35
Space Relative Humidity Sensor or Humidistat
Connections —
NOTE
: The accessory space relative humidity sensor and
humidistat are not available for single phase (--3 voltage
code) models.
Space Relative Humidity Sensor connections:
The
accessory space relative humidity sensor (33ZCSENSRH-01)
is installed on an interior wall to measure the relative
humidity of the air within the occupied space.
The use of a standard 2 X 4 inch electrical box to
accommodate the wiring is recommended for installation.
The sensor can be mounted directly on the wall, if
acceptable by local codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
permanent damage to the sensor.
DO NOT clean or touch the sensing element with
chemical solvents as they can permanently damage
the sensor.
CAUTION
!
UNIT PERFORMANCE HAZARD
Failure to follow this caution will result in inaccurate
sensor readings.
DO NOT mount the sensor in drafty areas such as near
heating or air--conditioning ducts, open windows, fans,
or over heat sources such as baseboard heaters,
radiators, or wall--mounted dimmers. Sensors mounted
in those areas will produce inaccurate readings.
CAUTION
!
If the sensor is installed directly on a wall service, install the
humidity sensor using 2 screws and 2 hollow wall anchors
(field supplied). Do not over tighten screws. See Fig. 60.
SW2
1
2
3
4
5
6
ON
Io
Vin
Gnd
Vo
MOUNTING
HOLES
WIRING
OPENING
C11084
Fig. 60 -- Space Relative Humidity Sensor Installation
The sensor must be mounted vertically on the wall. The
Carrier logo should be orientated correctly when the
sensor is properly mounted.
Avoid corner locations. Allow at least 4 ft between the
sensor and any corner. Airflow near corners tends to be
reduced, resulting in erratic sensor readings. The sensor
should be vertically mounted approximately 5 ft up from
the floor, beside the space temperature sensor.
For wiring distances up to 500 feet, use a 3--conductor, 18
or 20 AWG cable. ACCN communication cable can be
used, although the shield is not required. The shield must
be removed from the sensor end of the cable if this cable
is used. See Fig. 61 for wiring details.
Io
Vo
Vin Gnd
BLACK
RED
TB1-7
TB1-13
C11180
Fig. 61 -- Space Relative Humidity Sensor Connection
The power for the sensor is provided by the PremierLink
control on terminal J5--4 (+33 to +35vdc).
To wire the sensor:
1. At the sensor, remove 4 inches fo the jacket from the
cable. Strip
¼
inch of insulation from each conductor.
Route the cable through the wire clearance opening in
the center of the sensor. See Fig. 60.
2. Connect a field--supplied BLACK wire to the sensor
screw terminal marked Vin.
3. Connect a field--supplied RED wire into the sensor
screw terminal marked Io.
4. Connect the field--supplied RED wire from the sensor
to TB1--13.
5. Connect the field--supplied BLACK wire from the
sensor to TB1--7.
Smoke Detector/Fire Shutdown (FSD) —
This function is available only when PremierLink is
configured for (Space) Sensor Mode. The unit is
factory--wired for PremierLink FSD operation when
PremierLink is factory--installed.
On 48HC units equipped with factory--installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s CTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The PremierLink
communicates the smoke detector’s tripped status to the
CCN building control. See Figs. 48 and 49, PremierLink
wiring schematics.
48H
C
Summary of Contents for 48HC Series
Page 24: ...24 C12251 Fig 42 ComfortLink Control Wiring Diagram 48HC 3 5 Ton Units 48HC ...
Page 27: ...27 C12254 Fig 45 48HC ComfortLink with Humidi MiZer Power Wiring Diagram 575V 3 Ph 60 Hz 48HC ...
Page 29: ...29 C101145 Fig 48 PremierLink Wiring Schematic 48HC ...
Page 30: ...30 C101146 Fig 49 PremierLink Wiring Schematic with Humidi MiZerR 48HC ...
Page 39: ...39 C101147 Fig 69 RTU Open System Control Wiring Diagram 48HC ...
Page 40: ...40 C101148 Fig 70 RTU Open System Control Wiring Diagram with Humidi MiZerR 48HC ...