49
FIOP MOISTUREMISER DEHUMIDIFICATION PACKAGE
STATIC PRESSURE DROP
(in. wg)
EVAPORATOR-FAN MOTOR EFFICIENCY
*Single phase/3 phase.
NOTE: Convert bhp to watts using the following formula:
UNIT SIZE
48HJ
UNIT NOMINAL
TONS
CFM PER TON
300
400
500
004
3
.04
.07
.09
005
4
.07
.12
.15
006
5
.09
.15
.21
007
6
.12
.20
.28
008
7
1
/
2
.08
.13
.18
009
8
1
/
2
.10
.15
.22
012
10
.08
.13
.18
014
12
1
/
2
.11
.18
.26
FIOP — Factory-Installed Option
UNIT SIZE
48HJ
EFFICIENCY%
004,005
75
006*
74/84
007
84
008,009
80
012
85
014
87
watts =
bhp (746)
motor efficiency
0.25
0.20
0.15
0.10
0.05
0.00
0
500
1000
1500
2000
FLOW (CFM)
ST
A
TIC PRESSURE (in. wg)
3 TO 6 TON
7 1/2 TO 12 1/2 TON
DURABLADE ECONOMIZER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS — 48HJ004-007
DURABLADE ECONOMIZER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS — 48HJ008-014
ECONOMI$ER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS