for...

Page 6: ...STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 STEP 7 STEP 8 STEP 9 STEP 10 Fig 4 To Light Unit 6...

Page 7: ...STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 STEP 7 Fig 5 To Shut Unit Off 7...

Page 8: ...age for your unit BEFORE YOU CALL FOR SERVICE CHECK FOR SEVERAL EASILY SOLVED PROBLEMS If insufficient heating or cooling is suspected Check for sufficient airflow Check the air filter for dirt Check...

Page 9: ...DETACH AND MAIL PRODUCT REGISTRATION 9...

Page 10: ...10...

Page 11: ...11...

Page 12: ...acturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 111 Catalog No 564 908 Printed in U S A...

Reviews: