background image

46

2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.

The suction and discharge pressure levels should now move to

their normal start-up levels.

NOTE

: When the compressor is rotating in the wrong direction,

the unit makes more noise and does not provide cooling.

Step 10

Cooling

Set the space thermostat to the OFF position. Set the system

selector switch at COOL position and the fan switch at AUTO
position. Adjust the thermostat to a setting below room

temperature. The compressor starts when contactor closes.
Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The

compressor will shut off. Evaporator fan will shut off after a
30--second delay.
To Shut Off Unit -- Set the system selector switch at OFF
position. Resetting the thermostat at a position above room

temperature shuts off the unit temporarily until the space

temperature exceeds the thermostat setting. Units are equipped
with a Cycle-LOC

protection device. The unit shuts down on

any safety trip and remains off; an indicator light on the
thermostat comes on. Check the reason for the safety trip.

Step 11

Main Burners

Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move
thermostat set point above room temperature and verify that the

burners light and evaporator fan is energized. Check heating

effect, then lower the thermostat setting below the room
temperature and verify that the burners and evaporator fan turn

off.
Refer to Tables 37 and 38 for the correct orifice to use at high

altitudes.

Table 37—Altitude Compensation*

48HJ004--007, 48HE003--006 Standard Units

ELEVATION

(ft)

72,000 AND

115,000 BTUH

NOMINAL INPUT

150,000 BTUH

NOMINAL INPUT

Natural

Gas

Orifice

Size†

Liquid

Propane

Orifice

Size†

Natural

Gas

Orifice

Size†

Liquid

Propane

Orifice

Size†

0-2,000

33

43

30

37

2,000

36

44

31

39

3,000

36

45

31

40

4,000

37

45

32

41

5,000

38

46

32

42

6,000

40

47

34

43

7,000

41

48

35

43

8,000

42

49

36

44

9,000

43

50

37

45

10,000

44

50

39

46

11,000

45

51

41

47

12,000

46

52

42

48

13,000

47

52

43

49

14,000

48

53

44

50

*As the height above sea level increases, there is less oxygen per cubic

foot of air. Therefore, heat input rate should be reduced at higher alti-

tudes.

†Orifices available through your Carrier distributor.

Table 38—Altitude Compensation* —

48HJ004-006, 48HE003--006 Low NOx Units

ELEVATION

(ft)

60,000 AND

90,000 BTUH

NOMINAL INPUT

120,000 BTUH

NOMINAL INPUT

Natural

Gas

Orifice

Size†

Liquid

Propane

Orifice

Size†

Natural

Gas

Orifice

Size

Liquid

Propane

Orifice

Size†

0-2,000

38

45

32

42

2,000

40

47

33

43

3,000

41

48

35

43

4,000

42

49

36

44

5,000

43

49

37

45

6,000

43

50

38

45

7,000

44

50

39

46

8,000

45

51

41

47

9,000

46

52

42

48

10,000

47

52

43

49

11,000

48

53

44

50

12,000

49

53

44

51

13,000

50

54

46

52

14,000

51

54

47

52

*As the height above sea level increases, there is less oxygen per cubic

foot of air. Therefore, the input rate should be reduced at higher alti-

tudes.

†Orifices are available through your local Carrier distributor.

Step 12

Heating

1. Purge gas supply line of air by opening union ahead of the

gas valve. If gas odor is detected, tighten union and wait 5
minutes before proceeding.

2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan

switch at AUTO or ON position. Set heating temperature

lever above room temperature.

4. The induced-draft motor will start.
5. After a call for heating, the main burners should light

within 5 seconds. If the burner does not light, then there is
a 22-second delay before another 5-second try. If the

burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout.

To reset the control, break the 24 v power to W1.

6. The evaporator-fan motor will turn on 45 seconds after

burner ignition.

7. The evaporator-fan motor will turn off in 45 seconds after

the thermostat temperature is satisfied.

8. Adjust airflow to obtain a temperature rise within the

range specified on the unit nameplate.

NOTE

: The default value for the evaporator-fan motor on/off

delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to

180

seconds. When one flash of the LED (light-emitting diode) is
observed, the evaporator-fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle during the
evaporator on delay, the time period of the on delay for the next

cycle will be 5 seconds less than the time at which the switch

tripped. (Example: If the limit switch trips at 30 seconds, the
evaporator-fan on delay for the next cycle will occur at 25

seconds.) To prevent short-cycling, a 5-second reduction will
only occur if a minimum of 10 minutes has elapsed since the last

call for heating.
The evaporator-fan off delay can also be modified. Once the call
for heating has ended, there is a 10-minute period during which

the modification can occur. If the limit switch trips during this
period, the evaporator-fan off delay will increase by 15 seconds.

48H

E,

H

J

Summary of Contents for 48HE003

Page 1: ...intenance functions of cleaning coils and filters and replacing filters All other operations should be performed by trained service personnel When working on air conditioning equipment observe precaut...

Page 2: ...horizontal applications field supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges Insulate and weatherproof all external d...

Page 3: ...e 7 Direction of airflow 8 Connector packages CRBTMPWR001A01 and 002A01 are for thru the curb type gas Packages CRBTMPWR003A01 and 004A01 are for thru the bottom type gas connections CONNECTOR PKG ACC...

Page 4: ...local codes and Section 5 3 Air for Combustion and Ventilation NFGC National Fuel Gas Code ANSI American National Standards Institute Z223 1 1984 and addendum Z223 1a 1987 In Canada installation must...

Page 5: ...and a 48 ft long pipe would have a minimum of 6 support beams PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury death and property damage All panels must be in plac...

Page 6: ...6 C06112 Fig 8 48HJ004 007 Base Unit Dimensions 48HE HJ...

Page 7: ...7 C06113 Fig 9 48HE003 006 Base Unit Dimensions 48HE HJ...

Page 8: ...ases must be balanced within 2 and the current within 10 Use the formula shown in Tables 3 and 4 Note 3 to determine the percent voltage imbalance Operation on improper line voltage or excessive phase...

Page 9: ...tor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter A B in Std 1 9 2 9 1 9 2 0 2 4 3 4 2 4 3 4 Hi Static 2 8 3 8 2 8 3 8 3 4 4 4 3 4 3 4 Nominal Motor...

Page 10: ...M 81 HJM 81 HJN 80 7 HJN 80 7 Temperature Rise Range HJE 25 55 HJD 25 25 HJD 25 55 HJD 25 55 HJF 55 85 HJE 35 65 HJE 35 65 HJE 35 65 HJF 50 80 HJF 50 80 HJF 50 80 HJH 25 55 HJG 25 55 HJG 25 55 HJK 55...

Page 11: ...7 Total Face Area sq ft 3 5 3 9 3 9 3 9 EVAPORATOR FAN Centrifugal Type Belt Drive Quantity Size in 1 10 x 10 1 10 x 10 1 10 x 10 1 10 x 10 Nominal Cfm 800 1200 1600 2000 Maximum Continuous Bhp Std 0...

Page 12: ...25 55 HED 25 25 HED 25 55 HEE 25 65 HEF 55 85 HEE 35 65 HEE 35 65 HEF 50 80 HEF 50 80 HEH 25 55 HEG 25 55 HEG 25 55 HEK 55 85 HEH 35 65 HEH 35 65 HEK 50 80 HEK 50 80 HEM 20 50 HEL 20 50 HEL 20 50 HEN...

Page 13: ...S2 THERMOSTAT DIPSWITCH SETTINGS R G Y1 Y2 W1 W2 C IPD X ON OFF A B C D LEGEND NOTE Underlined letter indicates active thermostat output when configured for A C operation Field Wiring C06008 Fig 13 L...

Page 14: ...1 145 460 3 60 STD 414 508 1 7 1 45 1 0 8 0 3 2 2 NO 11 9 15 11 6 53 YES 14 6 20 14 1 55 HS 2 6 NO 12 3 15 12 1 67 YES 15 0 20 14 6 70 575 3 60 STD 518 632 1 6 1 38 1 0 6 0 3 1 9 NO 10 1 15 9 9 44 YES...

Page 15: ...6 15 10 54 YES 13 3 15 13 56 HS 2 6 NO 11 0 15 11 68 YES 13 7 15 13 70 575 3 60 STD 518 632 1 6 4 40 1 0 4 0 3 1 9 NO 10 3 15 10 45 YES 12 5 15 12 47 HS 2 0 NO 10 4 15 10 52 YES 12 6 15 12 53 HumidiMi...

Page 16: ...STD 187 254 2 17 6 125 2 1 4 0 6 10 6 NO 53 0 60 56 341 YES 59 0 70 61 345 HS 15 0 NO 57 4 70 61 364 YES 63 4 70 66 369 460 3 60 STD 414 508 2 8 3 62 5 2 0 7 0 3 4 8 NO 24 9 30 26 171 YES 27 6 30 29 1...

Page 17: ...high voltage and low voltage wiring 3 A field supplied relay must be installed between the Thermidistat and the Humidi Mizer circuit recommended relay HN612KK324 See Fig 19 The relay coil is connected...

Page 18: ...V Unit Shown ROOF TOP UNIT R C Y1 Y2 G W1 W2 PINK PINK RED 24V FROM HUMIDI MIZER SYSTEM LLSV R1 TS TATWIRES LCT R C Y1 Y2 G W1 W2 DEHUM OC R1 HUMIDI MIZER SYSTEM PINK LTLO CB 3 2 AMPS LEGEND CB Circu...

Page 19: ...ly air duct as required by local codes Drill or punch a 1 2 in hole in the flange or duct Use two field supplied self drilling screws to secure the sensor probe in a horizontal orientation NOTE The se...

Page 20: ...r Air Temperature sensor CRTEMPSN001A00 Included with factory installed PremierLink control field supplied and field installed with field installed PremierLink control NOTES 1 CO2 Sensors Optional 33Z...

Page 21: ...12 1 2 3 4 5 6 7 8 9 10 11 12 PNK PNK VIO VIO GRA ORN PNK PNK GRA GRA GRA SAT BRN ORN BLK RED Space Temp Set Point Adjustment Indoor Air Quality Sensor OAT PNK VIO YEL YEL BLU BLU Economi er2 4 20mA...

Page 22: ...in high outdoor air enthalpy state Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy 3 Remove sensor mounted on back of control and locate in outside air stream C0601...

Page 23: ...ef damper in place 6 Insert the hood divider between the hood sides See Fig 34 and 35 Secure hood divider with 2 screws on each hood side The hood divider is also used as the bottom filter rack for th...

Page 24: ...nstalled Differential Dry Bulb CRTEMPSN002A00 Single Enthalpy HH57AC078 Differential Enthalpy HH57AC078 and CRENTDIF004A00 CO2 for DCV Control using a Wall Mounted CO2 Sensor 33ZCSENCO2 CO2 for DCV Co...

Page 25: ...R ASSEMBLY RED WHITE ECONOMISER2 PLUG DIRECT DRIVE ACTUATOR 2 NOTES 1 Switch on actuator must be in run position for economizer to operate 2 PremierLink control requires that the standard 50HJ540569 o...

Page 26: ...ame mounting location See Fig 29 Mount the return air enthalpy sensor in the return air duct See Fig 44 Wiring is provided in the EconoMi er IV wiring harness See Fig 36 The outdoor enthalpy changeove...

Page 27: ...oss terminals TR and TR1 5 Carefully adjust the minimum position potentiometer until the measured supply air temperature matches the calculated value 6 Reconnect the mixed air sensor to terminals T an...

Page 28: ...In order to have the CO2 sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to...

Page 29: ...ing processes are more than adequate to remove the humidity loads for most commercial applications If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level an ene...

Page 30: ...4 20 mA 0 1100 1100 50 5 Proportional 20 0 10V 4 20 mA 0 900 900 50 6 Exponential 15 0 10V 4 20 mA 0 1100 1100 50 7 Exponential 20 0 10V 4 20 mA 0 900 900 50 8 Health Safety Proportional 0 10V 4 20 mA...

Page 31: ...30 4 9 460 2 2 575 2 2 006 Single 1 30 1650 208 230 9 2 Three 2 40 2120 208 230 6 7 460 3 0 575 3 0 007 Three 2 40 2120 208 230 6 7 460 3 0 575 3 0 LEGEND Bhp Brake Horsepower Extensive motor and elec...

Page 32: ...se units ensures that the full range of the motor can be utilized with confidence Using the fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure Unit warr...

Page 33: ...r rpms require field supplied drive Table 18 Fan Performance 48HJ004 48HE004 Vertical Discharge Units High Static Motor Belt Drive AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bh...

Page 34: ...3 730 1027 0 89 888 1101 1 05 1040 1170 1 20 1189 1800 885 0 66 652 978 0 83 826 1060 1 00 994 1133 1 16 1157 1900 923 0 75 745 1014 0 94 930 1093 1 11 1109 2000 962 0 85 847 1049 1 05 1043 AIRFLOW CF...

Page 35: ...1 64 1627 1376 1 79 1779 1428 1 94 1930 1479 2 09 2078 1900 1293 1 63 1620 1350 1 79 1784 1405 1 96 1946 1457 2 12 2106 1506 2 28 2265 2000 1323 1 79 1776 1380 1 96 1950 1434 2 13 2123 1486 2 31 2293...

Page 36: ...an Performance 48HJ006 48HE006 Vertical Discharge Units High Static Motor Belt Drive AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Wa...

Page 37: ...1429 1 96 1736 1503 2 19 1945 2600 1305 1 63 1448 1390 1 89 1677 1468 2 14 1900 1540 2 38 2117 2700 1348 1 80 1602 1431 2 07 1841 1507 2 33 2073 2800 1392 1 99 1768 1472 2 27 2016 2900 1435 2 19 1945...

Page 38: ...Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1406 1 43 1273 1475 1 58 1403 1540 1 72 1531 1601 1 87 1657 1660 2 00 1780 1900 1438 1 58 1401 1505 1 73 1541 1569 1 89 1678...

Page 39: ...Fan Performance 48HJ004 48HE004 Horizontal Discharge Units High Static Motor Belt Drive AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp...

Page 40: ...atts Rpm Bhp Watts Rpm Bhp Watts 1200 643 0 23 234 762 0 34 343 859 0 46 458 944 0 58 579 1020 0 71 705 1300 675 0 28 277 790 0 40 394 886 0 52 517 969 0 65 644 1044 0 78 777 1400 707 0 33 326 819 0 4...

Page 41: ...98 867 1206 1 11 986 1279 1 25 1111 2000 1001 0 84 744 1085 0 96 855 1163 1 09 972 1238 1 23 1095 2100 1043 0 96 850 1123 1 09 965 1199 1 22 1086 2200 1085 1 09 966 1162 1 22 1086 2300 1127 1 23 1092...

Page 42: ...l other rpms require field supplied drive Table 33 Fan Performance 48HJ006 48HE006 Horizontal Discharge Units High Static Motor Belt Drive AIRFLOW CFM EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1...

Page 43: ...2 24 1990 2500 1196 1 51 1345 1273 1 73 1538 1345 1 96 1738 1412 2 19 1945 2600 1238 1 69 1497 1312 1 91 1697 1382 2 14 1904 1448 2 38 2117 2700 1280 1 87 1660 1352 2 10 1867 1420 2 34 2081 2800 1322...

Page 44: ...1 4 1 6 1 8 2 0 Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1322 1 56 1382 1388 1 77 1568 1451 1 98 1762 1510 2 21 1962 1568 2 44 2169 1900 1351 1 68 1495 1416 1 90 168...

Page 45: ...with water to ensure proper drainage d Make sure that all tools and miscellaneous loose parts have been removed START UP Step 1 Unit Preparation Make sure that the unit has been installed in accordan...

Page 46: ...NOMINAL INPUT Natural Gas Orifice Size Liquid Propane Orifice Size Natural Gas Orifice Size Liquid Propane Orifice Size 0 2 000 38 45 32 42 2 000 40 47 33 43 3 000 41 48 35 43 4 000 42 49 36 44 5 000...

Page 47: ...ill be energized and deenergized If field installed accessory CO2 sensors are connected to the EconoMi er IV control a demand controlled ventilation strategy will begin to operate As the CO2 level in...

Page 48: ...e S Indoor fan has been on for at least 30 seconds S The SPT SAT and OAT inputs must have valid readings S OAT must be less than 75_F S OAT must be less than SPT S Enthalpy must be LOW may be jumpered...

Page 49: ...n the space condition is satisfied and HS1 is deenergized the IFM stops after a 45 second time off delay unless in the occupied mode The fan will run continuously in the occupied mode as required by n...

Page 50: ...em sequence of operation SERVICE ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death When sevicing unit shut off all electrical power to unit and install lockou...

Page 51: ...ar at the start of the cooling season In winter keep the drain dry or protect it against freeze up filters Clean or replace at the start of each heating and cooling season or more often if operating c...

Page 52: ...er evacuating system to 500 microns weigh in the specified amount of refrigerant Refer to Table 1 or 2 and unit information plate Low charge cooling Using Cooling Charging Charts Fig 60 63 vary refrig...

Page 53: ...ing Charging Chart 48HJ005 with Optional Humidi MiZer Adaptive Dehumidification System NOTE When using the charging charts it is important that only the subcooling reheat dehumidification coil liquid...

Page 54: ...with Optional Humidi MiZer Adaptive Dehumidification System C06146 Fig 67 Cooling Charging Chart 48HJ007 with Optional Humidi MiZer Adaptive Dehumidification System TO USE COOLING CHARGING CHART STAN...

Page 55: ...ure Example Fig 64 Leaving Condenser Pressure 250 psig Leaving Condenser Temperature 105 F NOTE When using the charging charts it is important that only the subcooling reheat dehumidification coil liq...

Page 56: ...LED Light Emitting Diode A 3 second pause exists between LED error code flashes If more than one error code exists all applicable codes will be displayed in numeri cal sequence Indicates a code that i...

Page 57: ...EE F005 48HED E F006 C06154 Fig 74 Spark Gap Adjustment Cleaning and Adjustment 1 Remove burner rack from unit as described above 2 Inspect burners and if dirty remove burners from rack 3 Using a soft...

Page 58: ...egrated Gas Unit Controller LPS Low Pressure Switch LS Limit Switch MGV Main Gas Valve Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To indic...

Page 59: ...r IV preparation procedure has been performed 2 Ensure terminals AQ and AQ1 are open The LED for both DCV and Exhaust should be off The actuator should be fully closed 3 Connect a 9 v battery to AQ po...

Page 60: ...nadequate airflow to unit Check operation of indoor evaporator fan motor and that supply air temperature rise agrees with range on unit nameplate information Ignition Lockout LED 5 Flashes Unit unsucc...

Page 61: ...t Table 43 Humidi MiZer Adaptive Dehumidification System Subcooling Mode Service Analysis PROBLEM CAUSE REMEDY Subcooling Mode Liquid Reheat Will Not Energize No power to control transformer from evap...

Page 62: ...ce Restriction in refrigerant system Locate restriction and remove Compressor Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermos...

Page 63: ...ulating between closed and DCV maximum On Off On Off Off Off Off Off Low Free Cooling LED On High On On On Off Modulating Modulating On Off Off Off Off Off Off Off For single enthalpy control the modu...

Page 64: ...HARP METAL EDGES j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS III START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3 TEMP...

Reviews: